
18
KN USER’S CONTROL MANUAL
Method 3: External 4-20ma control (continued)
3
4-20mA operation
1. A 4.02 mA current signal will start the boiler, at low re. A
20mA signal will cause the boiler to go to full input.
2. Between these input signal limits, the boiler modulates. e
boiler ring rate percentage is equal to the percentage of the
signal between 0 and 20 mA. Example, a signal of 12 mA is
60% of 20 mA, so the boiler ring rate would be 60% of max.
3. In addition to the 4-20mA signal, the remote controller
must also close a contact across each boiler’s Remote
Enable contact in order for the boiler to re.
4. See Figure 16 for wiring. Notice that the boiler 4-20mA
terminals are wired in series.
When using the 4-20 mA input for direct modula-
tion, the maximum modulation the boiler can
obtain when rst starting is equal to the;
ADVANCED SETUP: MODULAR BOILER:
MOD MAX – LAST FIRE:. e timer value
ADVANCED SETUP: MODULAR BOILER:
ADD BOILER DELAY is used in conjunction to
limit the modulation for this amount of time. Once
the boiler has red and the ADD BOILER DELAY
time expires, the full modulation is available.. When
the boiler is operating under these conditions a
blinking * is displayed. is is a protective means
for extending the life of the heat exchanger which
mayconsistentlybeexposed tothermalstress.
IAR (Indoor Air Reset) wiring —
apply ONLY if using space heating
override mode
• IAR can only be used if one or more of the boilers is wired
and piped for override operation. Override would occur
when a contact closed across the Heat Demand terminals.
While this contact is closed, the boiler will operate based on
local control, including feedback for IAR if wired.
• If override operation will be used, and you want to operate
with IAR when in override mode, follow the instructions
under Method 1 in this manual to wire for IAR.
Sensor wiring
• Header sensor cannot be used when the boilers are
congured for remote operation by a 24-mA source.
• Outdoor reset application can be done only in
override mode — To operate with outdoor reset,
purchase and install an outdoor sensor. Mount the sensor
such that it is shielded from direct sunlight if possible and
not likely to be covered by snow dris or debris. Connect
the outdoor sensor leads to the master boiler’s electrical
connection board as shown in Figure8. (Member boilers
couldhavetheir ownoutdoorsensorif they will be operated
inoverridemodebyclosingthe HeatDemandterminals.)
• Return water temperature sensor — e return water
temperature sensor is optional, only needed if you want
to automatically control the boiler postpurge pump cycle
time. Install the sensor in a well in the boiler return piping.
Connect the sensor leads to the electrical connection board
as shown in Figure 8. Each boiler requires a return water
temperature sensor.
• Sensor wiring, return water sensor — Firmware
Version 2.5 and greater monitors the temperature
dierential (Delta T) across the heat exchanger. If the Delta
T exceeds the seing, the input to the boiler can be
optionallylimited.
DHW wiring — ONLY if using DHW
override mode
• The boiler (or boilers) must be piped with isolation
valves and wired for override operation. Override of
the 4-20mA input will occur if a contact closes across the
boiler’s DHW Demand terminals.
• To operate the boiler for domestic water heating with a
storage tank, install and pipe the tank according to the
tank manufacturer’s instructions and the recommended
piping diagrams in this manual. Consult the factory for
applications not covered.
• e circulator used for DHW must be operated by a
circulator relay or zone controller that is activated when the
tank aquastat calls for heat.
• Connect the tank aquastat terminals across the DHW
DEMAND terminals on the master boiler’s electrical
connection board as shown in Figure 7. (Member boilers
could be connected to tank aquastats if they are piped
appropriately and intended to operate in override mode.)
External interlocks
5. Wire external limits and ow switch, when used, as shown
in Figure 17.
Overrides — Control priorities
1. e KN control can provide override operation for any or
all member boilers. is requires the boilers be piped with
appropriate isolation piping and controls.
2. OverrideisdonebyclosingacontactacrosstheHeatDemand
or DHW Demand terminals of any boiler. ese priority
inputs override all 4-20mA input controls to the boiler.
3. DHW Demand — e DHW Demand closure takes
priority for ALL boilers, including the master and all
members. When DHW Demand closes, the boiler or
boilers immediately switch to DHW operation, including
seing the water temperature to the DHW Setpoint.
4. Space heating, Heat Demand — If any member boiler
sees closure across its Heat Demand terminals it will
begin operation in space heating mode independently of
commands from the 4-20mA input source.
Do not wire boilers for override operation unless
the piping design provides automatic isolation of
the overriding boilers.
Override operation control setup — Boilers
must be set up with operating parameters
necessary during their override operation; i.e.,
local setpoint, DHW setpoint, etc.
5. Summary — priority sequence is:
Priority 1 = DHW Demand
Priority 2 = Heat Demand
Priority 3 = 4-20mA Input/Enable