BPC HP-206P User manual

HP-200P SERIES
UPS’s
HP-206P
HP-210P
HP-215P
6 – 10 – 15 kVA
3 Phase Input – 1 Phase Output
USER MANUAL


CONTENTS
I. GENERAL DESRCIPTION.......................................................................................1
1.1 Introduction........................................................................................................1
1.1.1 Cautions for service personal.................................................................1
1.1.2 Battery cautions......................................................................................1
1.2 HP-200P UPS block diagram.............................................................................1
1.3 Technical Specifications ....................................................................................5
II. FRONT PANEL........................................................................................................6
2.1 Introduction .......................................................................................................6
2.2 Front Panel Menu Descriptions..........................................................................6
2.2.1 Main Menu .............................................................................................7
2.2.2 COMMAND Menu items.........................................................................7
2.2.3 MEASURES Menu items........................................................................8
2.2.4 ALARMS Menu items.............................................................................8
2.2.5 USER OPTIONS Menu items.................................................................9
2.2.6 TIME Menu items ..................................................................................10
2.2.7 CALIBRATION Menu items...................................................................10
2.2.8 ADJUST MODE submenu......................................................................10
2.2.9 INFORMATION Menu items...................................................................10
2.3 STATUS Messages...........................................................................................11
2.4 SHUTDOWN MESSAGES ...............................................................................11
2.5 Fault messages and quick troubleshooting........................................................12
III. PARALLEL OPERATION........................................................................................14
3.1 Introduction........................................................................................................14
3.1.1 Redundancy...........................................................................................14
3.1.2 Power Increase......................................................................................14
3.2 Parallel Operation Mode...................................................................................14
3.2.1 Redundant Parallel Mode.......................................................................15
3.3 Parallel Operation Mode Fault Codes................................................................15
3.4 Parallel System Accessories..............................................................................15
3.5 Effects of the parallel configuration on HP-200P series UPS.............................17
3.6 Taking off the parallel devices from a UPS........................................................17
IV. UPS INSTALLATION...............................................................................................18
4.1 Introduction........................................................................................................18
4.2 Unpacking .........................................................................................................18
4.3 Equipment Positioning.......................................................................................18
4.4 Connecting The UPS Power Cables..................................................................19
4.4.1 Safety Earth ...........................................................................................19
4.4.2 Cable connection procedure...................................................................20
4.4.3 Description of connection terminals of the UPS .....................................20
4.4.4 Battery Installation..................................................................................21
V. OPERATING INSTRUCTIONS.................................................................................22
5.1 First operating and Power ON ...........................................................................22
5.2 Power down.......................................................................................................22
5.3 Switching into maintenance bypass mode.........................................................22
5.4 Switching from maintenance bypass into normal operation................................22

VI. MAINTENANCE ......................................................................................................23
6.1 Scheduled Maintenance ....................................................................................23
6.2 Daily checks ......................................................................................................23
6.3 Weekly checks...................................................................................................23
6.4 Annual maintenance..........................................................................................24
6.5 UPS Storage and transportation........................................................................24
VII. FAULTS AND TROUBLESHOOTING.....................................................................25
7.1 General procedure for fault checking and troubleshooting.................................25
VIII. UPS’s REMOTE CONTROL CONNECTION .........................................................26
8.1 Using Serial Port................................................................................................26
8.2 Serial port connection cable...............................................................................26
8.3 Remote control/connection with a modem ........................................................26
8.3.1 Hardware Configuration..........................................................................27
8.3.2 Functioning Principle..............................................................................27
8.3.3 Modem programming procedure ...........................................................27
8.3.3.1 Smart Modem (SM) configuration (programming)....................28
8.3.4 Modem connection cables......................................................................28
8.4 UPS Remote monitoring panel connection ........................................................28

IMPORTANT SYMBOLS
Symbols used in a UPS are classified as SAFETY and OPERATING categories as shown
below.
Kg
Pb H
2
SO
4
HIGH VOLTAGE.
WEIGHT.
ISOLATED LEAD
–
ACID BATTERY.
ATTENTION, FOLLOW INSTRUCTIONS BELOW.
READ INSTRUCTION MANUAL.
SAFETY SYMBOLS
OPERATING SYMBOLS


1
ı. GENERAL DESRCIPTION
1.1 Introduction
Messages displayed on the front panel are subject to change depending on the developments in UPSs. But
the Axx codes in front of the alarm messages are always the same. To be informed by the latest
developments in software. Please contact the service center.
1.1.1 Cautions for service personal
High voltage exists inside the UPS. Touching such points is very dangerous and hazardous. Accidental
electric arcs can be very hazardous while working inside the UPS (Only trained personal).
Some electrical components are heavy. If replacement is required please use suitable and helpful apparatus.
Otherwise injuries may occur.
Energy storage devices such as batteries and capacitors are used in the UPS. Before maintenance turn off
the device and wait at least 3 minutes to completely discharge the capacitors. Make sure batteries are
disconnected.
Unfortunate accidents may occur, therefore we advise a second helping service element nearby.
Take of any metal objects such as rings ot bracelets that can make a short circuit.
1.1.2 Battery cautions
Ni Cd batteries are used in the UPS’s. If not so, then the type of the batteries is lead acid. Therefore, use
protecting wear or hand gloves while maintaining batteries. Keep a fire extinguisher nearby the batteries
against any probable fire due to arcs.
Batteries are polluting elements. Therefore, be careful when disposing.
1.2 HP-200P UPS block diagram
Inverter
Rectifier /
Charger
Static Transfer Switch
Maintenance Bypass
3 Phase
AC
Input
1 Phase
AC
Output
Battery
MB
S
F2
F3-F4-F5
F1-F0
Figure 1 Electrical Block Diagram
On-Off
Micro switch
F6

2
Switches
F1-F0 : Battery circuit breaker switch & fuses
F2 : ON – OFF and By Pass switch & fuse
F3-F4-F5 : Rectifier input switch – Input switch & fuse
MBS : Maintenance By Pass switch.
F6 : Output switch & fuses
•F1-F0 – Battery circuit breaker switch & fuse
Located at the input side of the device. It protects the other side of the system against any faults may occur
on the battery or the device.
•F2 – ON – OFF switch & fuse
F2 is basically a fuse on the bypass input line and it has an integrated micro switch which is used for turning
ON and OFF the UPS. Therefore, F2 will be mentioned as ON – OFF switch.
•F3-F4-F5 – Rectifier input fuse (switch)
These switches connect the line input to the input of the rectifier/charger. All power supplies in the equipment
connected to this switch.
•MBS – Mechanical maintenance bypass switch
There is no fuse on the line of mechanical by pass.
When the UPS is faulty or during the maintenance period this switch is used to connect the load, directly to
the bypass line.
•F6 – Output switch & fuses
This switch connects the output of the UPS to the load. This switch must be turne
d OFF after the
maintenance bypass switch is turned on properly according to its procedure. Maintenance bypass line is
connected to the output of this switch.
General description of UPS parts:
RECTIFIER/CHARGER: The first conversion stage (from AC to DC) uses a 3 phase, 6 pulse, fully controlled
rectifier to convert the incoming mains supply into a regulated DC BUS BAR. The DC BUS BAR produced by
the rectifier provides both battery charging power and power to the inverter section.
BATTERY GROUP: It keeps as an reserve DC power supply, for the inverter in case of mains failure.
Note : To increase the lifetime of the batteries keep them in room temperature (20
o
C-25
o
C).
INVERTER: It is made by utilizing the latest technology of power transistor (IGBT) and pulse width
modulation (PWM). Inverter converts dc bus voltage into (second conversion) an alternative voltage like line
voltage. And provides this voltage and frequency being fixed.
STATIC TRANSFER SWITCH (STATIC BY-PASS): The circuit block annotated contains an electronically
controlled switching circuit, which enables the critical load to be connected either to inverter output or to a by-
pass power source via the” static by-pass line”.
MECHANIC TRANSFER SWITCH (MAINTENANCE BY-PASS): Manually controlled, ”maintenance by-pass”
supply is also incorporated into the UPS design. Its purpose is to enable the critical load to be powered from
the mains (by-pass) supply while the UPS is shut down for maintenance or troubleshooting.

3
F0
-
F1
Battery Fuses
F2
ON - OFF Switch
F
3
-
F4
-
F5
Input Switch
MBS
Maintenance
ByPass Switch
( RS232 / SNMP )
Communication
Select Switch
(optional)
RS232 Communication
Socket (DB9 Female)
Emergency
Stop Switch I/P
F6
Output Switch
Figure
2
-
1
6 Kva Fuse and Switch Locations
Parallel Port

4
F0
-
F1
Battery Fuses
F2
ON - OFF Switch
F
3
-
F4
-
F5
Input Switch
MBS
Maintenance
ByPass Switch
( RS232 / SNMP )
Communication
Select Switch
(optional)
RS232 Communication
Socket (DB9 Female)
Emergency
Stop Switch I/P
F6
-
F7
Output
Switch & Fuses
Figure
2
-
2
10-15 Kva Fuse and Switch Locations
Parallel Port

5
1.3 Technical Specifications
MODEL HP-206P HP-210P HP-215P
Output kVA 6 10 15
Output kW 4.2 7 10.5
Output Power Factor 0,7
Parallel Operation Equipment Available
Battery charging temperature compensation Available
Serial Communication RS232 (optional SNMP, RS485 or MODBUS)
INPUT
Input voltage 230/400Vac 3 Phase, N
Voltage tolerance ±15%
By-Pass voltage 230Vac, N
Input frequency 50 Hz. ±5%
RFI Level EN 50091
OUTPUT
Nominal output voltage 230Vac, N
Voltage regulation tolerance ±1%
Nominal output frequency 50 Hz.
Output frequency tolerance (Line syncron) ±1%
Output frequency tolerance (Free running) ±0,2%
Efficiency 100% Load 88-90 %
Load Crest factor 3:1
Overload 100%-125% load 10 min.
125%-150% load 1 min.
> 150% by-pass
Total Harmonic Distortion (THD) <%3
BATTERY
Type of Batteries Ni Cd
Number of Cells 242
Float charge voltage 340 Vdc
End of discharge voltage 273 Vdc
Battery Charging Current 20A 25A 46A
ENVIRONMENT
Maximum Temperature 0°C - 40°C
Audible noise <60dBA
Weight (approx) 165 Kgs 190 Kgs 200 Kgs
Dimensions (HxWxD) (mm) 1265x545x740
Protection Class IP 32
OTHER
Serial communication RS232 (standard) RS485 (optional)
Alarm contacts Standard
UPS SNMP Adaptor Optional
Remote Monitoring Panel Optional

6
II. FRONT PANEL
WARNING! The messages in this section are applicable for equipments having software version Y11PAR2.
If the version changes, the messages and functions will change as well.
2.1 Introduction
The front panel of UPS, consisting of a 2 lines alphanumeric display, 2 status lamps, plus 4 function keys,
allows the complete monitoring of the UPS status. The mimic flow diagram helps to comprehend the operating
status of the UPS. By using the function keys operator can move on menus and change some parameters.
Figure 3
L1 :
If lamp is lit static bypass is active and load is connected to mains voltage
L2 :
If lamp is lit inverter supplies the load
There are 4 function keys on front panel these are ENTER, UP, DOWN and (↔
↔↔
↔).
UP and DOWN keys help moving on menus, (↔
↔↔
↔) key selects options, ENTER key means the selected option
or menu is valid.
NOTE : During parameter settings, “+” sign will change into “—“ sign if “↔
↔↔
↔” button is pressed for 3 seconds
and the parameter values will start decreasing.
2.2 Front Panel Menu Descriptions
By using menu buttons on the front panel you can move on main menu functions. You can enter the submenu
of the item seen on the LCD panel (MEASURES, ALARMS, INFORMATION) and navigate within it by using
again ↓
↓↓
↓, ↑
↑↑
↑, ↵
↵↵
↵(Enter) buttons.
MEASURES submenu
LD% (output load percentage)
OPV (output voltage)
FREQU (output frequency)
IPV (input voltages)
BYP (bypass source voltage)
BATT (battery voltage and current)
...... etc
L1
L2 ENTER

7
SAMPLE menu selection:
If you want to go to MEASURES menu use UP and DOWN keys and find MEASURES MENU, press ENTER
key, now you can move on MEASURES menu subitems by UP and DOWN keys.
At the end of sub menus ENTER (EXIT) message is available and while reading this message, if you press
ENTER key you can go back to MAIN menu.
In ALARMS MENU you can see LOG HISTORY, log events are recorded with event time and date.
PASSWORD Menu is used for service purposes. This menu requires a three digit password and should be
used only by qualified service personnel..
2.2.1 Main Menu
Main menu items are described below, navigation through them can be performed using up and down
buttons.
Main menu items Function
STATUS The status message which shows the UPS status
COMMAND MENU →Enter “go to Command submenu”
MEASURES MENU →Enter “go to Measures submenu”
ALARMS MENU →Enter “go to Alarms submenu”
USER OPTIONS →Enter “go to User Option submenu”
TIME MENU →Enter “go to Time submenu”
CALIBRATION MENU →Enter “go to Calibration submenu”
ADJUST MENU →Enter “go to Adjust submenu”
INFORMATION MENU →Enter “go to Information submenu”
Go to STATUS MENU
2.2.2 COMMAND Menu items
This menu is used to give commands to the UPS or perform tests on it.
Submenu item Function
1
SOUND : ON/OFF
(is available)
Used for turning on/off alert sound.
If you press ENTER key the option will change, one press ON, one press OFF.
If the OFF option is selected sound alert is turned off but if a new alarm, UPS
changes the option to ON state.
2
ENTER <BYPASS> If you press ENTER for 3 seconds, the load is transferred to BYPASS
automatically and the submenu item changes to ENTER <INVERTER> this time.
If you press ENTER for 3 seconds, the load is transferred back to Inverter.
3
ENTER B.TEST>405
If you press enter for 3 seconds battery test starts and lasts for 15 seconds.
If battery test fails A6 BATT FAULT message is shown on panel and this
message stays until you press ENTER key for 3 seconds.
The value on at the right shows the battery voltage during battey test.
Starting time of battery test recorded to log event menu if the test is successful
you can see only BATTERY TEST message on log records..
4
ENTER <BOOST>
If you press ENTER key for 3 seconds boost charge starts. The given time for
boost charge is 10 hours. At the end of this time UPS stops the boost charge.
If the boost charge is active this submenu item changes to STOP BOOST>
005H message the 005H shows that boost charge is going on for 5 hours.
If the number is 10 boost charge stops. If you press ENTER key boost charge
stops immediately.
Boost charge starting and boost charge end times are recorded to log event
menu.
If boost is active UPS beeps each 15 seconds

8
Submenu item Function
5
SIMULATION OFF
The purpose of this submenu to check dry contact connections. Normally to
check line failure contact you must turn off mains power. This is not
necessary with this utility. 3 options are available.
SIMULATION OFF simulation mode is off
SIM:LINE FAILURE if you press ENTER key for 3 seconds the line failure
lamp on interface board is turned on.
SIM:LIN.F+BT.LOW if you press enter key for 3 seconds the line failure and
battery low lamps on interface are turned on.
SIM:BYPASS if you press ENTER key for 3 seconds the bypass (aux) lamp
on interface board is turned on.
So you can check dry contact connections
6
ENTER FAULT RESET Faults reset selection.
7
ENTER EXIT →Enter (↵
↵↵
↵) exit from submenu
Goto first submenu item
2.2.3 MEASURES Menu items
All the measurements of the UPS can be monitored via this menu, navigation through the items is performed
using up and down buttons.
Submenu item Function
1 LD%: 060 Output load percentage
2 OP CURR : 011A Output current
3 OPV: 236 Output voltage
4 IPV: 400 400 400 3 Phase input voltages
5 BATT: 340 V Battery voltage
6 BYP: 230 By-pass voltage
7 FREQU: 50.0 Hz 50.0 Hz Input frequency – Output frequency
8 TEMP: 030 c UPS Internal temperature
9 ENTER EXIT →Enter (↵
↵↵
↵) exit from submenu
Goto first submenu item
2.2.4 ALARMS Menu items
The last 64 events can be monitored in this menu.
Submenu item Function
1 UPS STATUS Alarm status at that instant.
2 000>311201 23:15
Monitoring past alarms:
First 3 digit number indicates the event number, 000 event is the last one.
Date is in ddmmyy and time is in hh:mm format.
On the second line, the alarm events on the first line are listed. Using ↔
button 128 events can be viewed.
3 PARR.ERR.NR : 017 Parallel controller board error (If parallel hardware exists)
If this value is 0 then the parallel is OK
4 ENTER EXIT →Enter (↵
↵↵
↵) exit from submenu
Goto first submenu item

9
2.2.5 USER OPTIONS Menu items
From this menu the user selects some important parameters and apply them.
Submenu item Function
1 MODE: ONLINE
4 Operating modes can be selected using up and down buttons.
ONLINE: normal operating mode.
PARALLEL: Symmetric parallel operation mode of 2 UPS’s.
HOT STANDBY: 1 UPS is master and 1 UPS is redundant operating mode.
REDUNDANT: 2 UPS’s redundant operating mode.
→Press ENTER for 3 seconds to save the selected mode.
2 UPS No : 001
By using PLUS and MINUS keys you can change number 0 to 3.
In parallel operation select different numbers for each UPS. If you select the
same number DUBL UPS NUMBER message tells the fault.
→press ENTER for 3 seconds and then the selection is valid
3 BYP.PROTECT ON
By using ↔key you can change on and off options.
ON: if the bypass source is out of tolerance, UPS turns off load power in
case of a fault or overload..
OFF : UPS turn off load power only during bypass moves. If bypass period is
completed UPS continues to supply the load.
→press ENTER for 3 seconds and then the selection is valid
4 RESTART:ON/OFF
By using ↔key you can change on and off options.
ON : during mains failure at the and of battery discharge UPS shutdowns
,after mains restored UPS starts again.
(battery trip out is on every time)
OFF: after mains restoration UPS doesn’t start again.
(battery trip out is off)
→press ENTER for 3 seconds and then the selection is valid
5 REMOTE : ENABLE
By using ↔key you can change enable and disable options.
Enable : remote battery test, shutdown and bypass functions are enabled
disable : these functions are disabled
→press ENTER for 3 seconds and then the selection is valid
6 CENTER-EDGE
LANGUAGE Turkish – English is selected.
7 BOOST TIME Quick charge period of 1-15 hours is configured. Boost is disabled if 0 is
entered while boost charge.
8 BOOST Manual – automatic modes are selected using ↔key. Normal charge mode
operates in manual selection. In automatic mode, if the line is off, at each
time input line voltage is restored the boost charge starts automatically.
9 DIRECT START: ON
ON: UPS at the beginning starts automatically.
OFF: The inverter is in standby.
The inverter starts and the output forms when ENTER is pressed. Until this
moment the load is supplied from the by-pass.
10
XFER MOD: CURRENT CURRENT: Switches into bypass without delay when the current is zero
DELAY: If the UPS is not synchron , switching into bypass takes place with
15 ms. Delay.
11
RELAY COMMON
12
RL4 COMMON
Alarms: COMMON, RL4, BATT. LOW, OUTPUT HĐGH, OVERLOAD, LĐNE
FAILURE, OVER TEMP., OVER CURRENT, OUTPUT LOW, BATTERY
HĐGH, BATT. FAULT, BY-PASS BAD, BOOST CHARGE, MANUEL BYP,
ROT. PHASE, OUTP. OFF, UPS FAILURE.
RL4 relay can be defined for any desired alarm.
13
RL5 COMMON
Alarms: COMMON, RL4, BATT. LOW, OUTPUT HĐGH, OVERLOAD, LĐNE
FAILURE, OVER TEMP., OVER CURRENT, OUTPUT LOW, BATTERY
HĐGH, BATT. FAULT, BY-PASS BAD, BOOST CHARGE, MANUEL BYP,
ROT. PHASE, OUTP. OFF, UPS FAILURE.
RL5 relay can be defined for any desired alarm.
14
ENTER EXIT →Enter (↵
↵↵
↵) exit from submenu
Goto first submenu item

10
2.2.6 TIME Menu items
You can see date and time of RTC (real time clock) on UPS. And you can adjust date and time.
Submenu item Function
1 TIME : 23 :15 time
2 DATE : 11-10-2006 date
3 SET HOURS: 11 (+) and (-) adjust hours (0-23)
4 SET MINS : 38 (+) and (-) adjust minutes (0-59)
5 SET DAY : 21 (+) and (-) adjust day (1-31)
6 SET MONTH : 06 (+) and (-) adjust month(1-12)
7 SET YEAR : 2006 (+) and (-) adjust year (2000-2099)
8 ENTER <UPDATE> →Enter update new date and time
9 ENTER EXIT →Enter (↵
↵↵
↵) exit from submenu
Goto first submenu item
2.2.7 CALIBRATION Menu items
This menu is used to adjust time and date of the UPS.
Submenu item Function
1 (Password required ) System adjustments.
ENTER EXIT →Enter (↵
↵↵
↵) exit from submenu
Goto first submenu item
2.2.8 ADJUST MODE submenu
This menu is used to adjust time and date of the UPS.
Submenu item Function
1 (Password required ) System adjustments.
ENTER EXIT →Enter (↵
↵↵
↵) exit from submenu
Goto first submenu item
2.2.9 INFORMATION Menu items
This menu gives information about the UPS
Submenu item Function
1 COMM :OK SYNC :OK If the UPS is operating syncron to mains SYNC:OK ,if not syncron
SYNC:--
If communication is active COMM:OK ,if not active COMM:--
2 POWER: 10000 VA The maximum power rating of the UPS
3 VERSION : Y11PAR2 Shows the UPS software version
4 SPARE MASTE 006
5 ENTER EXIT →Enter (↵
↵↵
↵) exit from submenu
Goto first submenu item

11
2.3 STATUS Messages
This message group simply shows the UPS STATUS at the upper line of LCD PANEL.
RECTIFIER START ! : UPS started the rectifier
ENTER START : Press ENTER to start the UPS.
INVERTER START ! : UPS started the inverter.
MAINT SWITCH ON ! : Maintenance bypass switch is on
STATUS NORMAL ! : UPS is operating.
EMERGENCY STOP ! : External emergency stop signal is applied to UPS.
WAITING SYNC ! : Inverter started waiting for mains synchronization.
STATUS FAULT ! : Fault status
RECTIFIER START :
At start up the UPS controller board checks for input voltage, frequency, battery voltage for starting ,if these
parameters normal, UPS starts.
INVERTER START :
If the inverter stops from any reason, controller board tries to start inverter again, during inverter start this
message appears on first line of LCD PANEL
MAINT SWITCH ON:
Maintenance bypass switch is connected from input to the output of UPS directly .Đf the maintenance bypass
switch is on (1 position) controller stops inverter for accidental short circuits between mains voltage and
inverter output. If the user turn off maintenance switch inverter starts again.
EMERGENCY STOP :
If an external EPO switch is installed to system (connected to interface board), to stop all UPS parts (rectifier,
static bypass ,inverter ,etc….) is possible . After pressing EPO switch all parts of the UPS stops, for restart
turn off S1 (inverter input) switch and turn on again.
FAULT STATUS :
In some cases controller checks events but can not find solutions, in this case controller decide to stop
system, for restart user must turn off S1 (inverter input) switch and turn on again.
2.4 SHUTDOWN MESSAGES :
HP-200P series UPS’s can operate interactive with operating system, you can send commands to UPS from
operating system by using some softwares .UPS takes this commands and produces some messages these
are:
WAITING SHUTDOWN : Shutdown command is performed from operating system and UPS is waiting
for a certain delay for shutdown.
UPS SHUTDOWN : UPS is in shutdown status
WAITING RESTART : UPS is shutdown but it is waiting for a certain delay for restart
PAR.SHUTDOWN : In parallel system the other UPS send shutdown command and UPS is in
shutdown status.
CANCEL SHUTDOWN : Shutdown command is cancelled.
Only operating system or a PC computer can send this commands.
If the shutdown command is performed during line failure UPS shutdowns and is the mains is okay UPS starts
again automatically.

12
2.5 Fault messages and quick troubleshooting
All alarms contained in Y11PAR2 version are listed in the following table.
ALARM POSSIBLE CAUSE
A1 BYPASS FAILURE Bypass system failure. Bypass elements may be broken.
A2 INVERTER FAILURE Inverter digital start system is failed. Call the service.
A3 3 OVERTEMP
Overtemperature in UPS repeated 3 times in 30 min.
1) Check for UPS air inlets and outlets for any blocking by dust etc.
2) Fan failure
3) Bad UPS location
4) Check for Overload
A4 OUT FAILURE UPS output voltage is out of tolerance at 3 times in 30 min. Call the service.
A5 BATT AUT END Batteries are completely discharge wait for restoration of electric power
input.This message occurs only at line failure
A6 CHARGER FAULT Rectifier could not produce DC bus voltage.
A7 BATTERY LOW Battery voltage is low.
1) UPS operation for a long time when line out
2) Charger system failure
A8 OUTPUT HIGH Inverter output voltage is over than max. tolerated value.
Inverter is stopped
1) Inverter failure
A9 OVERLOAD UPS loaded over than max. %100 load level.
A10 LINE FAILURE
Line failure.
1) Maybe line out
2) Check 3 input phases.
3) Check UPS input fuses.
A11 HIGH TEMPER
Over temperature. (inverter or rectifier section)
1) Overload for inverter
2) Over temperature
3) Fan failure or dirty air inlets
4) Bad UPS settling. There is not enough ventilation area.
A12 OVERCURRENT
Inverter output system failure
1) Internal overcurrent
2) Short circuit.
3) UPS failure. Call the service.
A13 OUTPUT LOW Inverter output voltage is below the min tolerated value.
Inverter is stopped.
A14 BATTERY HIGH
Battery voltage is over than max. tolerated value.
If the mains is off the tolerance when switching into bypass. The UPS turns
off the output voltage and waits until the inverter starts again to prevent the
load.
A16 BYP INPUT BAD
During transfer to bypass, Voltage or frequency value of bypass source is
incorrect and the UPS turns off the load power.
During normal (inverter) operation some times you can see this message.
During bypass if the bypass protection option is on, and if the bypass
source is out of tolerance UPS turns off the static bypass for load
protection.
A19 REPLACE BATT
Battery test aborted. And batteries are not OKAY
UPS gives beep sound within 15 sec
You can clear this message by pressing 3 seconds to ENTER key
1) Rectifier fault
2) Damaged battery cells
3) POOR battery connections
A20 BOOST CHARGE Boost charge is active for 10 hours. At the end of this time UPS stops the
boost charge.
UPS gives beep sound every 15 sec

13
ALARM POSSIBLE CAUSE
A21 ROTATE PHASE UPS input phases sequence is not correct
1) Turn off the UPS and rotate phase sequence
2) Turn on UPS again
A22 OUTPUT OFF Output OFF alarm
- Output switch may be off.
- A fault may be in the output. Check the output components.
A23 MODE FAILURE
In parallel operation the slave device tries to operate as the same mode as
the master device, If the modes are different this message will appear.
Change the mode of the slave UPS from USER OPTION MENU. Press
ENTER button for 3 seconds after mode selection, then restart the UPS.
A24 P.FAILURE 10 RS485 failure
A25 PAR. PSP FAIL Power supply error in parallel controller board.
A26 4 CABLE FAIL Master-Slave digital cable connection error.
A27 P.FAILURE 13 Parallel controller board failure, online UPS found in parallel system.
A28 PLUG IN DIG. Digital connection cable plug in failure
A31 DUBL UPS NUMBER Parallel UPS numbers are same change one of them
A40 CANT FIND PR
Parallel mode is selected but main controller could not find parallel control
board.
Select ONLINE mode from SETTING MENU.
Turn off the ups and turn on again.
A41 P.BAL.FAILURE In parallel operation current sharing is not okay
A42 BATTERY TEST Performing battery test
A43 P.SYNC.FAIL In parallel system SLAVE UPS is not synchronized to MASTER UPS
1) Wait for 10 seconds the UPS will be restart
A48 STATIC BYPS. Load is transferred statically to bypass
A50 EMERGE.STOP Emergency stop button is pressed.
A51 MAINT SW.ON Maintenance bypass switch is open. (optional)
A53 CHECK +6V Check +6V on them main controller board.
A54 CHECK DC1 Battery voltage is below the lower limit.
A55 PDLY FAIL Parallel delay fault
A59 REF FAILURE 2.5 V ADC reference voltage on MPB211 main controller board exceeds
predefined tolerances.

14
III. PARALLEL OPERATION
3.1 Introduction
Two of HP-200P UPS can be used in parallel mode, the purpose of parallel use:
•Redundancy
•Power increment purpose.
3.1.1 Redundancy
Even if UPS designs are perfect sometimes some failures are possible. Also the lifetime of batteries and
some parts are limited. In such a case, the second UPS installed on the system will be working on.
3.1.2 Power Increase
Some load systems always develop and the power need increases, the cheapest solution is to install one
more UPS to the system.
3.2 Parallel Operation Mode
NOTE: Parallel control board and some accessories are not installed in a standard HP-200P series UPS, but
parallel operation option is available for these models.
User can select parallel operation mode as an option according to purpose. If parallel control board is installed
in your UPS, you can select operation mode from SETTINGS MENU. In this chapter you can find parallel
operation mode information.
The general diagram of parallel connection is shown below:
Figure 3-1 Parallel connected UPS’s
MB1
SB1
UPS1
CB1
AC/DC -1
BATT.1
INVERTER 1
SB2 CB2
MB2
SB3
UPS2
CB3
AC/DC -2
BATT.2
INVERTER 2
SB4 CB4
OUTPUT
LINE
S1
S2
S3
S4
S1
S2
S3
S4
This manual suits for next models
2
Table of contents
Other BPC UPS manuals
Popular UPS manuals by other brands

Delta
Delta UPS V3 installation guide

Tripp Lite
Tripp Lite SU140KMBPK Installation and operation manual

Tripp Lite
Tripp Lite OMNIVSINT800 owner's manual

PowerWalker
PowerWalker VI SCL Series quick guide

Tripp Lite
Tripp Lite SmartOnline SU2200XL manual

Tripp Lite
Tripp Lite SMART1000LCDU owner's manual

Delta
Delta Amplon RT Series 5-10kVA user manual

Tripp Lite
Tripp Lite SmartOnline SU2200RTXL2UA Specifications

PowerWalker
PowerWalker VFI 3000 LCD Technical details

Tripp Lite
Tripp Lite SmartPro SMART3000RMXL2U owner's manual

Smart power
Smart power DSS1500RT-TBF user guide

PowerWalker
PowerWalker VFI 1000T/E LCD user manual