Avansys Power iTrust UH11-0030L User manual

iTrust Online UPS
UH11 Series-1kVA/2kVA/3kVA
User Manual
E1-20010915-C-1.0
Avansys Power Co., Ltd.

iTrust Intelligent High Frequency Online UPS
UH11 Series-1kVA/2kVA/3kVA
User Manual
31010809BOM:
StandardPublication State:
E1-20010915-C-1.0Manual Ver.:
Avansys Power Co., Ltd. provides customer with satisfactory technical
support. To obtain support, please contact the distributor in the first
instance. When failing to reach the distributor, please contact your
local technical support center or the company headquarters.
Avansys Power Co., Ltd.
Address: Huawei Manufacturing Center, Banxuegang Industrial Base,
Longgang District, Shenzhen 518129, PRC
Homepage http://www.avansys.com
E-mail [email protected]

Copyright Information
Copyright by Avansys Power Co., Ltd.
All rights reserved.
The information in this document is subject to change without notice.
No part of this document may in any form or by any means
(electronic, mechanical, micro-copying, photocopying, recording or
otherwise) be reproduced, stored in a retrieval system or transmitted
without prior written permission from Avansys Power Co., Ltd..

Publication Statement
Thank you for using iTrust series UPS by Avansys Power Co.,
Ltd. UH11 series is the latest single-phase input single-phase
output intelligent online UPS developed by Avansys incorporating
years of experience in power supply development. As a
world-leading standard UPS product, this series delivers
excellent electrical performance, is fully compliant with safety
regulations and EMC standards, features perfect intelligent
monitoring and network management, and is well-shaped with
beautiful appearance.
Please read through this manual prior to installation and
operation.
Readers
This manual is intended for equipment operator and technical
support personnel.
Conventions
Symbol
Notice This symbol is used in this manual to alert you to
important information.

Safety Guidelines
. Prohibitions
1. As high voltage exists within UPS, no one but Avansys
technician and Avansys-authorized technician should open the
panel and the chassis cover. Otherwise, one may get electric
shock and such situation is not covered under warranty.
2. When the UPS is purchased to supply the equipment listed
below, please consult the distributor in advance on the UPS
application, setting, management and maintenance, which need
special consideration and design.
Life support medical apparatus;
Facilities such as lift which may endanger human life;
Mission-critical equipment like above.
3. Never dispose of battery in a fire, as battery may explode
when exposed to flame.
. Matters needing attention
1. The UPS contains its own energy source-battery, the UPS
output may carry live voltage even when the UPS is not
connected to an AC supply.
2. To move or re-wire the UPS, please disconnect the input and
make sure that the UPS is completely shut down. Otherwise, live
voltage still exists at the output terminal, which may cause
electric shock.
3. To ensure human safety, the UPS must be reliably grounded
before use.

4. The operating environment and storage method will affect the
lifetime and reliability of the UPS. Please don’t use the UPS long
in the following environments
Place with temperature and relative humidity outside
specifications (temperature: 0 to 40 , relative humidity: 5% to
95%);
Place with direct sunlight or near heat source;
Place with vibration or shock;
Place with dust, corrosive material, salt or flammable gas.
5. Please keep the air inlet and outlet unblocked. Poor ventilation
will increase the internal temperature, which will shorten the
lifetime of the UPS components, hence that of the UPS.
6. Liquid and other irrelevant substances are strictly prohibited
inside the UPS chassis.
7. In case of fire, please use dry-chemical fire extinguisher. Using
foam fire extinguisher may cause electric shock.
8. High ambient temperature shortens battery lifetime, so battery
should be replaced regularly to ensure normal UPS operation
and adequate backup time. Battery replacement must be
conducted by authorized technician.
9. If the UPS will not be used for long, it should be placed in dry
environment. Storage temperature of standard UPS (with battery):
–20 +55 , storage temperature of long backup time UPS
(without battery): –40 +70 .
10. During the period the UPS is left unused, it is recommended
to supply the UPS with AC mains for more than 12 hours every 3
months, so that the battery will not be damaged due to long time
of not-in-use.

11. Please don’t open or damage the battery, as the electrolyte is
harmful to skin and eye. If tainted with electrolyte, wash it off
immediately with plenty of water and go to hospital for a check.

Contents
213.1.3 Battery Mode ----------------------------------
21
3.1.2 Bypass Mode ---------------------------------
20
3.1.1 Normal Mode ----------------------------------
20
3.1 Operation Mode ------------------------------------
20
Chapter 3 Operation -------------------------------------
14
2.2.2 Installing the UPS ------------------------------
12
2.2.1 Matters Needing Attention ------------------------
12
2.2 Installation ----------------------------------------
12
2.1 Unpacking Inspection --------------------------------
12
Chapter 2 Installation ------------------------------------
9
1.5.3 Rear Panel ------------------------------------
5
1.5.2 Front Panel ------------------------------------
4
1.5.1 Appearance ------------------------------------
4
1.5 Appearance and Panels -------------------------------
2
1.4 Features -------------------------------------------
2
1.3 Schematic Diagram -----------------------------------
1
1.2 Model ---------------------------------------------
1
1.1 Application -----------------------------------------
1
Chapter 1 Product Introduction -----------------------------

35
V. Function Inspection -----------------------------------
34
IV. UPS State Check ------------------------------------
34
III. Keep Air Vent Unblocked ------------------------------
33
II. Battery Maintenance ----------------------------------
33
I. Fan -----------------------------------------------
33
Chapter 4 Maintenance ----------------------------------
32
3.4 UPS Monitoring -------------------------------------
31
3.3.4 Output Short-circuit Protection ---------------------
31
3.3.3 Transfer to Bypass Mode in the Event of
Overtemperature ------------------------------------
31
3.3.2 Transfer to Battery Mode in the Event of Mains
Failure -------------------------------------------
30
3.3.1 Transfer to Bypass Mode in the Event of
Overload ------------------------------------------
30
3.3 Auto Transfer Between UPS Operation Modes -------------
30
3.2.5 System Power-off ------------------------------
29
3.2.4 Turn off Inverter --------------------------------
28
3.2.3 Battery Management ----------------------------
23
3.2.2 Start Inverter Output ----------------------------
22
3.2.1 System Power-on ------------------------------
22
3.2 Operation -----------------------------------------
22
3.1.4 Fault Mode -----------------------------------

50
Appendix 4 Optional Component --------------------------
47
Appendix 3 Technical Specifications -----------------------
43
Appendix 2 Grounding & Lightning Protection ----------------
42
Dry Contact Communication Mode --------------------------
41
RS-232 Communication Mode -----------------------------
41
Appendix 1 Communication Port ---------------------------
39
Chapter 6 Service and Support ----------------------------
36
Chapter 5 Troubleshooting --------------------------------

Chapter 1 Product Introduction
1.1 Application
iTrust series UPS provides reliable and high quality AC power to
your sensitive equipment. It is applicable to supply AC power to
computer center, network management center, communication
system, auto control system, and precision instrument, etc.
1.2 Model
iTrust series UPS has among others 1kVA, 2kVA, and 3kVA UPS
products available, as listed below:
Long
backup time
UPS, with
external
battery
Standard
UPS, with
internal
battery
Long backup
time UPS, with
external battery
Standard
UPS, with
internal
battery
Long
backup time
UPS, with
external
battery
Standard
UPS,
with
internal
battery
Expla
nation
UH11-0030LUH11-0030
UH11-0020L
UH11-0020L(B)
UH11-0020
UH11-0020(B)
UH11-0010LUH11-0010Model
3kVA2kVA1kVA
Capa
city
Chapter 1 Product Introduction 1
E1-20010915-C-1.0

1.3 Schematic Diagram
Rectifier Inverter
Mains Load
Bypass
Electronic transfer
switch
Charger
Charger
High capacity rectifier
Input fuse
(a) 1kVA
Rectifier
AC mains
Bypass
Inverter Load
Electronic
transfer switch
Charger
Charger
High capacity rectifier
Input switch
(b) 2kVA/3kVA
Fig. 1 System Schematic Diagram
1.4 Features
iTrust series 1kVA/2kVA/3kVA UPS is an intelligent online UPS
system with sine wave output newly developed by Avansys Power
Co., Ltd.
2 Chapter 1 Product Introduction
E1-20010915-C-1.0

The system adopts high-frequency double conversion topology
structure with high input power factor, wide input voltage range,
and output immune from mains interference, hence the product
is suitable for areas with unstable mains supply;
It adopts advanced full digital control technology based on DSP
to achieve high system reliability, features self-protection and
fault diagnosis;
It features excellent intelligent battery management, extending
battery life;
The panel operation interface adopts LED display, facilitating
user to learn about the system operation state;
With Avansys monitoring software, perfect network management
of UPS can be achieved.
Chapter 1 Product Introduction 3
E1-20010915-C-1.0

1.5 Appearance and Panels
1.5.1 Appearance
Air inlet Air inlet
LED display panel
LED display panel
1kVA UPS 2kVA/3kVA UPS
Fig. 2 Appearance of 1kVA/2kVA/3kVA UPS
4 Chapter 1 Product Introduction
E1-20010915-C-1.0

1.5.2 Front Panel
Mains indicator
ON/SILENCE button
OFF button
Fault indicator
Battery backup capacity/load indicators
Battery indicator
Bypass indicator
Inverter indicator
ΥΠΣ−1Κς Α
ΥΠΣ−1Κς ΑΥΠΣ−1Κς Α
ΥΠΣ−1Κς Α
Fig. 3(a) Front Panel of 1kVA UPS
Chapter 1 Product Introduction 5
E1-20010915-C-1.0

Battery backup capacity/load indicators
Inverter indicator
Fault indicator
ON/SILENCE button
Air inlet
Mains indicatior
OFF button
Bypass indicator
Battery indicator
Fig. 3(b) Front Panel of 2kVA/3kVA UPS
I. Functions
For heat dissipation of UPS.Air inlet
There are several LED indicators on the panel, showing the UPS state,
load, battery backup capacity, fault, etc.
LED
When the UPS is supplying power through inverter, pressing and
holding this button for 1 second can stop the inverter output (i.e., turn off
the inverter).
OFF button
When the UPS is supplying power through bypass, pressing and holding
this button for 1 second can start the inverter output (i.e., turn on the
inverter); when the UPS is supplying power through inverter, which
obtains power from rectifier, pressing and holding this button for 4
seconds can perform manual battery test; when the UPS is giving
audible alarm, pressing this button can silence the alarm sound.
ON/SILENC
E button
6 Chapter 1 Product Introduction
E1-20010915-C-1.0

II. LED
The LED indicators on the panel are divided into 2 groups according
to their use: one group indicates the load, battery backup capacity or
fault, totally 5 LED indicators, 4 green and 1 yellow; the other group
indicates the UPS state, including the mains indicator, battery
indicator, bypass indicator, inverter indicator and fault indicator.
Below is the detailed description of these indicators:
1. UPS state indicators
The light shines in the event of fault, and goes off
otherwise.
Fault indicator
red
The light shines when the inverter is supplying
power, goes off otherwise, and flashes in the event
of inverter fault.
Inverter indicator
green
The light shines when the battery is supplying
power, goes off otherwise, and flashes in the event
of charger fault, improper battery connection,
reverse battery connection, or battery fault.
Battery indicator
green
The light shines when the bypass is supplying
power, and goes off otherwise.
Bypass indicator
green
The light shines when the mains is normal, goes off
in the event of mains failure, and flashes when the
mains voltage is outside tolerances.
Mains indicator
green
2. Load, battery backup capacity/fault locating indicators
When the AC mains is working normally during UPS operation,
these indicators indicate the load, as described in the following
table:
Chapter 1 Product Introduction 7
E1-20010915-C-1.0

4 green lights and 1 yellow light shining
indicates the UPS assumes more than 95%
rated load
4 green lights shining indicates the UPS
assumes 75%--95% rated load
3 green lights shining indicates the UPS
assumes 55%--75% rated load
2 green lights shining indicates the UPS
assumes 35%--55% rated load
1 green light shining indicates the UPS
assumes 0--35% rated load
When the battery is supplying load, these indicators indicate the
battery backup capacity, as detailed in the following table:
The yellow light shining means the battery is approaching
discharge termination voltage, and the UPS is about to
stop output
1 green light shining means the battery backup capacity is
greater than 20% rated capacity
2 green lights shining means the battery backup capacity
is greater than 40% rated capacity
3 green lights shining means the battery backup capacity
is greater than 60% rated capacity
4 green lights shining means the battery backup capacity
is greater than 80% rated capacity
In the event of UPS fault (the fault indicator shines), these indicators
tell the fault reason (as shown in the following table), so that the fault
can be located quickly.
8 Chapter 1 Product Introduction
E1-20010915-C-1.0

The yellow light flashes
Output
short-circuit
The 4th green light from the left flashes
Auxiliary supply
fault
The 3rd green light from the left flashes
Internal
overtemperature
The 1st green light from the left flashesRectifier fault
1.5.3 Rear Panel
INPUT
Input socket
EXTERNAL BATT.
OUTPUT
Fan
Dry contact
RS232
Output socket
Input fuse
External battery socket
(Long backup time UPS)
SNMP adaptor
slot/false panel
Fig. 4(a) Rear Panel of 1kVA UPS
Chapter 1 Product Introduction 9
E1-20010915-C-1.0

External battery socket /false panel
INPUT
Input switch
Fan
RS-232
Dry contact
Output socket
adaptor slot/false panel
SNMP
Mains input power line
Fig. 4(b) Rear Panel of 2kVA/3kVA UPS
10 Chapter 1 Product Introduction
E1-20010915-C-1.0
This manual suits for next models
7
Table of contents
Popular UPS manuals by other brands

Emerson
Emerson Liebert NXC 60kVA user manual

Dynamode
Dynamode 850VA quick start guide

Forza
Forza DC-140USB user guide

MGE UPS Systems
MGE UPS Systems Comet Series Installation and user manual

S&C
S&C PureWave Operation and maintenance manual

socomec
socomec MASTERYS GP4 Series Installation and operating manual