Bartec 17-51P6-1 11 Series User manual

Operating Instructions
Ex p power relay
ATEX/IECEx Zone 1/21

BARTEC GmbH
Max-Eyth-Straße 16
97980 Bad Mergentheim
GERMANY
Phone: +49 7931 597-0
Fax: +49 7931 597-480
Internet: www.bartec.de
Operating Instructions
Ex p power relay
Type 17-51P6-1*11/****
ATEX / IECEx Zone 1 / 21
Document number: 11-51P6-7D0001
Revision: 0
436730


Ex p relay
Power
Table of contents
20190910_Manual_Exp-Relais_Power_en.docx Rev. 0 Page 3 of 24
0Table of contents
0Table of contents ........................................................................................................... 3
1About these operating instructions ................................................................................ 5
Highlighting in the document ......................................................................................... 6
Warnings ........................................................................................................................ 6
Symbols and icons ......................................................................................................... 7
Technical changes.......................................................................................................... 7
Languages...................................................................................................................... 7
2Safety............................................................................................................................. 8
Intended use .................................................................................................................. 8
Exclusive purpose .......................................................................................................... 8
Improper use.................................................................................................................. 8
Warranty ........................................................................................................................ 8
Qualification of staff ...................................................................................................... 9
Safety instructions......................................................................................................... 9
General .......................................................................................................................... 9
Safety instructions for operation.................................................................................. 10
Obligations of the owner............................................................................................... 11
Instructions for use ...................................................................................................... 11
Standards complied with ............................................................................................. 11
Marking and test certificate ......................................................................................... 12
Avoidance of damage to property ................................................................................. 12
Short circuit due to improper connection ..................................................................... 12
Storage at an excessively high temperature ................................................................. 12
Aggressive cleaning agents .......................................................................................... 12
Danger to health due to improper disposal................................................................... 12
3Product description...................................................................................................... 13
General information ..................................................................................................... 13
Ex p power relay ........................................................................................................... 13
Module......................................................................................................................... 13
Complete control unit................................................................................................... 13
4Transport and storage .................................................................................................. 14
Scope of delivery.......................................................................................................... 14
Packaging..................................................................................................................... 14
Transport ..................................................................................................................... 14
Storage ........................................................................................................................ 14
5Installation................................................................................................................... 15
General information ..................................................................................................... 15

Table of contents
Ex p relay
Power
Page 4 of 24 Rev. 0 20190910_Manual_Exp-Relais_Power_en.docx
Installation of the Ex p power relay .............................................................................. 15
Installation of the module version ................................................................................ 15
Installation of complete control unit version ................................................................ 16
6Electrical connections.................................................................................................. 17
General information ..................................................................................................... 17
Functional circuit diagram ........................................................................................... 18
Connection notes ......................................................................................................... 18
7Maintenance and care.................................................................................................. 19
Maintenance work........................................................................................................ 19
Maintenance intervals.................................................................................................. 19
Repairs......................................................................................................................... 20
Faults and troubleshooting .......................................................................................... 20
Faults........................................................................................................................... 20
Disposal ....................................................................................................................... 20
8Technical data.............................................................................................................. 21
Ex p power relay ........................................................................................................... 21
Ampacity of the Ex p power relay.................................................................................. 21
9Order numbers ............................................................................................................. 22
Ex p power relay (module)............................................................................................. 22
Ex p power relay (control unit) ...................................................................................... 22
10 Declaration of conformity............................................................................................. 23
11 Notes ........................................................................................................................... 24

Ex p relay
Power
About these operating instructions
20190910_Manual_Exp-Relais_Power_en.docx Rev. 0 Page 5 of 24
1About these operating instructions
Please read carefully before putting the device into operation.
Please observe the corresponding user manual.
This manual contains the information required for using the Ex p relay in
accordance with its intended purpose. It is addressed to technically qualified
personnel.
Familiarity with and the technically perfect implementation of the safety
instructions and warnings described in this manual are preconditions for safe
installation and commissioning. The safety notes and warnings in these
operating instructions are given in a general manner and only qualified
personnel will have the necessary know how to interpret and implement them
correctly in specific individual cases.
These operating instructions are an integral part of the scope of delivery even if,
for logistical reasons, they can be ordered and delivered separately.
Should you require further information, please request the required
information from your local or responsible BARTEC branch. Read the
operating instructions and in particular the safety instructions carefully
before using the device.
Keep the operating instructions during the entire service life of the
device.
Make the brief instructions accessible to all persons entrusted with
handling the device.

About these operating instructions
Ex p relay
Power
Page 6 of 24 Rev. 0 20190910_Manual_Exp-Relais_Power_en.docx
Highlighting in the document
Warnings
Warnings are used in this user manual to warn of property damage and personal
injury.
Always read and follow these warnings.
Warnings are specially highlighted in this user manual and identified by symbols:
DANGER
DANGER indicates a hazardous situation which, if safety measures are not
observed, may result in death or serious injuries with permanent damage.
WARNING
WARNING indicates a hazardous situation which, if safety measures are not
observed, may result in serious injuries without permanent damage.
CAUTION
CAUTION indicates a hazardous situation which, if safety measures are not
observed, can result in minor injuries.
ATTENTION
ATTENTION indicates a hazardous situation which, if the safety measures
are not observed, may result in damage to property.
Explanation of the structure of a warning notice
WARNING WORD
Identifies the source of danger, cause of danger or type of danger
Consequence of non-compliance with the described safety measure.
Safety measure
Example of a warning notice
DANGER
Operation of the control unit in the case of damage!
Death or serious injury.
Put the control unit out of operation and secure it against restart.

Ex p relay
Power
About these operating instructions
20190910_Manual_Exp-Relais_Power_en.docx Rev. 0 Page 7 of 24
Symbols and icons
Symbol
Explanation
Important notices and information for the effective, efficient and
environmentally friendly use of the product.
Ex application; this symbol indicates special information for Ex
applications
Table 1: Symbols and icons
Technical changes
The current versions of the datasheets, operating instructions, certificates and
EC declarations of conformity as well as information on new accessories can be
downloaded from www.bartec.de under “Products” in the product area “Control
and Connection Equipment”, or requested directly from BARTEC GmbH.
Languages
The original user manual is written in German. All other available languages are
translations of the original user manual.
The user manual is available in German. If further languages are required, these
must be requested from BARTEC or stated when placing the order.

Safety
Ex p relay
Power
Page 8 of 24 Rev. 0 20190910_Manual_Exp-Relais_Power_en.docx
2Safety
Intended use
Exclusive purpose
The Ex p relay serves exclusively as a separation from non-intrinsically safe
voltage supply lines in connection with the Ex p control units APEX and SILAS.
It is intended for use in explosion group II, category 2GD and temperature class
T4 or for use in dusty environments with surface temperature of T130 °C.
The permissible operating data of the device used must be observed.
Improper use
Any other use is not in accordance with the intended purpose and may lead to
damage and accidents. The manufacturer will not be liable for any use beyond
that of its intended purpose.
Warranty
WARNING
UNAUTHORISED MODIFICATIONS AND/OR ALTERATIONS TO THE CONTROL
SYSTEM.
Explosion protection as well as design and manufacture in line with strain
and safety requirements are no longer guaranteed.
Before making any modifications or alterations, contact the
manufacturer to obtain written approval.
Use only original spare parts and original wearing parts.
Assumption of warranty
The manufacturer assumes the complete warranty only and
exclusively for the spare parts ordered from the manufacturer.
As a basic rule, our “General Terms and Conditions of Sale and Delivery” apply.
They are available to the managing operator on conclusion of contract at the
latest. Warranty and liability claims for personal injury and damage to property
are excluded if they are due to one or several of the following reasons:
Improper use of the Ex p relay.
Incorrect installation, commissioning, operation and maintenance.
Non-compliance with the instructions in the manual with respect to
transport, storage, assembly, commissioning, operation and maintenance.
Unauthorised structural changes.
Inadequate monitoring of parts that are subject to wear.
Improperly performed repairs.
Disasters caused by foreign bodies and force majeure.

Ex p relay
Power
Safety
20190910_Manual_Exp-Relais_Power_en.docx Rev. 0 Page 9 of 24
We guarantee the Ex p relay and its accessories for a period of one year starting
on the date of delivery from the Bad Mergentheim plant. This warranty covers all
parts of the delivery and is restricted to the replacement free of charge or the
repair of the defective parts in our Bad Mergentheim plant. Any packaging
delivered here should be kept where possible. If necessary, the goods should be
sent to us after written agreement. There is no entitlement to rectification at the
site of installation.
Qualification of staff
Target group
Skills
Design /
engineering
Technical training
Knowledge and experience to identify and avoid
hazards that may be caused by electricity
Understanding of the overall system
Configuration / programming
Special induction for the Ex area
Electrician / installer
Technical training
Knowledge and experience to identify and avoid
hazards that may be caused by electricity
Understanding of the overall system
Special induction for the Ex area
Operator
Induction in operation by the owner
Special induction for the Ex area
Storage and transport
companies
Loading and transport activities
Professional storage
Table 2: Tasks of individual target groups
Safety instructions
General
Do not dry wipe or clean devices in hazardous areas!
Do not open devices in hazardous areas.
The general statutory regulations or guidelines relating to safety at work,
accident prevention and environmental protection legislation must be
observed, e.g. the German Industrial Health and Safety Ordinance
(BetrSichV) or the applicable national ordinances.
Wear suitable clothing and footwear in view of the risk of dangerous
electrostatic charges.
Avoid exposure to heat outside the specified temperature range (see
Chapter “General technical data”).
Avoid exposure to moisture.

Safety
Ex p relay
Power
Page 10 of 24 Rev. 0 20190910_Manual_Exp-Relais_Power_en.docx
Safety instructions for operation
Commissioning
Before commissioning, check that all components and documents are
available.
Inspection
Under EN/IEC 60079-17, the owner of electrical systems in hazardous
areas is obliged to have them checked by a qualified electrician to ensure
that they are in a proper condition.
Maintenance
For electrical systems, the relevant installation and operating regulations
must be observed (e.g. Directive 99/92/EC, Directive 2014/34/EUEC,
BetrSichV or the nationally applicable ordinances EN/IEC 60079-14 and
the DIN VDE 0100 series)!
Please observe the national waste disposal regulations for disposal.
Servicing
Regular servicing is not necessary if the device is operated correctly in
accordance with the installation instructions and ambient conditions.
BARTEC recommends annual servicing and inspection.
See Chapter “Maintenance and care”.
Repairs
Repairs on explosion-protected equipment may be done only by authorised
persons working in accordance with the latest developments in technology
and using original spare parts. The applicable provisions must be
observed.
Repairs must be carried out in accordance with EN / IEC 60079-19.
For Ex applications, only one device and one electronic module may be
used with corresponding Ex approval. Order the spare parts from your local
representative. The serial number can be found on the type plate of the
device, inside the enclosure.

Ex p relay
Power
Safety
20190910_Manual_Exp-Relais_Power_en.docx Rev. 0 Page 11 of 24
Obligations of the owner
The owner undertakes to restrict permission to work with and on the Ex p power
relay control unit to people who:
are familiar with the basic regulations on safety and accident prevention
and have been instructed in the use of the Ex p power relay;
have read and understood the documentation, the chapter on safety and
the warnings.
The owner must check that the safety regulations and accident prevention
rules valid for the respective application are observed.
Instructions for use
The control unit must be completely installed in an enclosure that meets
the requirements for the enclosure according to IEC 60079-0 with a
minimum degree of protection of IP 54 for EPL Gb and IP 6X for EPL Db.
The overvoltage category II of the non-intrinsically safe circuits according
to IEC 60664-1 must be observed.
The warning “WARNING – DO NOT OPEN UNDER VOLTAGE” must be part of
the external marking of the entire electrical device or the enclosure must
have a locking system to prevent the fuses from being energised during
replacement.
Standards complied with
Standard
Designation
EN IEC 60079-0:2018
IEC 60079-0:2017
Explosive atmospheres –Part 0: General
requirements
EN 60079-5:2015
IEC 60079-5:2015
Explosive atmospheres - Part 5: Equipment
protection by powder filling "q"
EN 60079-7:2015
IEC 60079-7:2015
Explosive atmospheres –Part 7: Equipment
protection by increased safety “e“
EN 60079-31:2014
IEC 60079-31:2013
Explosive atmospheres - Part 31:
Equipment dust ignition protection by enclosure
“t”
EN 61000-6-4:2019
IEC 61000-6-4:2018
Electromagnetic compatibility (EMC) –
Part 6-4: Generic standards –Emission standard
for industrial environments
EN 61000-6-2:2019
IEC 61000-6-2:2016
Electromagnetic compatibility (EMC) - Part 6-2:
Generic standards - Immunity standard for
industrial environments

Safety
Ex p relay
Power
Page 12 of 24 Rev. 0 20190910_Manual_Exp-Relais_Power_en.docx
Marking and test certificate
The relay is approved for the following areas
ATEX (Europe)
17-51P6-1*11/****
Marking
II 2G Ex eb qb IIC T4 Gb
II 2D Ex tb IIIC T130 °C Db
Test certificate
EPS 18 ATEX 1159 X
IECEx (International)
17-51P6-1*11/****
Marking
Ex eb qb IIC T4 Gb
Ex tb IIIC T130 °C Db
Test certificate
IECEx EPS 18.0082X
Avoidance of damage to property
Short circuit due to improper connection
An incorrect connection of the power supply will destroy the electronics and void
the warranty.
Storage at an excessively high temperature
Store the Ex p control unit at the intended storage temperature since otherwise
damage to the electronics or seals may occur. Ensure adequate air conditioning
at high storage temperatures.
Aggressive cleaning agents
When selecting the correct cleaning agent, it is essential that it is suitable for
use since otherwise damage may occur to seals and connections. Combustible
products are generally not permitted.
Danger to health due to improper disposal
According to the European WEEE Directive, electrical and electronic equipment
may not be disposed of with household waste. Their components must be sent
separately for recycling or disposal because toxic and hazardous components
can cause long-term damage to health and the environment if not disposed of
properly.
As consumers, you are obliged under the Electrical and Electronic Equipment Act
(ElektroG) to return electrical and electronic equipment at the end of its
serviceable life free of charge to the manufacturer, the point of sale or to public
collection points set up for this purpose. Details of this are regulated by the
respective national law. The symbol on the product, the operating instructions
or/and the packaging refers to these regulations. With this type of material
separation, recycling and disposal of old devices, you make an important
contribution to the protection of our environment.

Ex p relay
Power
Product description
20190910_Manual_Exp-Relais_Power_en.docx Rev. 0 Page 13 of 24
3Product description
General information
The Ex p power relay is intended for the safe separation of supply lines directly in
hazardous areas and can be used together with the BARTEC pressurised
enclosure systems APEX or SILAS.
The Ex p power relay has four electrically isolated switch contacts which open
the contacts when the power falls away. The safe opening of the contacts is
guaranteed by two series-connected relays. Up to three phases of supply lines
can be switched off using the switching power of 400V, 16 A and 4kW.
The Ex p power relay is available in three different activation voltages and as a
module for integration in a separately certified enclosure or as a complete
control unit.
Ex p power relay
Module
The Ex p power relay (module) must be installed in an enclosure with the
minimum dimensions of 220 mm x 120 mm x 90 mm.
The enclosure must be certified according to a recognised ignition protection
class in accordance with section 1 of IEC/EN 60079-0.
In the case of installation in an enclosure with enhanced safety “e“ IEC/EN
60079-7, the clearances and creepage distances and ambient temperatures
must be observed.
If used in atmospheres with high air humidity, a separately approved
enclosure with breathing device must be used.
Complete control unit
The Ex p power relay (complete control unit) is installed in an enclosure in
accordance with IEC/EN 60079-7 with the dimensions 220 mm x 120 mm x 90
mm.
It can be simply mounted to the Ex p protected equipment using the
installation aids on the enclosure.

Transport and storage
Ex p relay
Power
Page 14 of 24 Rev. 0 20190910_Manual_Exp-Relais_Power_en.docx
4Transport and storage
Scope of delivery
Missing parts or damage must be reported immediately in writing
to the forwarding agent, the insurance company or BARTEC
GmbH.
Check the completeness of the scope of delivery using the delivery note
As standard, each Ex p relay unit is delivered with the following scope of delivery:
Ex p power relay in the ordered version
Operating instructions
Packaging
The Ex p power relay is delivered packed in film, on pallets and/or in boxes.
Dispose of the packaging materials at the designated disposal points.
Observe the applicable national regulations for disposal.
Transport
WARNING
DEATH OR RISK OF INJURY FROM FALLING HEAVY SUSPENDED LOADS.
Never stand under suspended loads.
Secure the Ex p power relay before transport using suitable fastening
(e.g. straps)
ATTENTION
AVOID HARD IMPACTS, E.G. BY FALLING DOWN OR SETTING DOWN TOO
VIGOROUSLY.
The Ex p control unit may be damaged.
Only use hoists and load handling attachments with sufficient load
bearing capacity.
The permissible lifting weight of a lifting device may not be exceeded.
Slowly set down the control unit.
Observe the weight of the goods to be transported and select an adequate
transport device.
Storage
Store the Ex p relay in a horizontal position and at a temperature of -25 °C to +65
°C in its original packaging. The environment must be dry, dust-free and low
vibration.
Store the control unit for a maximum of 2 years.
For warehouse logistics, we recommend the “first in – first out” principle.

Ex p relay
Power
Installation
20190910_Manual_Exp-Relais_Power_en.docx Rev. 0 Page 15 of 24
5Installation
Before starting work, find out about the general safety
instructions (see Chapter 2 Safety instructions).
The Ex p power relay has been developed for use in hazardous areas of Zone
1/21.
Carry out the installation according to the following sections, unless otherwise
agreed for customer-specific control units.
General information
The installation of the Ex p relay is explained in the following chapters.
Deviations in the installation of customer-specific superstructures may arise.
Installation of the Ex p power relay
Installation of the module version
Install the Ex p power relay at the desired position
with the following drilling pattern (82 mm x 204
mm).
The module version can be installed in any
position.

Installation
Ex p relay
Power
Page 16 of 24 Rev. 0 20190910_Manual_Exp-Relais_Power_en.docx
Installation of complete control unit version
Install the Ex p power relay at the desired position
with the following drilling pattern (82 mm x 204
mm).
The complete control unit version can be installed
in any position.

Ex p relay
Power
Electrical connections
20190910_Manual_Exp-Relais_Power_en.docx Rev. 0 Page 17 of 24
6Electrical connections
DANGER
DEATH OR SERIOUS PHYSICAL INJURY DUE TO WORK ON LIVE PARTS.
Fatal injury from electrical current.
Observe the 5 safety rules for work on electrical systems:
Disconnect mains; protect against unintended reconnection; verify
the absence of voltage; earth and short-circuit; cover or safeguard
nearby live parts.
General information
Connection terminals with the type of protection “Ex e” are on the connection
board of the Ex p relay.
Terminal row
Function
Ex e
PE
Ground connection
A1
Activation of the Ex p relay (L / +)
A2
Activation of the Ex p relay (N / GND)
L3
Phase L3
L2
Phase L2
L1
Phase L1
N
Neutral conductor

Electrical connections
Ex p relay
Power
Page 18 of 24 Rev. 0 20190910_Manual_Exp-Relais_Power_en.docx
Functional circuit diagram
Connection notes
DANGER
DEATH OR SERIOUS PHYSICAL INJURY WHEN THE COVER OF THE APEX
CONTROL UNIT IS OPENED IN AN EXPLOSIVE ATMOSPHERE.
Risk of explosion.
Before opening the lid of the enclosure, check the atmosphere for
any explosive gases.
ATTENTION
SHORT-CIRCUITS DUE TO LOOSE OR PROTRUDING WIRES IN THE EX P
POWER RELAY.
The Ex p relay may be damaged.
All core wires, including those not required, must be attached to a
terminal.
Lay the wires only in the space between the shield bus and the
connecting terminal.
Make sure that none of the wires are loose or jump out/protrude.
AVOID DAMAGE TO THE SEAL.
Cancellation of the Ex protection concept.
Visual inspection of the seal when closing the Ex p relay (cleanliness,
seat and integrity).
The procedure for connecting cables to the Ex p control unit is described in the
following:
Procedure:
Establish the electrical connections in accordance with the terminal
assignment. Terminals are designed in tension spring technology. A
suitable tool must be used for this purpose.

Ex p relay
Power
Maintenance and care
20190910_Manual_Exp-Relais_Power_en.docx Rev. 0 Page 19 of 24
7Maintenance and care
Find out about the general safety instructions before starting
work (see Chapter 2.4 Safety instructions).
Carry out maintenance and care in accordance with the following sections,
unless otherwise agreed for customer-specific versions.
Maintenance work
Maintenance intervals
MAINTENANCE INTERVALS
Maintenance according to the following maintenance schedule
is recommended in the case of proper operation, observing the
installation instructions and ambient conditions.
ATTENTION
MAINTENANCE AND CARE
The currently applicable regulations and the national provisions must
be observed for maintenance, service and inspection of the
equipment!
Operation and maintenance work may be performed by trained
specialist personnel only. The statutory regulations and the other
binding directives on occupational health and safety, accident
prevention and environmental protection must be observed.
When opening covers or removing parts, unless possible by hand, live
parts may be exposed. Connecting parts may also be live.
Maintenance interval
Work to be performed
Semi-annually
Visual inspection
Annually
Regular maintenance
This manual suits for next models
6
Table of contents