Atek ALC 77-T User manual

73,5X73,5 MM DIMENSIONS
2 ROW, 7 DIGITS DISPLAY
5 KHZ INPUT FREQUENCY
COUNTING A AND B SIGNAL
2 PIECES DOUBLE RELAY OUTPUT
DECIMAL BETWEEN 1ST AND 6TH STEP POINT
5 VDC OR 12 VDC SENSOR SUPPLY OUTPUT
ENTERING THE OFFSET VALUE
PASSWORD SECURITY
DISPLAY RANGE: -999999....9999999
PROCESS CONTROL DEVICE
ALC 77-T
USER
MANUAL

INDEX
1. TECHNICAL FEATURES……….………….……………………………………………………………………………………….…1
2. CONNECTIONS…………….………………..………………………………………………………………………………………... 2
3. DESCRIPTION OF FRONT PANEL ……………………………………………………………………………………………… 3
4. DEVICE PROGRAMMING ……………………..…………………………………………………………………………………. 4
4.1. Entering Set Value to Device (set)……………………………………………………………………………….. 4
4.2. Selection Of Input Type -Forward/Backward- (Cnt_typ)………………………….…………………… 5
4.3. Entering of Constant (const)…………..………………………………………………………………………….…5
4.4. Selection of Point Position (point).………………..………………………………………………….……….…6
4.5. Selection Of Sample Time (SAMP.time)……………………………………………..………………………… 6
4.6. Selection Of Time Unit (time.bas)………………………………………………………………………………… 7
4.7. Relay Output Mode (output)………………………………………………………………………………………… 7
4.8. Relay Output Time (tout)………………………………………….……………………………………………..….. 8
4.9. Relay output Positions (out)…………..………………………………………………….………………………… 8
4.10. Activating The Hold Input (hold)……………………..…………………………………………………………… 8
4.11. Selection Of Sensor (NPN/PNP) Type (senstyp)………….………………………………………………… 9
4.12. Return To Factory Defaults (factory)…………..………………………………………………………………. 9
4.13. Password Protection (code_in).…….……………………………………………………………………………. 9
4.14. ANNEX A –Graphics of Relay Output Types (out menu)………….………………………………….. 11
5. CERTIFICATE OF WARRANTY…………………………………………………………………………………………………… 12

73,5 mm
73,5 mm
69 mm
69 mm
ELECTRICAL CHARACTERISTICS
Supply Voltage
24 VAC/DC 50/60 Hz
85-265 VAC 50/60 Hz
Power Consumption
5.5 VA / 4.4 W Max
Sensor Supply Voltage
5 VDC 100 mA (for TTL Sensor)
12 VDC 100 mA (for Push-Pull Sensor)
Connection
2,5 mm² screw-clemens
Inputs
A/B Encoder Pulse Inputs (600 KHz speed reading)
Hold Input
Outputs
2 pieces 250 VAC 3A (for Resistive Load) Relays
Serial Communication
RS-232 (Optional)
PHYSICAL CHARACTERISTICS
Dimensions
73,5 x 73,5 x 96 mm
Weight
300 gr.
Mounting
Upper and lower legs are fixed to the clipboard.
Relative Humudity
%80 up to 31 °C , %50 up to 40 °C
Storage Temperature
-10 and 60 °C
Operating Temperature
0 and 50 °C
Protection Class
IP 60 Front Panel, IP 20 Back panel
DIMENSIONS
Panel Dimensions:
1. TECHNICAL FEATURES
- 1 -

+
-
+
-
L
N
Supply Voltage
24 VAC / DC or
85 / 265 VAC
GND
+5 Vdc or +12 Vdc
A Input of Counting Signal
B Input of Counting Signal
Z Input of Reset
Input of Hold
COM
NO
NC
COM
NO
NC
OUT 2
OUT 1
Ground of Sensor
Ground
SAFETY WARNINGS
1. Follow the instructions and warnings in the user guide.
2. Please check the type of power supply before connects energy to the device.
3. Please the device mounted on panel against dangers of fall, snap, shake during working.
4. Make Sensor connections without energy on the device; do not connect in any way during
operation.
5. Make sure that is shielded cables between device and sensor.
6. Do not leave the device exposed to a heat source (solar, heater etc.)
7. ALC77 industrial control device is not suitable for use in the external environment, Use only
room conditions.
8. Wipe with a damp cloth to clean the device, do not use water, thinner etc.
9. Comply with the limit values specified in the technical specifications for relay outputs.
10. The device cannot be changed by the user in the event of a fault, Please contact our technical
service in case of failure.
2. CONNECTIONS
12
13
14
15
16
17
18
19
20
21
22
1
2
3
4
5
6
7
8
9
10
11
- 2 -

3. DESCRIPTION OF FRONT PANEL
ALC77 device operates in 2 different modes:
Programming mode : Specifies the function used during programming.
Operating mode : Specifies the function used during operating.
Display and Position LEDs
1. 7 Digit LED Display (9,2mm) at Operating mode: Indication of counting
At programming mode: Indication of program parameter
2. 7 Digit LED Display (7mm) at Operating mode: Indication of Set value.
At programming mode: Indication of program parameter
3. Out-1 output LED position: On while the power at Out-1.
4. Out-2 output LED position: On while the power at Out-2.
5. Set-1 Led position: On while Set-1 value is displayed in the bottom display
6. Set-2 Led position: On while Set-2 value is displayed in the bottom display.
Button Functions
7. RESET Button at Operating mode: Used to reset of counted value.
At programming mode: Using to exit without saving the entered value of the
parameter and return to the operation mode.
8. PROG Button at Operating mode: Used to return to the menu.
At programming mode: Used to save and enter menu parameter value.
9. Down Button at Operating mode: Used to in the bottom display to show the value of Set-1.
At programming mode: Used to switch between the menus and decrease the
value of the selected parameter.
10. Up Button at Operating mode: Used to in the bottom display to show the value of Set-2.
At programming mode: Used to switch between the menus and decrease the
value of the selected parameter.
- 3 -

Enter to the menu and Changing Parameters:
For switch to programming mode while device operating mode push ( ) button. Firstly “”s menu
will appear on the screen.
Switch between program menus with Down ( ) and up ( ) buttons. PRG button is entered into for
the menu to be changed. Changes are saved with prg ( ) button. Return to operating mode with rst ( )
button. If password protection is activated at device, password must be entered. If password is correct,
true message is displayed on the bottom line. Also password is incorrect, “false” is displayed.
Set 1 menu is displayed firstly on the screen as prg button is pressed while operating mode. Menu is
displayed firstly on the screen as prg button is pressed while operating mode. The top row shows the name
of the menu and bottom row also (yellow marked) selected value in menu content. Set 1, set 2 allows
controlling to out1 and out2 relays.
Move to the desired set point for setting. The rightmost digit starts flashing when prg button is pressed.
Desired point is selected up and down button. Used to prg button for Digits scrolling. Shifted to the left for
one step when each press of the button, If pres the prg button when coming the rightmost digits, positive
or negative value will be asked. Value is selected by up and down button then saved with prg button. If you
do not want to save, you can exit with esc button. İki menü de bu şekilde ayarlanır. Both menus are set in
this way.
3. DEVICE PROGRAMMING
If Password is correct :
“true”.
If Password is incorrect:
“false”
RST
PRG
PRG
PRG
4.1. Entering The Set Point to Device (Set)
PRG
- 4 -
PRG

By selecting the input type, the way the device counts with the signals from the input channels is selected.
There are 9 different counting options. How they work is described below.
In order to select counter type, pressed to prg button at operation mode. Found to Cnt_typ menu with up-
down button and pressed to prg button then bottom row choice flashes. Make the selection with up-down
button and saved value by prg button. Then return with rst button to operating mode.
Count Type
A Signal Pin
B Signal Pin
Function
tacho
Yes
Yes
Indicates the rotational speed in RPM (rev/
min).
ratio
Yes
Yes
Increases with A and B signals.
differ
Yes
Yes
Decreases with A signal, increases with B signal.
period
Yes
Yes
Decreases with A and B signals.
L1_sped
Yes
Yes
Increases with A signal,
A counts down as long as signal B is received.
t1_ntr
Yes
Yes
Decreases with A signal,
A counts forward as long as signal B is received.
PLS_time
Yes
Yes
Increases with A signal,
As long as signal B is received, signal A is not
counted.
cnt_PLSE
Yes
Yes
Decreases with A signal,
As long as signal B is received, signal A is not
counted.
cnt_CYCL
Yes
No
Pulse counts.
Provides accurate display of sensors with different resolutions by entering the multiplier value.
By way of example, 0,025 constant value is entered to Const Menu for the 25 micron-sensor or 0,005
constant value for 5 micron-sensor. So when sensor moves 100mm, value of 100 is displayed on the
screen.
In order to set to Conts Menu, pressed to prg button while operating mode and ound to Const Menu with
using up-down button. When pressed to prg button (While being cons menu), the right-hand digit of
4.2. Selection Of Input Type -Forward/Backward- (Cnt_typ)
PRG
4.3. Entering Constant Value (const)
- 5 -

bottom row flashes. Set to wanted value with up-down button. Digit moves to the left while pressed to prg
button. Then pressed to prg button again, this digit flashes. Digit position is set with up-down button. You
press again prg button, the digit is continuously flashing. Therefore the constant value is entered in. If you
want to exit without saving, you can back to operating mode with rst button.
Resolution of the value shown on the display is set here. This change is done by changing position of the
point on the screen. In order to changed position of the point, pressed to prg button at operating mode
and found point menu with up-down button. The point is flashing when pressed to prg button; you can set
position of the point with up-down button. Then you can save them with prg button. Return to operating
mode with rst button.
The input frequency can be filtered to prevent undesired interference. Above frequencies of the value
selected in the in_freg menu are not detected by the counter.
In operation mode, press prg button to select input frequency. The in_freg menu is located with the up and
down keys. When the prg button is pressed, the selection in the bottom row flashes. The desired selection
is set with the up-down button and saved with the prg button. Return to operating mode with Rst button.
.
.
.
PRG
4.4. Selection Of Point Position (Point)
.
.
.
PRG
4.5. Selection Of Sample Time (SAMP.time)
PRG
- 6 -

Selects the time unit in minutes, seconds or hours in the desired unit. In default settings, “minute” is selected.
Output menu enables different relay outs according to different set values. There are 11 different output
type. For detailed information refer to Annex-A part at the end of the manual. In order to select output
mode, pressed to prg button at operation mode. Found to output menu with up-down button and pressed
to prg button then bottom row choice flashes. Assigned value with up-down button and saved value by
prg button. Then return with rst button to operating mode.
4.7. Relay Output Modes (Output)
PRG
The relay function is turned off.
When passed over Set1 value, Output1 will be
active.
When passed over Set2 value, Output2 will be
active.
When passed over Set1 value, Output1 will be
active.
When passed over Set2 value, Output2 will be
active. Counter will be Hold position as long as
without reset.
When passed over Set1 value, Output1 will be
active.
When passed over Set2 value, Output2 will be
active. So Output1 is not active.
When passed over Set1 value, Output1 will be
active.
When passed over Set2 value, Output2 will be
active. Out1 will be inactive and the value on the
screen returns to the ofset value.
When passed over Set1 value, Output1 will be
active.
When passed over Set2 value, Output2 will be
active. Out1 is not active. And then and the
value on the screen returns to the ofset value.
4.6. Selection Of Time Unit (time.bas)
PRG
- 7 -

The value entered is in seconds after the point. If the value is zero, the display shows hold. In this case, the
relays remain drawn as long as they exceed the set value.
Tout menus allow role output times according to entered times. If entered to time as zero, writes hold on
the screen. Thus situated, relays will be active during the set value is exceeded. In order to entered output
time, if you press to prg button, found tout1 or tout2 menus with up-down button. When press prg button,
the right-digit of bottom row flashes. Its value is set with up-down button. Each press of the button moves
to the left in a digit. Then you can save them. Therefore point is fixed.
Out1 and out2 menus allow positions of the relays. The relay is inactive at Nclose option, active while
reached set point. And also the relay is active at Nopen option, it will be inactive while reached set point.
While hold input is active, value on the screen is fixed when coming the signal of hold input. If signal of
hold input isn't cut, counting can not to be continued. While you select the hold input, also select the edge
you will make reset on. You can select one of Rising and falling edges. If you want to hold off Input, select
to off option. In order to select to Hold Input, pressed to prg button at operating mode and found hold
menu with up-down button. When prg button is pressed, options will flash and made the selection with up-
down button. Then save it by prg button.
4.8. Relay Output Time (tout)
.
PRG
4.9. Relay Output Positions (out)
PRG
PRG
4.10. Activating The Hold Input (Hold)
PRG
- 8 -

The used sensor type can be select from this menu. The sensor output signal is selectable as NPN or PNP.
In order to selected sensor type, pressed to prg button at operating mode and fount S.typ menu with up-
down button. When prg button is pressed, options will flash and made the selection with up-down button.
Then save it by prg button and return with rst button to operating mode.
Factory menu enables to return the first fabrication settings of device. At this situated, all device setting
will change and for this reason important settings should be saved previously. Device will require the
password for returning to factory defaults and this password is 454. In order to return to factory defaults,
pressed to prg button at operating mode and found to factory menu with up-down button. When prg
button is pressed at menu screen, The right-digit of bottom row is flashing and changed value with up-
down button. When pressing to prg button, moves to the left in a digit and you can set it as 454 and press
to prg button. So device will return to factory defaults..
Password security enables that unauthorized persons is prevented to change the parameters of the menu.
If Code-in menu is on position, you can enter to device’s menu and password is required for any setting
changes. If the password is wrong, you cannot change anything. While Code_in menu is off, the password
protection is not active. If Code_in menu is on, recode is added to menu titles. In order to turn on Code-in
menu, pressed to prg button at operating mode and found Secu Menu with up-down button. Then save it
by prg button.
4.11. Selection Sensor Type (Npn/Pnp) (Senstyp)
PRG
4.12. Return To Factory Defaults (Factory)
PRG
4.13. Password Protection (Code_in)
PRG
When Code_in menu is on position, recode is added to menu titles. Recode menu enables
identification of password to device. Default password is 000, if you have not changed.
- 9 -

PRG
When prg button is pressed at menu screen, the right-digit of bottom row is flashing and changed value
with up-down button. When Pressed to prg button, moves to the left in a digit. So you can set the value
with up-down button and save them when pressed to prg button at third digit. So password is defined.
- 10 -

4.14. Annex A –Graphics of RELAY OUTPUT Types (Output Menu)
- 11 -

Product : ALC77 T 85/265 VAC 24 VAC/DC
TTL Push Pull
Serial No : ……………………………………
This product is guaranteed for two years against manufacturing defects.
Conditions out of the warranty:
-Mechanical damage
-Shipping damage
-Users error
Other situations are covered by the manufacturer's warranty.
5. CERTIFICATE OF WARRANTY
Signature and Stamp
- 12 -
Table of contents
Other Atek Control Unit manuals
Popular Control Unit manuals by other brands

MDS
MDS NETio Series Installation & operation guide

American Dynamics
American Dynamics ADACSNET Specifications

Pignology
Pignology Piglet quick start

Taco Comfort Solutions
Taco Comfort Solutions 5120 Series instruction sheet

Siemens
Siemens VAI61 Series Mounting instructions

Viessmann
Viessmann VITOTRONIC SPS operating instructions