BMC ECON-DB-2 User manual

Page 1 of 29
Models:
ECON-DB-2, ECON-DB-3, ECON-WD-2 & ECON-WD-3
Factory-Installed Vent Option
Use for Enthalpy or Dry Bulb Installations
For Use with 1-1/2 Through 3 Ton
Wall Mount Air Conditioners
and Heat Pumps
NOTE: These instructions are written to cover field-installed economizers, but are also
included with factory-installed economizers. For factory-installed economizers,
all portions addressing “installation” are for reference only.
Full Flow Low Leakage Economizers
with Exhaust for Building Applications
Available with Enthalpy or Dry Bulb Outdoor Control
INSTALLATION INSTRUCTIONS
Manual : 2100-702D
Supersedes: 2100-702C
Date: 11-10-20
BMC, Inc.
Bryan, Ohio 43506

Manual 2100-702D
Page 2 of 29
CONTENTS
GENERAL................................................................... 3
Nomenclature ..................................................... 3
General Information ............................................. 3
Field-Supplied Tools Needed ................................ 3
Unpacking .......................................................... 3
Description ......................................................... 3
INSTALLATION OF FIELD-INSTALLED
ECONOMIZER........................................................... 4
Installation ......................................................... 4
Preparing Unit for Economizer Installation .......... 4
Outdoor Air Sensor Installation .......................... 8
Economizer Installation..................................... 8
Economizer Checkout ..................................... 10
Control Wiring Connection Diagrams..................... 10
START-UP/CHECKOUT PROCEDURES ............... 15
JADE™ Economizer Controller ............................ 15
Review/Customize System Setup...................... 15
Enthalpy Settings .............................................. 19
Economizer Sequence of Operation .....................20
Condition
–
Cool/Dry OA Conditions .................. 20
Condition
–
Warm/Humid OA Conditions ...........20
Economizer Operation for Single Stage .............22
Balanced Climate Mode – S, Y and Z Option
Economizer Sequence of Operation ..................23
Economizer Operation – Balanced Climate Mode
.. 24
FIGURES
Figure 1 Wall-Mount Unit Access Panels ............. 5
Figure 2 Condenser Exhaust Plate with Screen..... 5
Figure 3 Filter and Filter Brackets ...................... 6
Figure 4 Filter Bracket and Filter Bracket
Fill Plate Installation ............................ 7
Figure 5 Outdoor Air Sensor Installation.............. 8
Figure 6 Control Panel....................................... 8
Figure 7 Mixed Air Temp Sensor Installation ........ 9
Figure 8 Vent Option Door Installation............... 10
Figure 9 Programmable Thermostat Connections
for Air Conditioner with Economizer ..... 11
Figure 10 Programmable Thermostat Connections
for Heat Pump with Economizer .......... 12
Figure 11 Non-Programmable Thermostat
Connections for Air Conditioner with
Economizer ....................................... 13
Figure 12 Non-Programmable Thermostat
Connections for Heat Pump with
Economizer ....................................... 14
Figure 13 JADETM Economizer Controller ............. 15
Figure 14 100% Outside Airow Path................. 20
Figure 15 Mixed Airow Path ............................. 20
Figure 16 100% Closed Loop Airow Path .......... 19
Figure 17 CO2Sensor Default and Final Settings
Bard Part #8403-067 CO2Controller ... 25
Figure 18 Wiring Diagram – Enthalpy Sensor ....... 28
Figure 19 Wiring Diagram –
Temperature Only Sensor .................... 29
TABLES
Table 1 Economizer Application ........................ 3
Table 2 System Setup Menu Levels ................. 16
Table 3 Advanced Setup Menu Levels.............. 16
Table 4 Setpoints Menu Levels ....................... 17
Table 5 Checkout Menu Levels........................ 17
Table 6 Status Menu Levels............................ 18
Table 7 Alarm Examples................................. 18
Table 8 Unit Operation with S (Part Flow), Y
and Z (Full Flow) Economizer Options .. 23
GRAPHS
Graph 1 W/J18 Ventilation Delivery ................... 26
Graph 2 W/J24 Ventilation Delivery ................... 26
Graph 3 W/J30 Ventilation Delivery ................... 27
Graph 4 W/J36 Ventilation Delivery ................... 27
ECONOMIZER FEATURES
• One piece construction—easy to install.
• Exhaust air damper—built in with positive closed
position. Provides exhaust air capability to prevent
pressurization of tight buildings.
• JADE™ controller provides nearly limitless
customization on a solid, intuitive electronic
platform.
• Actuator Motor – 24 volt, power-open, spring-
return, direct-coupled with stall protection. Self-
centering shaft clamp and access cover facilitate
ease of replacement/maintenance.
• Proportioning-type control for maximum “free”
cooling economy and comfort with up to 100%
outside air.
• Enthalpy sensor to monitor outdoor air conditions.
• Minimum Ventilation Position available for required
ventilation of occupants or dilution of pollutants.
• Mixed air sensor to monitor outdoor and return air
to automatically modulate damper position.

Manual 2100-702D
Page 3 of 29
GENERAL
General Information
The economizer should only be installed by a trained
heating and air conditioning technician. These
instructions serve as a guide to the technician
installing an economizer package, not as a step-by-step
procedure with which the mechanically inclined owner
can install the package.
The economizer housing is shipped in one carton,
which contains the electrical harness, miscellaneous
hardware and installation instructions.
The economizer installation requires the use of a 2-stage
cooling thermostat (if there is not one already present)
and requisite amounts of low voltage conductor wire for
two-stage cooling. The number of low-voltage control
conductors will vary depending upon application.
If using a master controller, the MC4002 controller is
designed specically to control two (2) redundant wall
mount units equipped with economizers.
Any wall mount unit equipped with an economizer must
also have a factory/eld installed low ambient control.
Please refer to appropriate model/year Specication
Sheet for requisite eld installed low ambient control
kit part numbers.
Field-Supplied Tools Needed
• Appropriate personal protection equipment,
including gloves and safety glasses
• 5/16" nut driver
• Phillips head screwdriver
• Small flat head screwdriver for securing wire in
terminal blocks
• Electrical tools
• Multimeter
Unpacking
Upon receipt of the equipment, be sure to compare the
model number found on the shipping label with the
accessory identication information on the orders and
shipping document to verify that the correct accessory
has been shipped.
Inspect the carton housing of each economizer assembly
as it is received and, before signing the freight bill, verify
that all items have been received and there is no visible
damage. Note any shortages or damage on all copies
of the freight bill. The receiving party must contact the
last carrier immediately, preferably in writing, requesting
inspection by the carrier’s agent. Concealed damage not
discovered until after loading must be reported to the
carrier within 15 days of its receipt.
Description
ECON-DB and ECON-WD economizers are designed
to be used with the wall mount series air conditioners
and heat pumps, shown in Table 1, equipped with
low ambient controls. They are electromechanical
economizer systems designed to provide “free” cooling
where the outdoor air temperature/enthalpy is cool
enough to provide the needed cooling without running
the compressor, or in addition to the compressor. When
cooling is required, the system automatically takes
advantage of cold outdoor air when available and uses
it for rst stage cooling. This then reduces the need
to run the air conditioning compressor providing lower
operating costs and increasing the service life of the
equipment. If the outdoor air temperature/enthalpy
is too warm to be sufcient for cooling, the dry bulb
outdoor air temperature sensor detects the condition
and automatically closes the outdoor air intake/exhaust
damper, opens the return air damper and switches to
compressor-only operation.
Without attention from the end user, the economizer
assembly is meant to automatically achieve maximum
savings while ensuring appropriately cool space
temperatures. The economizer utilizes a fully
modulating damper actuator, which will control intake/
exhaust in order to obtain and maintain a factory-set
minimum supply air temperature. As a secondary
feature, the economizer assembly can be programmed
for a minimum ventilation based on an “occupied”
(or otherwise dedicated) 24V signal to satisfy fresh
air ventilation on populated structures or dilution of
internal pollutants.
ECON-DB and ECON-WD Series economizers are not
for use with variable capacity ECU models.
TABLE 1
Economizer Application
Low ambient control is required w/economizer for low
temperature operation.
Model For Use with the Following Units
ECON-DB-2
ECON-WD-2
W/J17A
W/J18A
W/J24A
W/J18H
W/J24H
W/J17L
W/J18L
W/J24L
ECON-DB-3
ECON-WD-3
W/J30A
W/J36A
W/J30H
W/J36H
W/J30L
W/J36L
Economizer with Exhaust Model
Nomenclature
DB – Temperature Only
WD – Wet/Dry Bulb
Cabinet Size
2 – 2 Ton
3 – 3 Ton
(See Table 1)
ECON – WD – 2
Economizer

Manual 2100-702D
Page 4 of 29
INSTALLATION OF FIELD-INSTALLED ECONOMIZER
Installation
Electrical shock hazard.
Disconnect remote electrical power supply
or supplies before servicing.
Failure to do so could result in electric
shock or death.
!WARNI NG
Sharp metallic edges.
Take care and wear appropriate protective
devices to avoid accidental contact with
sharp edges.
Failure to do so can result in personal
injury.
!CAUTI ON
Exposed moving parts.
Disconnect all electrical power before
servicing.
Failure to do so can result in severe injury
or amputation.
!WARNI NG
Preparing Unit for Economizer Installation
1. Disconnect power to unit.
2.
Unpack the economizer assembly, which
includes the integral economizer with attached
electrical harness, mixed air sensor, body panels,
miscellaneous hardware and installation instructions.
3. From existing wall mount unit, remove and save (or
discard) as directed (see Figure 1):
• Blower access panel and screws (save)
• Ventilation access panel (discard)
• Filter access panel (discard)
• Filter (save)
• Outer and inner control panel doors and screws
(save)
4. Remove and discard the exhaust cover plate (save
screws).
5. Install new condenser exhaust plate with screen
over opening into condensor section (see Figure 2).
6. Remove lter brackets if necessary (see Figure
3 on page 6): Two types of lter brackets have
been used with these wall mount units. If the
lter brackets are mounted at, they can be used
with the economizer. If the lters are set at a
30°angle, they must be removed and discarded for
economizer installation. The circuit breaker offset
plate must be loosened and moved slightly to gain
access to several of the screws holding the lter
brackets in place. Tighten screws holding control
panel after lter brackets have been removed.
If lter brackets were removed in Step 6, proceed to
Step 7. If the brackets were not removed, proceed
to Outdoor Air Sensor Installation on page 8.
7. Install lter bracket ll plate as shown in Figure 4
on page 7.
8. Install provided lter brackets on economizer (see
Figure 4).

Manual 2100-702D
Page 5 of 29
FIGURE 1
Wall-Mount Unit Access Panels
MIS-3619 A
CONTROL PANEL
DOOR
FILTER
PANEL
BLOWER ACCESS
(THIS PANEL IS DISCARDED)
VENTILATION ACCESS PANEL
PANEL
DISCARDED)
(THIS PANEL IS
ACCESS DOOR
CIRCUIT BREAKER
FILTER ACCESS
FILTER BRACKETS
INNER CONTROL
PANEL DOOR
CONDENSEREXHAUST
PLATE (DISCARD AND
SAVE SCREWS)
MIS-3620
SHOWN FACING DOWN
PARTITION SUPPORT ANGLE
PARTITION
CONDENSERPARTITION (HIDDEN)
SCREEN MEDIA FACING
4 SCREWS
INSTALL COVER PLATE
PARTITION COVER
PLATE
FIGURE 2
Condenser Exhaust Plate with Screen

Manual 2100-702D
Page 6 of 29
FIGURE 3
Filter and Filter Brackets
REFERENCE
ANGLE
30
30° REFERENCE
ANGLE
BRACKET
LEFT FILTER
THERMISTOR
BRACKET
FILTER
RIGHT FILTER
LOCATION
MOUNTING HOLE
LOCATED BEHIND THE
C. BREAKER
OFFSET PLATE
FOR THE 30 RIGHT
FILTER BRACKET
MIS-3621

Manual 2100-702D
Page 7 of 29
FIGURE 4
Filter Bracket and Filter Bracket Fill Plate Installation
LEFT HAND VENT
RIGHT HAND VENT
BRACKET
LONG FILTER (4) REGULAR SCREWS
BRACKET
LONG FILTER
BRACKET
SHORT FILTER
(4) REGULAR SCREWS
MIS-3814
LEFT HAND UNITRIGHT HAND UNIT
INSTALL FILTER BRACKET
FILL PLATE WITH (2) SCREWS
(ONLY FOR 2-3 TON UNITS)

Manual 2100-702D
Page 8 of 29
EnthalpyTemperature Only
FIGURE 5
Outdoor Air Sensor Installation
Outdoor Air Sensor Installation
1. Remove and save both side grilles and screws.
2. Install the outdoor air sensor (temperature only or
enthalpy) in the lower condenser section on the
side opposite the control panel with two (2) screws
provided. Tube end of sensor should mount ush
with base (see Figure 5).
NOTE: The temperature-only sensor is shipped with
a bracket attached. The bracket is not needed for 2
and 3 ton Series 1 units and must be removed before
installation.
3. Route the wire harness across the back of the unit
and secure with two wire ties (provided). Push
harness up through the grommet in the bottom of
the control panel. Secure with wire ties (provided)
to the other wires in the grommet. Ensure the wire
harness cannot contact moving parts or copper
tubing. Replace side grilles.
Economizer Installation
1. Connect 12-pin male plug into female plug in side
of the control panel as shown in Figure 6. See
wiring diagrams found on pages 11 – 14.
2. Remove (and discard) left and right lter brackets
from economizer assembly if existing wall mount
unit brackets are in place.
3. Insert economizer into opening in wall unit
between the lter rack (if not removed earlier) and
condenser section, being careful not to tear unit
insulation. To clear blowers, position economizer at
45° angle under the blowers. Fully seat economizer
assembly to the rear of the wall unit cavity. Slide
economizer to right and line up with return air
opening in back of wall unit.
FIGURE 6
Control Panel
RED AND BLACK
LOW VOLTAGE
SENSOR
WIRES TO
TERMINAL BOARD
PLUG
WIRES FROM
LOW VOLTAGE
TERMINAL BOARD
WIRE HARNESS
MIS-4005

Manual 2100-702D
Page 9 of 29
MIS-3765
AIRFLOW
COIL
TOP OF OUTDOOR
FILTER/FILTER RACK
AFTER SLIDING THE VENT PACKAGE
INTO THE WALL MOUNT, SLIDE IT
TOWARD THE CONTROL PANEL SIDE
ALIGNING IT WITH THE RETURN AIR
OPENING IN THE REAR
THE WIRE HARNESS
FROM THIS LOCATION
ON THE VENT PACKAGE
WILL PLUG INTO THE
FRONT SIDE OF THE
CONTROL PANEL
CONTROL PANEL
(RH SHOWN)
4. Route the two orange wires along refrigerant lines
behind the lter bracket (if applicable) to terminate
at the blower partition (see Figure 7).
5. Install the mixed air temperature sensor and
bracket in blower partition (see Figure 7) using
the two existing holes. If necessary, remove the
shield to aid in mounting the sensor (replace after
mounting sensor). Insert white, two-pin sensor plug
into sensor housing. Coil excess orange wires and
wire tie to suction/discharge line.
FIGURE 7
Mixed Air Temperature Sensor Installation
TEMPERATURESENSOR
MIXED AIR
BRACKETPART #113-468
MIXED AIR
TEMPERATURESENSOR
PART #8602-058
(C7250A1001)
TOP VIEW
ORANGE WIRES
MIS-3622
6. Run black and red wire from economizer upper
12-pin wiring harness through grommet and other
bushing into the control panel and connect to the
black and red wire sensor wires (see Figure 6).
Wrap and wire tie the excess wire.
7. Remove hood front (grille), mist lter and control
door.
8. Lift economizer hood to unit and hold in position.
Line up four (4) holes in outer economizer hood
door (two on each side) with corresponding holes in
OPPOSITE SIDE FOR LEFT
HAND UNITS

Manual 2100-702D
Page 10 of 29
FIGURE 8
Vent Option Door Installation
MIS-3627
HIDDEN COMPONENTS
FOR CLARITY
BETWEENVENT OPTION & DOOR
(10) SCREWS TO SEAL
INSERT (4) SCREWS
TO HOLD DOOR IN
PLACE.
MIST ELIMINATOR
AIRFLOW
DIRECTION
12 PIN
CONNECTORS
JADE CONTROLLER LOCATION
FILTER DOOR
unit and mount economizer hood to unit with four
(4) screws.
9. Connect vent option front to vent hood door (see
Figure 8) using ten (10) screws (supplied).
10. Connect economizer upper and lower 12-pin wiring
connectors to 12-pin wiring connectors inside
economizer control panel.
11. Re-insert lter into lter brackets. Arrow on lter
should point up.
12. Attach blower access panel.
Economizer Checkout
Since observation of motor/damper operation is difcult
after air hood installation, it is recommended the unit
be enabled for start-up now. If no power is available, or
if immediate start-up is not desired, continue with the
basic installation process by skipping to Step 4. The air
hood assembly can be partially disassembled at a later
time for start-up/checkout procedures.
1. Attach wall unit outer and indoor control panel
doors.
2. Turn power to unit on.
3. Complete economizer checkout using economizer
control touchpad (see CHECKOUT on page 17).
4. After conrming economizer operation, attach the
economizer hood mist eliminator (with airow arrow
pointed towards unit), control door and front door.
Control Wiring Connection Diagrams
The control wiring diagrams on pages 11 – 14
represent typical control wiring for single units
controlled by individual thermostats. If thermostats
other than those referenced are used, the installer must
verify output functions accordingly.
For dual unit installation utilizing lead/lag controller
systems, complete details are contained in MC4002
Series Lead/Lag Controller installation manual 2100-
614. For operation with MV5000 lead/lag controller,
see MV5000 installation manual 2100-636.

Manual 2100-702D
Page 11 of 29
FIGURE 9
Programmable Thermostat Connections for Air Conditioner with Economizer
Thermostat W1/E AYO/D
LO/BY2Y1R GC W2
Bard #8403-060
61012
119 4
12-Pin
Vent Plug
23 5 7
CO2 OUT
Optional CO2 Controller
Bard Part #8403-067
6
5
4
3
2
1
TEMP-OUT
24VAC
W3 65421R
Unit Low
Voltage
Term. Strip
W2C GRT Y1 Y2 B/W1 L DA 3
mode.
8
7
6
Do not connect "A" from thermostat if optional CO2 controller is used
0-10 VDC modulating C02 control signal for modulating ventilation
control (optional for ECON only)
5
Change model configuration from heat pump to heat/cool. Must be configured to programmable
and fan set to be programmed fan for the "A" output to function during scheduled occupied
periods. Must be configured for multi-stage for Y1 output to be active 1st stage cooling. For
dehumidification, must be configured for "No Economizer" for YO/D to be active for humidity
control.
4
Factory installed jumper. Remove jumper and connect
to N.C fire alarm circuit if emergency shutdown required.
3
Wire not needed below 15KW.2
Wire required for dehumidification models only.
1
Do not add these wires if setting up for modulating control. See note 6.
Install jumper for 1 stage electric heat on units with less than 15KW
9Factory installed jumper. Remove jumper to activate Balanced Climate™
A 2-stage thermostat is recommended for Balanced Climate mode.
W1/E
SC SC
SC
Completestat
Model #CS9B-THOA or
Model #CS9BE-THOA
W2
COM G
24V Y1 Y2 O/B L DA GND
ALL VENT OPTIONS PLUG IN HERE
2
3
3
1
6
2
4
5
7
If not equipped with a ventilation option to plug in, a jumper plug must be installed.
4
8
9
MIS-4080 A

Manual 2100-702D
Page 12 of 29
FIGURE 10
Programmable Thermostat Connections for Heat Pump with Economizer
Thermostat W1/E AYO/D
LO/BY2Y1R GC W2
Bard #8403-060
61012
119 4
12-Pin
Vent Plug
23 5 7
CO2 OUT
Optional CO2 Controller
Bard Part #8403-067
6
5
4
3
2
1
TEMP-OUT
24VAC
W3 65421R
Unit Low
Voltage
Term. Strip
W2C GRT Y1 Y2 B/W1 L DA 3
W1/E
SC SC
SC
Completestat
Model #CS9B-THOA or
Model #CS9BE-THOA
W2
COM G
24V Y1 Y2 O/B L DA GND
Factory installed jumper. Remove jumper and connect
Wire not needed below 15KW.
4
5
Do not add these wires if setting up for modulating control.
Jumper is located in jade wiring harness.
1
0-10 VDC modulating C02 control signal for modulating ventilation
3
6
8
2
dehumidification, must be configured for "No Economizer" for YO/D to be active for humidity
periods. Must be configured for multi-stage for Y1 output to be active 1st stage cooling. For
Wire required for dehumidification models only.
3
1
5
control (optional for ECON only - see vent instruction manuals)
2
If notequipped with a ventilation option to plug in, a jumper plug mustbe installed.
to N.C fire alarm circuit if emergency shutdown required.
4
control.
7
and fan set to be programmed fan for the "A" output tofunction during scheduled occupied
4 Do not connect "A" from thermostat if optional CO2 controller is used
6
2
3
ALL VENT OPTIONS PLUG IN HERE
7
Ensure model configuration is heat pump and not heat/cool. Must be configured to programmable
8Factory installed jumper. Jumper is not installed on unit with economizers.
MIS-4063 C

Manual 2100-702D
Page 13 of 29
IMPORTANT NOTE
An additional wire change is required if jumper 4 is used which connects "A" to "G" (shown on Figures 18 and
19 on pages 28 and 29). The red/white wire on the blower interlock relay (located on the vent control plate)
needs to be moved from the "common" terminal to the "normally closed" terminal. If this change is not made,
the relay will latch on once the "A" signal is received and the blower will not turn off. Refer to pages 28 and 29
to see the vent wiring diagram with this change called out.
FIGURE 11
Non-Programmable Thermostat Connections for Air Conditioner with Economizer
CO2 OUT
Optional CO2 Controller
Bard Part #8403-067
6
5
4
3
2
1
TEMP-OUT
24VAC
W3 65421R
Unit Low
Voltage
Term. Strip
W2C GRT Y1 Y2 B/W1 L DA 3
Factory installed jumper. Remove jumperto activate Balanced Climate™Mode.
A 2-stage thermostat is recommended for Balanced Climate mode.
9
5 Do notadd these wires if setting up for modulating control. See note 6.
7
Jumperneedsadded.8
For 8403-058, change "system type", set up Function 1, From 5 (2 Heat/ 1 Coolheat Pump)
to 6 (2 Heat / 2 Cool Conventional). For 8403-059, No change required.
2B Install Jumperfor 1 stage electricheaton units with more
than 10KW.
0-10 VDC Modulating CO2 control signal for modulating ventilation control
(Optionalfor ECON Only)
6
For ventoperation,add jumper if optional CO2 controller is not used.
Ventwill run while blower is energized.
4
Factory installed jumper. Remove jumperand connect
to N.C fire alarm circuit if emergency shutdown required.
3
Wirenotneeded below 15KW.
2A
Wire required for dehumidification models only.
1
61012
119 4
12-Pin
Vent Plug
23 5 7
Rc
3
C
8403-038
2B
Y
ALL VENT OPTIONS PLUG IN HERE
Y8403-047
4
or T6 Pro 8403-090
R W
Units With Dehumidification
G
5
Y2 W2
4
3
1
6
7
R
T4 Pro 8403-089 G
Rc
8
Mechanical Humidistat
Electronic Humidistat
C
2A
If notequipped with a ventilation option to plug in, a jumper plug must be installed.
(TH522OD1219/U)
8403-059
(TH522OD1151)
8403-058
6
O
5
9
WB
MIS-4079 A

Manual 2100-702D
Page 14 of 29
IMPORTANT NOTE
An additional wire change is required if jumper 4 is used which connects "A" to "G" (shown on Figures 18 and
19 on pages 28 and 29). The red/white wire on the blower interlock relay (located on the vent control plate)
needs to be moved from the "common" terminal to the "normally closed" terminal. If this change is not made,
the relay will latch on once the "A" signal is received and the blower will not turn off. Refer to pages 28 and 29
to see the vent wiring diagram with this change called out.
FIGURE 12
Non-Programmable Thermostat Connections for Heat Pump with Economizer
CO2 OUT
Optional CO2 Controller
Bard Part #8403-067
6
5
4
3
2
1
TEMP-OUT
24VAC
W3 65421R
Unit Low
Voltage
Term. Strip
W2C GRT Y1 Y2 B/W1 L DA 3
Factory installed jumper. Remove jumperto activate Balanced Climate™Mode.
A 2-stage thermostat is recommended for Balanced Climate mode.
5Do notadd these wires if setting up for modulating control. See note 6.
7
Jumperneedsadded.8
For 8403-058, change "system type", set up Function 1, From 5 (2 Heat/ 1 Coolheat Pump)
to 6 (2 Heat / 2 Cool Conventional). For 8403-059, No change required.
0-10 VDC Modulating CO2 control signal for modulating ventilation control
(Optionalfor ECON Only) - See vent installation manual.
6
For ventoperation,add jumper if optional CO2 controller is not used.
Ventwill run while blower is energized.
For ECON & CRV-V, an additionalwire change is required.
See install manual
4
Factory installed jumper. Remove jumperand connect
to N.C fire alarm circuit if emergency shutdown required.
3
Wirenotneeded below 15KW.
2
Wire required for dehumidification models only.
1
9
61012
119 4
12-Pin
Vent Plug
23 5 7
W
ALL VENT OPTIONS PLUG IN HERE
(TH522OD1151)
3
(TH522OD1219/U)
If notequipped with a ventilation option to plug in, a jumper plug must be installed.
8403-058
2
3
O/BRc CR G Y Y2 AUX
4
E
56
Mechanical Humidistat
8403-038
Electronic Humidistat
4
1
Units With Dehumidification
or T6 Pro 8403-090
BCRc YR G O
8403-059
T4 Pro 8403-089
8403-047
6
5
8
7
MIS-4122
9

Manual 2100-702D
Page 15 of 29
JADE™ Economizer Controller
W7220 controller offers unparalleled exibility and
expansion in a dependable and solid electronic
platform.
• Multiple economizer applications from one
controller.
• Nearly limitless customization of setpoints.
• Internal checkout menu provides fast performance
assessment.
• Alarms menu provides assistance in
troubleshooting.
Memory: User-dened setpoints remain in non-
volatile ash memory regardless of electrical outage
duration. Control voltage below 18V may cause erratic
performance.
START-UP/CHECKOUT PROCEDURES
FIGURE 13
JADETM Economizer Controller
MENU UP
(EXIT)
BUTTON
SCROLL
(UP/DOWN)
BUTTONS
SELECT (ENTER)
BUTTON
2 LINE
LCD
From the factory, the JADE™ economizer controller
has been preset with “default” values that were pre-
determined as optimum for equipment buildings,
and these are shown in Tables 2 – 4. However, it is
important to review and/or customize these operational
values per owner specications in order to guarantee
satisfactory performance.
The installing contractor can easily access the JADE™
programming by the integral keypad and LCD display.
There are six (6) basic MENU categories to navigate:
1. STATUS – provides real-time access to sensor
input, damper and equipment operation.
2. SETPOINTS – customizable operational
parameters.
3. SYSTEM SETUP – customizable application
programming (see Revew/Customize System
Setup).
4. ADVANCED SETUP – further application and
operational options.
5. CHECKOUT – instantly activate and verify
economizer functions.
6. ALARMS – displays alarms and pinpoints problem
areas.
Review/Customize System Setup
Before being placed in service, the JADE™economizer
controller programming should be reviewed/customized
through the following steps:
1. SYSTEM SETUP: from the main screen, press the
SCROLL (UP/DOWN) BUTTONS to navigate through the
six (6) basic menu items to the SYSTEM SETUP menu.
– Push the SELECT (ENTER) BUTTON to choose the
SYSTEM SETUP menu.
– Navigate through the multiple levels of SYSTEM
SETUP by pushing the SCROLL (UP/DOWN)
BUTTONS.
– To change a specic parameter in the SYSTEM
SETUP menu, press the SELECT (ENTER)
BUTTON to display its current value. Press the
SCROLL (UP/DOWN) BUTTONS to change or
increase/decrease value. Press the SELECT
(ENTER) BUTTON to save the new customized
value—“CHANGE STORED” will be displayed.
Press the SELECT (ENTER) BUTTON again to
return to current menu parameter.
– For specic SYSTEM SETUP level information,
refer to Table 2 on page 16.
NOTE: During an extended level of inactivity, the
display of the JADE™ economizer controller will begin
to automatically scroll through the various levels of the
STATUS menu as a screensaver. Each level will stay for
approximately 5 seconds before changing to the next
level.

Manual 2100-702D
Page 16 of 29
TABLE 2
System Setup Menu Levels
TABLE 3
Advanced Setup Menu Levels
Menu Level Default
Value Range Notes
INSTALL 01/01/10 Display Order = MM/DD/YY
Setting Order = DD/MM/YY
UNITS DEG °F °F / °C Sets controller to read in
either measurements
EQUIPMENT HP(B) HP Heat Pump HP
CONV = A/C
AUX IN HP(B) HP(O)
HP(B
Energize on Cool
Energize on Heat
FAN SPEED 1 Speed 1 Speed
2 Speed
FAN CFM 5000 100 to
15000 Not applicable
AUX OUT EXH2
NONE
ERV
EXH2
SYS
Product can be used to
signal other devices
OCC INPUT INPUT or
ALWAYS
INPUT is for dedicated OCC
signal, ALWAYS is for all
other situations
FACTORY
DEFAULT NO YES or
NO
Resets to factory defaults if
changed to YES
Menu Level Default
Value Range Notes
MA
LOW
SET
45°F 35-55° Temp to activate freeze
protection — Close Damper
FREEZE
POS CLO CLO or
MIN
Damper position upon freeze
protection
STG3
DLY 15 MIN 0 to 4.0h
or OFF
Delay for 3rd Stage Cooling –
allows for 3 stages of cooling,
one stage for econ & two
stages for compressor
DMPR
POS CLO CLO or
OPN
Where damper goes upon
shutdown signal
MA T
CAL 0.0°F
+/-2.5°F
from
actual
reading
Mixed Air Sensor temperature
calibration
OA T
CAL 0.0°F
+/-2.5°F
from
actual
reading
Outdoor Air Sensor
temperature calibration
OAS H
CAL 0%
+/-10%
from
actual
reading
Outdoor Air Humidity Sensor
calibration for economizers
using temp/humidity sensor
* In SYS SETUP, the correct Equipment setting is HP
and for the AUX2 IN is HP (B) in all applications.
This is correct for both air conditioner and heat
pump equipment in order to have correct operating
sequences for the economizers. DO NOT change to
CONV = A/C setting just because the equipment is
an air conditioner and not a heat pump.
2. ADVANCED SETUP: from the main screen, press the
SCROLL (UP/DOWN) BUTTONS to navigate through
the six (6) basic menu items to the ADVANCED SETUP
menu.
– Push the SELECT (ENTER) BUTTON to choose the
ADVANCED SETUP menu.
– Navigate through the multiple levels of ADVANCED
SETUP by pushing the SCROLL (UP/DOWN)
BUTTONS.
– To change a specic parameter in the ADVANCED
SETUP menu, press the SELECT (ENTER)
BUTTON to display its current value. Press the
SCROLL (UP/DOWN) BUTTONS to change or
increase/decrease value. Press the SELECT
(ENTER) BUTTON to save the new customized
value—“CHANGE STORED” will be displayed.
Press the SELECT (ENTER) BUTTON again to
return to current menu parameter.
– For specic ADVANCED SETUP level information,
refer to Table 3.
*
*
3. SETPOINTS: from the main screen, press the
SCROLL (UP/DOWN) BUTTONS to navigate through the
six (6) basic menu items to the SETPOINTS menu.
– Push the SELECT (ENTER) BUTTON to choose the
SETPOINTS menu.
– Navigate through the multiple levels of SETPOINTS
by pushing the SCROLL (UP/DOWN) BUTTONS.
– To change a specic parameter in the SETPOINTS
menu, press the SELECT (ENTER) BUTTON to
display its current value. Press the SCROLL (UP/
DOWN) BUTTONS to change or increase/decrease
value. Press the SELECT (ENTER) BUTTON
to save the new customized value—“CHANGE
STORED” will be displayed. Press the SELECT
(ENTER) BUTTON again to return to current menu
parameter.
– For specic SETPOINTS level information, refer to
Table 4.
NOTE: At this point, the economizer assembly should
be fully functional and ready for preliminary testing.

Manual 2100-702D
Page 17 of 29
TABLE 5
Checkout Menu Levels
TABLE 4
Setpoints Menu Levels
Menu Level Default
Value Range Notes
MAT
SET 53°F 38°F to
65°F
Mixed Air Temperature setpoint
at which the economizer
damper will begin to modulate
to maintain setting
LOW T
LOCK 0°F -45°F to
80°F
Low outdoor ambient
temperature for compressor
lockout
DRYBLB
SET 60°F 48°F to
80°F
Maximum outdoor
temperature setting for “free”
economizer cooling
ENTH
CURVE ES3
ES1,
ES2,
ES3,
ES4 or
ES5
Enthalpy boundary “curves”
for economizers using temp/
humidity sensor, see “Enthalpy
Settings” explanation
MIN
POS 2V 2 to 10
VDC
Actuator voltage for Minimum
Position – see Minimum
Position Note
EXH1 50% 0 to
100%
Setpoint for damper if exhaust
fan is powered by economizer
EXH2 6% 0 to
100% Setpoint for AUX output signal
DCV SET
(See NOTE
under Table
7 on page
18)
1100 500 to
2000
Displays only if a CO2sensor
is connected. Setpoint for
Demand Control Ventilation
of space. Above the setpoint,
the OA dampers will modulate
open to bring in additional OA
to maintain a space ppm level
below the setpoint.
NOTE: CHECKOUT functions bypass the normal
5-minute delay for compressor protection. Be sure to
allow for enough time to pass between tests so the
compressor is not damaged from extreme short-cycling.
MINIMUM POSITION NOTE: Minimum position
setting has been preset to 10V which when connected
to MC4002 Lead/Lag Controller System will allow
economizer to drive wide open per emergency ventilation
strategy as detailed in MC4002 Instructions. This may
require resetting to a lower value per job specifications.
4. CHECKOUT: from the main screen, press the
SCROLL (UP/DOWN) BUTTONS to navigate through the
six (6) basic menu items to the CHECKOUT menu.
– Push the SELECT (ENTER) BUTTON to choose the
CHECKOUT menu.
– Navigate through the multiple levels of CHECKOUT
by pushing the SCROLL (UP/DOWN) BUTTONS.
– To perform a specic test in the CHECKOUT menu,
press the SELECT (ENTER) BUTTON to choose a
particular exercise, “RUN?” will appear. Press the
SELECT (ENTER) BUTTON again to activate this
exercise. After a short pause, “IN PROGRESS” will
appear as the test activates. “DONE” will display
after the test is complete. Press the MENU UP
(EXIT) BUTTON to end the test and/or turn off the
activated relay.
– For specic CHECKOUT level information, refer to
Table 5.
NOTE: Economizer assembly should be ready to
put into service. At any point during operation, in
economizer mode or idle, real-time information from
sensors and integral components can be accessed from
the STATUS menu.
5. STATUS: from the main screen, press the SCROLL
(UP/DOWN) BUTTONS to navigate through the six (6)
basic menu items to the STATUS menu.
– Push the SELECT (ENTER) BUTTON to choose the
STATUS menu.
– Navigate through the multiple levels of STATUS by
pushing the SCROLL (UP/DOWN) BUTTONS.
– As the STATUS menu simply gives input/output
information in real-time, there is no way to
change or otherwise alter the displayed criteria.
It is simply a window into the operation of the
economizer controller.
– For specic STATUS level information, refer to
Table 6 on page 18.
NOTE: Upon power-up (or after power failure or low
voltage condition), the controller will begin a 5-minute
time delay before enabling mechanical cooling.
Menu Level Notes
DAMPER VMIN-HS Positions damper to the minimum amount
of opening allowed by actuator
DAMPER VMAX-HS
Opens damper to the MIN POS level
indicated in the SETPOINTS menu. See
Minimum Position Note above.
DAMPER OPEN Forces damper to full open position, energizes
exhaust contacts
DAMPER CLOSE Positions damper to completely closed
position
CONNECT Y1-O Forces Y1-OUTPUT to compressor
CONNECT Y2-O Forces Y2-OUTPUT to compressor
CONNECT EXH1 Setpoint for damper if exhaust fan is
powered by economizer
CONNECT EXH2 Setpoint for AUX output signal
CONNECT AUX
Depending upon AUX OUT setting from
SYSTEM SETUP menu:
NONE – no action
ERV – 24VAC out for ERV & NOT
Economizer
SYS – 24VAC out for alarm

Manual 2100-702D
Page 18 of 29
TABLE 7
Alarm Examples
Alarm(s) Notes
MA T SENS ERR Malfunctioning mixed air sensor
OA T SENS ERR Malfunctioning outdoor air sensor
ACT STALLED Actuator cannot reach desired percentage of
opening
SYS ALARM If AUX is set to SYS in SETPOINTS menu,
SYS will display upon any registered alarm
NOTE: This is not a complete list of alarms. Additional alarms
will display depending upon the parameter settings and
conguration and attached equipment.
TABLE 6
Status Menu Levels
NOTE: When using the Bard 8403-067 CO2controller,
congure the sensor to 2-10VDC output (see CO2
sensor instructions).
The JADETM controller default setting is 1100 PPM.
The economizer will modulate to maintain this CO2
level in the room. The default setting can be changed
in the SETPOINT menu in the DCV SET option. Default
settings and DCV MIN and DCV MAX will appear only
when the CO2sensor is connected.
In the SETPOINT menu, change the MAX VENT setting
to 9.5 volts.
The CO2controller is active at any time the A terminal
is energized.
The status of the CO2input can be viewed at any time
in the STATUS menu.
Menu Level Default
Value Notes
ECON AVAIL YES/NO Indicates if conditions are
favorable for economizing
ECONOMIZING YES/NO Indicates if economizer is
actively economizing
OCCUPIED YES/NO
Indicates if dedicated 24V
occupied signal is being received
on terminal OCC
HEAT PUMP COOL/HEAT Displays actual compressor use
if in HEAT PUMP mode
COOL Y1-IN ON/OFF Indicates if 24V signal is being
received on terminal Y1-I
COOL Y1-OUT ON/OFF
Displays if controller is
actively calling for mechanical
compressor cooling (24V on
Y1-O)
COOL Y2-IN ON/OFF Indicates if 24V signal is being
received on terminal Y2-I
COOL Y2-OUT ON/OFF
Displays if controller is actively
calling for Stg. 2 cooling
(24V on Y2-O)
MA TEMP 0° to 140°F Current mixed air temp
OA TEMP -40° to
140°F Current outdoor air temp
OA HUM 0% to 100%
Current outdoor air humidity
for economizers using temp/
humidity sensor
DAMPER OUT 2.0 to 10.0 Displays voltage to actuator
ACT POS 0 to 100% Current % of opening
ACT COUNT N/A Current count of actuator cycles
from installation
ACTUATOR OK YES/NO Indicates potential fault
EXH1 OUT ON/OFF Output of EXH1 Terminal
MECH COOL ON 0, 1, or 2 Stages of mechanical cooling
currently active
NOTE: If there are any potential problems recognized
by the economizer controller, it may be registered
in the form of an alarm in the ALARM(S) menu. If
there is a period of inactivity AND there is an alarm
registering, the controller will randomly scroll through
the ALARM(S) menu items as a screensaver.
ALARM(S): from the main screen, press the SCROLL
(UP/DOWN) BUTTONS to navigate through the six (6)
basic menu items to the ALARM(S) menu.
– Push the SELECT (ENTER) BUTTON to choose the
ALARM(S) menu.
– Navigate through the current alarms in ALARM(S)
by pushing the SCROLL (UP/DOWN) BUTTONS.
–
Once the alarm has been identied, and the cause
has been removed (e.g., replaced faulty sensor), the
alarm may erase itself. If a manual alarm-erasing
is required, it can be cleared from the display by
navigating to the desired alarm and pressing the
SELECT (ENTER) BUTTON to choose that specic
alarm. “ERASE?” will display. Press the SELECT
(ENTER) BUTTON again. “ALARM ERASED” will
appear. Press the MENU UP (EXIT) BUTTON to
complete the action and return to the previous menu.
– For specic ALARM(S) information, refer to
Table 7.

Manual 2100-702D
Page 19 of 29
Enthalpy Settings
If economizer is enthalpy-based and was shipped with
the temp/humidity sensor, the economizer must be
programmed for the specic enthalpy curve boundary
desired for “free” outdoor cooling. The available
enthalpy boundaries are all subject to specic OA
temperature, OA humidity and OA dew points. If all of
the OA conditions are below the specic points outlined
in each boundary, the conditions are good to economize
and economizer mode is set to “YES”. If some or all
the OA conditions are above the specic points outlined
in each boundary, the conditions are not good to
economize and the economizer mode is set to “NO”.
ES3 is factory default.

Manual 2100-702D
Page 20 of 29
FIGURE 14
100% Outside Airow Path
FIGURE 15
Mixed Airow Path
RETURN AIR
SUPPLY AIR
COOLING COIL
EXHAUST AIR
OUTDOOR AIR
CONDENSER AIR
ELIMINATOR
AIR FILTER
MIST
CONDENSER COIL
MIS-3613
MIS-3612
ELIMINATOR
RETURN AIR
OUTDOOR AIR
EXHAUST AIR
MIST
AIR FILTER
SUPPLY AIR
Economizer Sequence of Operation
Condition – Cool/Dry OA Conditions
• 1st Stage Cooling closes and sends signal to
JADE™ control. Since the air temperature outside
is cooler than the preset DRYBULB SET setting,
or is below the ENTH CURVE boundary in the
SETPOINTS menu, the actuator will power the
economizer damper to “economizer” mode as the
indoor blower motor starts. The mixed air sensor
senses a mixture of return air and cool outdoor
air and modulates opening to achieve preset MAT
SET setting in SETPOINTS menu. Compressor
operation is inhibited (see Figure 14).
• 2nd Stage Cooling closes and sends a signal to
JADE™ control, which closes the Y1-O relay to
begin mechanical cooling. The economizer damper
REMAINS OPEN in tandem operation with the
compressor as long as the OA conditions do not
drop below the preset DRYBULB SET/ENTH
CURVE settings in the SETPOINTS menu (see
Figure 15).
• 3rd Stage Cooling (if available) closes and sends a
signal to JADE™ control, which closes the Y2-O
relay to begin 2nd stage mechanical cooling. The
economizer damper REMAINS OPEN in tandem
operation with the compressor as long as the
temperature outside does not drop below the
preset DRYBULB SET setting in the SETPOINTS
menu (see Figure 15).
Condition – Warm/Humid OA Conditions
• 1st Stage Cooling closes and sends signal to
JADE™ control. Since the OA conditions are above
the preset DRYBULB SET/ENTH CURVE setting
in the SETPOINTS menu, the control will simply
close the Y1-O relay to initiate mechanical cooling.
The economizer damper will remain closed or in
a minimum ventilation setting depending upon
occupied status (see Figure 16).
• 2nd Stage Cooling (if available) closes and sends a
signal to JADE™ control. Since the OA conditions
are still above than the preset DRYBULB SET/
ENTH CURVE setting in the SETPOINTS menu,
the control will simply close the Y2-O relay
to initiate 2nd stage mechanical cooling. The
economizer damper will remain closed or in a
minimum ventilation setting depending upon
occupied status (see Figure 16).
This manual suits for next models
3
Table of contents
Popular Air Conditioner manuals by other brands

Toshiba
Toshiba RAS-18SKV-E Series Service manual

Samsung
Samsung AR**HV5D series User's installation guide

Honeywell
Honeywell CL30XC owner's manual

Airwell
Airwell Electra JMF Hi wall Series Service manual

Airxcel
Airxcel Marvair ComPac II AVHDA90 Installation & operation manual

Stealth
Stealth Designer SC-24CC-UM quick start guide

Technibel
Technibel KPAFP165R5IA Series installation manual

Daikin
Daikin RX15RMVJU installation instructions

Haier
Haier HSU-10VNJ17 Operation manual

Dettson
Dettson COND-UHD-09 Installation instructions and homeowner's manual

GE
GE ASQ12AL Dimensions and installation information

Panasonic
Panasonic CS-E15DKEW Service manual