INSTALLATIONANDOPERATINGINSTRUCTIONS
CEILING/WALLVENTILATION FAN
READ AND SAVE THESE INSTRUCTIONS
GENERAL SAFETY INFORMATION
1.
Make sure that the electric service supply voltage is
DC 12V 1A.
2.
Follow all local electrical and safety codes, as well as
the Nation Electrical Code (NEC) and the
Occupation Safety and Healthy Act (OSH Act).
3.
Always disconnect the power source before
workingonorneartheventilatingfan,motoror
junction box.
4.
Protect the power cord from sharp edges, oil, grease,
hot surfaces, chemicals or other objects.
1. INSTALLATIONS
Properinsulationaroundthe fantominimizebuilding
heat loss and gain. 4’’circular duct is recommended for
installation. The ducting from this fan to the outside of
the building has a strong effect on theairflow, noise
and energy use of the fan. Use the shortest, straightest
duct routing possible for best performance, and avoid
installing the fan with smaller ducts than
5.
Do not kink the power cord.
6.
Donotinstalltheunitwhereductsareconfigured
as shown in Fig. A.
CAUTION
Fig.A recommended. Insulation around the ducts can
reduce energylossand inhibitmoldgrowth.Fans
installed with existing ducts may not achieve their
rated air flow.
7.
Provide suction parts with proper ventilation.
8.
This unit is UL listed for use over a bathtub or
shower when installed in a GFCI protected branch
circuit.
WARNING
TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR
INJURY TO PERSONS, OBSERVE THE FOLLOWING:
1. Use this unit only in the manner intended by the
1.
For General Ventilating Use Only. Do Not Use To
Exhaust Hazardous Or Explosive Materials And
Vapors.
2.
Not for use in cooking areas. (Fig. B)
3.
This product must properly connect to the
grounding conductor of the supply circuit.
4.
To reduce the risk of injury to persons, install the
fan atleast 8.2 feet (2.5m) above the floor.
Cooking area
manufacturer. If you have questions, contact the
Do not install above or
manufacturer.
2.
Beforeservicingorcleaningunit,switchpoweroff
atservicepanelandlocktheservicedisconnecting
means to prevent power from being switched on
accidentally. When the service disconnecting means
cannot be locked, securely fasten a prominent
warning device,suchasa tag,tothe servicepanel.
3.
Installation work and electrical wiring must be done
by qualified person(s) in accordance with all
applicable codes and standards, including fire-rated
construction.
4.
Sufficientairisneededforpropercombustion and
exhaustingofgasesthroughthe flue(chimney) of
fuelburningequipmenttopreventbackdrafting.
Follow the heating equipment manufacturer’s
guideline and safety standards such as those
published by the National Fire Protection
Association (NFPA), and the American Society of
Heating, Refrigerating and Air-Conditioning
Engineers (ASHRAE), and the local code authorities.
5.
Whencuttingor drillinginto wallorceiling,do not
damage electrical wiring and other hidden utilities.
6.
Ductedfans mustalways beventedtotheoutdoors.
7.
Ifthis unitistobeinstalledovera tuborshower,it
must be marked as appropriate for the application
andbe connected toa GFCI (Ground Fault Circuit
Interrupter) -- protected branch circuit.
8.
NEVER placeaswitchwhereitcanbereachedfrom
a tub or shower.
9.
Not to be installed in a ceiling thermally insulated to
a value greater than R50. (This is required for
installation in Canada only).
inside this area
Fig. B
SUPPLIEDACCESSORIES
MOUNT HOUSING WITH FLANGE(CELING/ WALL)
1-1. To bend the housing tabs out to 90 degree and
makehousingtabscontactthebottom orfrontof
the joist.
1-2. The housing mounts with 4 screws (Ø4×25).
Screw housingtojoist throughlowestholesin
each mounting flange, then through the other
holes.