Broady's Fp 700 User manual

14 December 2010
Due to continued product improvement, Broady’s reserves the right to change product specifications without prior notification.
All Dimension are in mm………….Copyright ©
1
GAS OPEN FIRE’S
Installation Instructions into Wood or Block Alcoves
FPSG & FPEG 700-780-900-1100
Fire, flue system and instructions to comply with NZS 5261/5262 :2003
Keep these Instructions for further reference……Ensure that you have the correct and current installation details for the Broady’s Fire
Installation
The Broady’s unit is to be Installed by a Certified Broady’s Installer or an Approved NZHHA Installation Technician .
See www.homeheat.co.nz/members for a Certified NZHHA SFAIT Installer in your area .
A Certified Craftsman Gas Fitter and Certified Electrician are required to run Power and Gas Supplies as required to the unit and any Commissioning as
part of the Installation process . The heater must be Installed according to these Instructions and in Compliance with all relevant building , gas fitting,
electrical and other statutory regulations.
Installation to Comply with NZS 5261 / 5262:2003
IMPORTANT
Read all the instructions carefully before commencing the Installation. Failure to follow these instructions may result in a fire hazard and void the warranty
Warmington Flue System
Timber Framing
Hearth
Warm Air Outlet
Vent
Cool Air “Caitec
Vents” Inlet Vent
Gas Firebox
Warmington Gas Cowl
S/S Flashing
( Top Venting can also be
through S/S Flashing .
See Flashing Detail in Spec )

14 December 2010
Due to continued product improvement, Broady’s reserves the right to change product specifications without prior notification.
All Dimension are in mm………….Copyright ©
2
POINTS TO CONSIDER PRIOR TO INSTALLATION
INSTALLATION ORDER OF OPERATIONS
Location of the Fire. Open Fires are better located at one end of a room or area, as they project the heat away from their opening .
Venting to the Cavity.
This air is to allow the Cavity to Vent the Warm Air. This Warm Air helps keep the Fire and Flue System form getting to Cold . If the Flue and Fire get to Cold the System
may soot often and require cleaning. Each Fire has different ways of venting the cavity .
The Topography of the Land .
The slope and position of the Land in relation to the Home has a bearing on how the wind will interact with the Fire and Flue System. Care needs to be taken to ensure
that the Flue Termination is in the correct position to maximise performance .
The Prevailing Wind.
Care needs to be taken to ensure that the Flue Termination is in the correct position as wind and gusts that hits the Flue and Cowl System may overcome the Cowl and
draft back down the Flue into the Home. This can be a combination of down draft and high pressure.
Hearth and Plinth:
The height of the Hearth off the Floor. The Finishing that is to be used on the hearth is to be allowed for at the design stage.
Positioning of the Flue System:
There is a maximum distance that an Offset Flue can be Installed. Reference to AS/NZS : 2918 , NZS 5261:2003
Flue and Fire Clearance:
To be maintained to the Manufactures Instructions.
Pressure Differential, Venting & External Air into the Building :
All fires need air to burn and draw correctly, Kitchen Fans, Air Conditioning units, High Wind Zones, Naturally forming Draft spaces, can all have an effect on the
pressure difference from inside the building to the outside. A lower pressure in the building may induce a draft down the flue system and back into the building
causing the fire to smoke or spill into the building. Care needs to be taken at the design and installation stage to adequately vent the building, or some mechani-
cal system to ensure that there is always a neutral or positive pressure at the fireplace and a negative pressure at the flue outlet. This will ensure that the draft in
the flue system is always to the outside.
“CAITEC AIR” the limits and requirements. See details in these Spec’s or contact your local Agent.
Wind Noise:
You may encounter wind noise in some installations. It is recommended to use an enclosed chase with a chimney pot to help reduce noise.
There will always be some noise from the flue systems of all fireplaces.
Prior to Construction and Installation Important Notes:
1. Consult a Certified Craftsman Gas Fitter for correct Gas Installation.
2. Install to NZS 5261: 2003 (or current standard).
3. Install to manufacture’s specifications.
4. All New Installations require a permit.
5. Allow for gas supply to heat cell at R.H. rear, and power supply to L.H. rear if required (check product).
6. For special requirements concerning materials (Timber Mantle and Surrounds) within close proximity of Broady`s products, please contact
y
our local Broad
y
`s
Technical Consultant .
7.
Stage 1: Frame Construction Procedure by Builder.
1. Mark out Flue Centre.
2. Mark out Heat Cell Clearance requirements.
3. Build Timber Framing to Heat Cell Clearances and Chimney Chase Clearance requirements.
4. Ensure that the front face of Heat Cell Clearance alcove is left open and unframed to enable Installation of the Firebox. The Chimney Chase is left unlined for Installa-
tion of the Flue.
5. Construct Plinth only, to required height. *
Stage 2: Install Procedure by Certified “Broadys Installer”only.
1. Fit Fire to Plinth.(Ensure Gas Supply Line is fed through R.H. Side of Firebox.)
2. Fit Flue System.
3. Fit Cowl and Flashing System.
4. Fit Vents to Heat Cell Alcove and Chimney Chase, to cool the Heat Cell and ensure efficiency of CAITEC Technology.
5.
Stage 3: Finishing Procedure by Builder.
1. Construct Hearth to required thickness. *
2. Finish Framing of Heat Cell Alcove.
3. Close in Heat Cell Alcove and Chimney Chase.
4. Finish Heat Cell Alcove and Hearth to customer’s requirements (e.g. paint / tiles).
5. * Note: Certified Installer can Install Hearth and Plinth.
Maintenance.
Visually Inspect Fireplace and Flue System.
Ensure that Firebox is operated according to the Manufacture’s Instructions.

14 December 2010
Due to continued product improvement, Broady’s reserves the right to change product specifications without prior notification.
All Dimension are in mm………….Copyright ©
3
Firebox Fp
700
Fp
780
Fp
900
Fp
1100
Firebox Width A710 790 910 1110
Firebox Height B600 600 600 600
Firebox Depth C440 440 440 440
Flange Width D800 880 1000 1200
Flange Height E650 650 650 650
Insulation Kit Width F795 875 995 1195
Insulation Kit Height G630 630 630 630
Insulation Kit Depth H485 485 485 485
Centre of Flue I315 315 285 285
Flue J200 200 250 250
Flue Liner K250 250 300 300
Fascia Width L860 940 1060 1260
Fascia Height M680 680 680 680
Fascia Section N80 80 80 80
Heat Output kW
Range* 6-7 7-8 8-9 9
*Estimated unless stated otherwise.
FIREBOX DIMENSION
Minimum Flue Height
Flue Height 3600
Measured From Top of Firebox B + 3600
FIREBOX HEAT CELL CABINET Note:
DO NOT FRAME OUT TO THESE DIMENSIONS CHECK HEAT CELL
ALCOVE ON PAGE 5 & 6.
Seismec Restraint
Secure firebox through anchor positions provided, (Through base of fire).

14 December 2010
Due to continued product improvement, Broady’s reserves the right to change product specifications without prior notification.
All Dimension are in mm………….Copyright ©
4
HEARTH & PLINTH CONSTRUCTION DETAILS
Note: Hearth and Plinth Construction.
Plinth to be Offset above Hearth by the Hearth Finishing’s
( e.g. Tiles / Granite / Solid Plaster / etc )
Raised Hearth’s & Plinth’s with Canter Levered Hearth’s
must be adequately supported to take the weight in Ac-
cordance with the NZ Building Code .
IMPORTANT NOTES :
SEISMIC RESTRIANTS
GAS SPECIFICATIONS Tested to : AS 4558
NOTE : All Test Pressures are tested by an Independent Test Lab * Inlet Pressure not to exceed 4.0KPa
Lab. Test No GL 923 GL 900 GL 834 GL 876
Lab. Test Dates 20/04/2010 26/02/10 26/06/09 24/12/09
ESS Declaration No: 1149420106 1149520106 1149720106 1149820106
*Note: If Solid Plastering the Heat Cell Structure, it is recommended to use a Fibreglass Mesh with a Latex Based Plaster to
minimise the chance of the Solid Plaster cracking. (See your Solid Plasterer for correct materials and applications).
Seismic Restraint
Secure Firebox through
anchor points provided
Offset for
Hearth
finishing
Offset
This is a Raised & Canter Levered
Hearth. See page 15 for further
Raised Hearth Detail
MODLE Fp 700 Fp 780 Fp 900 Fp 1100
LPG
Nominal Pressure kPa 2.75 kPa 2.75 kPa 2.75 kPa 2.75 kPa
Nominal Injector Size mm 2 X 1.1mm 2 X 1.2mm 2 X 1.3mm 2 X 1.4mm
Burner Pressure High kPa 2.5 2.5 2.5 2.5
Burner Pressure Low kPa 0.75 0.75 0.75 0.75
MJ/h 29 38 42 50
Falme Effect Output Only Effect Effect Effect Effect
Supply Pipe Size dia—min 3/8” 3/8” 3/8” 1/2”
Natural Gas
Nominal Pressure kPa 1.5 kPa 1.5 kPa 1.5 kPa 2 kPa
Nominal Injector Size mm 2 X 1.8mm 2 X 2mm 2 X 2.2mm 2 X 2.4mm
Burner Pressure High kPa 1 1 1 1
Burner Pressure Low kPa 0.3 0.3 0.3 0.3
MJ/h 35 41 48 60
Flame Effect Output Only Effect Effect Effect Effect
Supply Pipe Size dia—min 3/8” 1/2” 1/2” 5/8”

14 December 2010
Due to continued product improvement, Broady’s reserves the right to change product specifications without prior notification.
All Dimension are in mm………….Copyright ©
5
TIMBER FRAMING & TRIM OUT DETAILS
Note:
All Framing Dimensions are Internal Only
Firebox Fp
700
Fp
780
Fp
900
Fp
1100
Heat cell Clearance Width O810 895 1010 1210
Heat Cell Clearance Height P660 660 660 660
Heat Cell Clearance Depth Q535 535 535 535
Hearth Width R1100 1180 1300 1500
Hearth Projection S300 300 300 300
Chimney Chase Clearance T 350 350 400 400
Window Height V660 660 660 660
Window Width W810 895 1010 1210
COMMON ALCOVE FRAMED
OUT TO 2.4 MTR HIGH
MINIMUM HEAT CELL ALCOVE CLEARANCES & FRAME OUT
Warm Air Vent
Window
Height ‘V’
must be
measured
from top of
Hearth .
Hearth Height
Standard
2400mm Stud
Q O
Cool Air external
Intake Vent Note:
Centre Line of Flue is `NOT’ in Centre of
Alcove

14 December 2010
Due to continued product improvement, Broady’s reserves the right to change product specifications without prior notification.
All Dimension are in mm………….Copyright ©
6
TIMBER : PLAN, FRONT ELEVATION & CROSS SECTION
BLOCK : PLAN, FRONT ELEVATION & CROSS SECTION
Firebox Fp
700
Fp
780
Fp
900
Fp
1100
Plinth Width OO 810 1210 1210 1210
Plinth Depth QQ 600 600 600 600
Centre of Flue II 315 315 285 285
Hearth Width RR 1100 1180 1300 1500
Hearth Projection SS 300 300 300 300
Firebox Fp
700
Fp
780
Fp
900
Fp
1100
Hearth Width R1100 1180 1300 1500
Hearth Projection S300 300 300 300
Alcove Width O810 895 1010 1210
Alcove Depth Q535 535 535 535
Centre of Flue I315 315 285 285
Chimney Chase Clearance T350 350 400 400
Note:
Centre Line of Flue is `NOT’ in Centre of Alcove
Note:
Centre Line of Flue is `NOT’ in Cen-
tre of Alcove

14 December 2010
Due to continued product improvement, Broady’s reserves the right to change product specifications without prior notification.
All Dimension are in mm………….Copyright ©
7
BLOCK ALCOVE & TRIM OUT DETAILS
Note:
Centre Line of Flue is `NOT’ in Centre of the
Chimney Chase
Firebox Fp
700
Fp
780
Fp
900
Fp
1100
Heat cell Clearance Width OO 810 1210 1210 1210
Alcove Clearance Height PP 2400 2400 2400 2400
Alcove Clearance Depth QQ 600 600 600 600
Window Height VV 630 630 630 630
Window Width WW 800 880 1000 1200
Chimney Chase Clearance TT 350 350 400 400
Cool Air
external
Intake
Vent
Warm Air Vent
Warm Air Vent
Cool Air
external
Intake
Vent
Note:
Ensure that the Fire and Flue System is Installed before the alcove
access is blocked off .
Block modules may vary to the drawing . (See Blocklayer)
MINIMUM HEAT CELL BLOCK ALCOVE CLEARANCES

14 December 2010
Due to continued product improvement, Broady’s reserves the right to change product specifications without prior notification.
All Dimension are in mm………….Copyright ©
8
FLUE DETAILS DIMENSIONS
Minimum Flue Height
Flue Height 3600
Measured From Top of Adaptor B + 3600
Flue details
No: Fp
700
Fp
780
Fp
900
Fp
1100
Cowl 1200 200 250 250
Flue Diameter 3200 200 250 250
Liner Diameter 3250 250 300 300
Spacer 3200/250 200/250 250/300 250/300
Bottom Spacer 1 200/250 200/250 250/300 250/300
NOTE:
Ensure that a Standard Tested Broady’s Flue System is used on the Broady’s Fires.
FLUE SYSTEM INSTALLATION GUIDE
This is a general installation guide only – Contact a “NZHHA Installer” or Gas Fitter for
Installation Advice.
1. Install the first length of flue pipe with the crimped end down, inside the Adaptor collar, ensure that the
flue pipe is sealed into the collar with exhaust sealant. Rivet the flue in 3 places around the Adaptor collar.
Place a bottom spacer around the flue pipe approximitaly150mm above the adaptor collar. Secure in posi-
tion by tightening the screw and nut.
2. Install the second length of flue pipe with the crimped end down and fit by riveting in at least 3 places
around the flue pipe joint. Ensure that the flue is sealed into position with sealant.
3. Install the first section of flue pipe liner with the Crimped end up, over the flue pipe and over the spacer
that is fixed to the flue pipe. This spacer will keep the liner concentric about the flue pipe.
4. Position flue spacer at the flue pipe joint for every length of “Flue pipe” and “Liner”.
Repeat the Steps from 1 – 4 to the installed required height of the flue system. The flue system is to comply with
ASNZS 2918:2001 4.9.1 & NZS 5261/5262:2003
IF FLASHING CONE NEEDED
1. NOTE: The last length of flue pipe needs to extend past the liner so that when the “top spider” and the “Flashing cone”
are fitted, that the “flashing cone” and the “flue pipe” are flush, or that the “flue pipe” is 5mm lower that the “Flashing
cone”.
2. Fit the “Top Spider” into position, ensure that the legs of the spider are fitted inside the liner and that the spider is
positioned hard down onto the liner and tighten with the screw and nut.
3. Place the “Flashing cone” over the “flue pipe” and press hard down onto the “Top Spider”. (Note that the “Flue pipe”
and the “Flashing Cone” are either flush or the “Flue pipe” is 5mm Lower than the “Flashing cone”.) Ensure that the
“Flashing cone” is clear for the venting from the “Liner” and the “flue pipe”.
4. Fit the “Cowl” to the top of the flue pipe. The “Cowl”, “Flashing cone”, and the “Flue pipe” can be secured to each
other with the uses of a stainless steel self tapping screw. This will allow the “Cowl” to be removed for cleaning.
5. Flue system may require Bird Proofing due to the installation and locations, discuss this with your installer for the best
advice.
6. If the Flue system is installed into a “Chimney Chase”, allow for air vent as close to the top of the chase as practical, or
allow venting through the “Chimney Chase Flashing”. A “Venting Flashing cone” and a 25mm gap around the Liner
with a “Venting Flashing Cone-Spider” can be used. Ref : to Figures ……in this specification.
•a “the flue pipe shall extend not less than 4.6m above the top of the floor protector.”
•b “ the minimum height of the flue system within 3 m distance from the highest point of the roof shall be 600mm
above that point.”
•c “the minimum height of the flue system further than 3 m from the highest point of the roof shall be 1000mm
above the roof penetration.”
•d “no part of any building lies in or above a circular area described by a horizontal radius of 3 m about the flue
s
y
stem exit.”

14 December 2010
Due to continued product improvement, Broady’s reserves the right to change product specifications without prior notification.
All Dimension are in mm………….Copyright ©
9
FLUE PENETRATION Vented through Alcove (Single
lined Flue System)
Test Report Number Date of Report
04/1039 20th July 2004
04/1040 20th July 2004
04/1041 20th July 2004
FLUE PENETRATION Vented through Alcove (Double
lined Flue System)
FLUE PENETRATION Vented through Top Flashing
All external air vents and ceiling penetrations are to
be Vermin and Rodent proof.
Note :
External Requirements
Refer to AS/NZS2918:2001 4.9.1/
NZS5261/5262:2003
Install Flue system to AS/NZS2918:2001/
5261/5262:2003
When using a rubber or Bitumen flashing (Butynol,
Dectite) an Additional Flue pipe Baffle is required.
All external air vents & ceiling penetrations must
be bird proofed with permanently fixed screens.
All flashing to comply with E2.

14 December 2010
Due to continued product improvement, Broady’s reserves the right to change product specifications without prior notification.
All Dimension are in mm………….Copyright ©
10
CHIMNEY CHASE FLASHING DETAILS
“CHIMNEY CHASE FLASHING” AND “AIR VENTILATION” OPTIONS :
Note:
Flashing Spigot height is determined by
the Insulation that is fitted under the
Flashing … See Details at bottom of page.
VENTING THROUGH CHIMNEY CHASE
“No Insulation
under flashing” VENTING THROUGH FLASHING
“Insulation under
flashing”

14 December 2010
Due to continued product improvement, Broady’s reserves the right to change product specifications without prior notification.
All Dimension are in mm………….Copyright ©
11
FLUE HEIGHT MINIMUM DETAILS
FRAME OUT AND TRIM OUT DETAILS FOR CHIMNEY CHASE
Option X – Singled Lined Flue System Option Y – Double Lined Flue System
The Flue exit is to comply to ASNZS 2918 : 2001
3D View

14 December 2010
Due to continued product improvement, Broady’s reserves the right to change product specifications without prior notification.
All Dimension are in mm………….Copyright ©
12
COMBUSTIBLE MANTLE CLEARANCES
HEARTH CLEARANCES
Note: For Combustible Floors
Minimum Hearth of 300mm (A) must be
maintained at any given height.

14 December 2010
Due to continued product improvement, Broady’s reserves the right to change product specifications without prior notification.
All Dimension are in mm………….Copyright ©
13
Fp SG & Fp EG Range: Gas Convection Fireplaces
FLUED GAS APPLIANCES All Gas Fires requiring Tested Flue Systems shall be Installed to the requirements of NZS 5261 and shall be appropriately designed and
constructed to permit safe and effective use. This Appliance must be flued to the outside atmosphere. All Broady`s Fires must be Installed with a minimum of 3.6m of
Approved Broady`s Gas Flue and Liners .
GAS TYPE All Gas Fires shall operate safely on the Gas Type specified on the Appliance and shall comply with the requirements of The Gas Act 1992 .
APPLIANCE SAFETY Any Gas Fire Appliance shall comply with the safety requirements of NZS 5262 or any one of the Standards listed or referred to in "related
documents" of this Standard .
ELECTRICAL REQUIREMENTS All Gas Fire Appliances Installed with Mains Supplied Electrical components for associated use with these Appliances, must comply
with The Electricity Regulations 1993.
ELECTRONIC CONTROL SYSTEMS Any Gas Fire Appliance Installed with Manual or Programmable Electronic Control System shall be tested and/or approved by
a Recognised Person or Authority.
SEISMIC RESTRAINTS All Fires used for Domestic and Commercial Purposes shall be firmly secured (unless defined as portable or mobile) to prevent dislodgement
from their point of fixture or Installation during Seismic Activity. Such Restraint must be of a reasonable expectation .
GAS CONNECTION
A Gas Certificate must be obtained for the Installation and Commissioning of this Appliance and Flue System .
Check that the Gas Type Specified on the Data Plate is correct for the available supply (LPG or NG).
A Copper Gas supply capable of supplying the correct MJ/h , should be brought into the rear of the Installation Cavity through the hole provided . A Flare Nut is pro-
vided on the Burner for Gas Connection to the Appliance .
TO THE INSTALLER / GAS FITTER and ELECTRICIAN
NOTES :
• Service annually or more if required.
• Custom built to clients requirements to NZS5261/5262:2003 Clause B2.3
• The Appliance and Flue System must be installed in accordance with NZS5261/5262:2003 and the appropriate Building codes.
• The Appliance and Flue System must be tested in accordance with NZS:5261 and the appropriate Building codes.
COMMISSIONING AND TESTING OF FIREPLACE (To be carried out by Gasfitter)
FITMENT OF BURNER
Burner may be
Secured
To the Firebox
(Optional)
Gas Supply Pipe
Into Fire ,
by Gasfitter .
See Spec’s for
Pipe Size.
Read all the instructions before commissioning. Install coals and logs and burner before commission.
Light appliance and check HIGH/LOW settings. Check operation of appliance and adjust to suit.
Adjust control valve setting if required. After a period of running (30min Plus) check the setting of the pilot and adjust if required. See Spec’s for details.
Extinguish appliance, remove test equipment and secure test nipple. Check for Gas Leaks.
Note* The Control Valves are factory set and should not require adjustment.
GAS FITTER TO CARRY OUT STANDARD TESTING FOR COMMISSION:
• Spill test taken at top of opening with smoke or smoke match,
• Leak testing appliance and joints,
• Correct operation of the burner and coal and log lay out,
• Test gas pressures high and low, drop test on supply line,
• 5 second light time across burner, Other testing that may be required.
• Ventilation requirements to the standards,
• Hand over to Client, tests and comply to NZS:5261.

14 December 2010
Due to continued product improvement, Broady’s reserves the right to change product specifications without prior notification.
All Dimension are in mm………….Copyright ©
14
APPLYING THE VERMICULITE : (Course—must be larger than the burner plates holes so not to block them)
Apply with care a thin layer of Vermiculite over the Burner, just enough to cover the Burner Tray only .
NOTE: If the burner flame is uneven, the Vermiculite may need to be changed or sifted to remove the smaller pieces that can block the burners
holes. The smaller pieces can ,cause uneven burn and the unit to run dirty.
COALS AND LOGS (To be set by Gasfitter)
VERMICULITE (COURSE) (To be set by Gasfitter)
Bottom Top
8 6
Bottom
2
Top
2
Model
Fp 780
Fp 900 10 9 2 2
Fp 1100 11 10 2 2
Fp 700 6 5 2 2
Total Coals
Total
22
28
38
42
Number of Coals per Row Number of Rows
2 : Top Row
Slide R & LH Grate
Pins into Holes located
on the Burner Side
plates .
1 : Bottom Row
Gloves should be worn when handling Ceramic Fibre Coals & Logs : care needs to be taken when handling Coals & Logs , Due to the Carbon on the
Coals can stain the surroundings.
HELPFUL HINTS : When Hot use Metal Tongs.
Apply a thin layer of Vermiculite over the Burner , just enough to cover the Burner Tray only as shown above.
1 : Bottom Row : Assemble 2 Bottom Rows of Coals onto the Vermiculite Base . 2 : Top Row : Assemble 2 Top Rows of Coals onto the Bottom Row .
Each Coal randomly positioned with the Torn (roughest) Face Outward . Ensure Coal positioning does not directly block the 3 Flame Pilot .
The placement of the Coals & Logs may vary to make an even Flame Pattern .
Logs and Twigs may be scattered to achieve best Visual Effect .
Fit Burner Grate by sliding R & L Side Metal Pins on Grate, into Holes Located on Burner Side Plates , as shown below .
Model SG780 Shown: Total number of coals will vary per model.
General Coal orientation fro optimum effect.

14 December 2010
Due to continued product improvement, Broady’s reserves the right to change product specifications without prior notification.
All Dimension are in mm………….Copyright ©
15
Locate the three self-tapping screws provided into the under-side of the top ledge of the firebox
Remove the backing tape from the adhesive Velcro pads at the bottom of each fascia side
Offer the fascia into position locating the three screws into their associated slots - tighten screws
Apply firm pressure to the bottom edges to bond the Velcro tape
The fascia may be removed at any time by loosening the screws and parting the Velcro
Please refer to additional sheet for Burner Ratings and Frame-out details.
FASCIA KIT (Black or Stainless Steel)
Your Fire must be Installed and Tested by a suitably qualified Gasfitter prior to use.
To light :
Lower the control-cover by pulling it outwards .
Depress the Ignition Switch and hold in the 'PILOT' position for 3-5 seconds. (This may take some time for the Gas to come
through to the Pilot-3 Flame)
Strike the Igniter by turning to the 'STAR' position , maintaining the Switch in a Depressed State ; (repeat steps 2 & 3 if neces-
sary)
Once the Pilot Flame is lit, hold this position for 3-5 seconds , release from the Depressed State
before setting the Flame Control to Full , it may take 3-5 seconds for the Burner to Light .
Once the Flame Bed is established, set the Flame Control to the desired level & close cover.
To shut down :
Open control cover by pulling it outwards.
Turn control switch to 'PILOT'. Flame bed will extinguish.
Pilot light may be left running or extinguished by switching to 'OFF' before closing cover.
OPERATION OF YOUR GAS CONVECTION FIRE (Manual ONLY)
Note:
Fascia is Fitted at the end of the
Installation process and may be
after the wall and surroundings
have been completed .

14 December 2010
Due to continued product improvement, Broady’s reserves the right to change product specifications without prior notification.
All Dimension are in mm………….Copyright ©
16
Note: When the Base screw is removed, gas will leak from the out let, ensure that the pilot is not adjusted
or the screw is removed when the fire is burning.
• Adjustment of Pilot - 3 Flame : Unscrew Base Screw as shown in Diagram 2 .
• Insert a Screw Driver as shown in Diagram 3 and adjust the Adjustment Screw up inside the 3
Flame Pilot to adjust the Flame Height .
• The Flame must always be passing over the Electrodes &/or File Tube on either side .
ADJUSTMENT OF HI—LOW PRESSURE (Manual ONLY) (Only to be Adjusted by Gasfitter)
ADJUSTMENT OF THE PILOT—3 FLAME (BOTH Fp SG & Fp EG) (Only to be Adjusted by Gasfitter)
Note* Control Valves are Factory Set but may require adjustment onsite .
Turn Appliance Off & Remove Front Plastic Cover on Igniter , Pull Cover to Slide off .
Unscrew Test Nipple on the Burner Manifold & fit the Test Gauge Securely - See Diagram
* To Set the High : Light the Burner & turn to High - Then Adjust the High Screw to the Desired Pressure . See Spec’s
* To Set the Low : Light the Burner & turn to Low - Then Adjust the Low Screw to the Desired Pressure . See Spec’s
Extinguish Appliance, remove Test Equipment and Secure Test Nipple .
* Check Valve & Burner for Correct Operation & check Fire for Gas Leaks .
Adjustment of High & Low Settings Must be Carried out by a Certified Gas Fitter Only .
3 Flame Pilot in
Assembled State
Correct Operation of
3 Flame Pilot
32
Note: to Gas Fitters
The 3 flame pilot may need adjustment
after a period of running time on set up
as the increase in heat in the fire will
induce a higher draft in the fire, and
may pull in flame away from the File
Tube causing the fire to shut down.
for Gas Fires

14 December 2010
Due to continued product improvement, Broady’s reserves the right to change product specifications without prior notification.
All Dimension are in mm………….Copyright ©
17
Open windows and doors
Do not light any gas appliance
Do not use any electrical appliance or switches
Do not use the telephone in your home
Leave the building; shut off the domestic gas supply valve (beside your meter)
POINTS OF SAFTEY—To the Customer /Home-Owner
WHAT DO YOU DO IF YOU SMELL GAS
*Lighting your gas fire using electronic or remote ignition systems may vary as per manufacturer instructions
Broadys recommend annual servicing of your gas fire by an approved Broadys dealer Gas Fitter.
External surfaces should be dusted with a damp, lint-free cloth when the fire is cold.
Broadys provide 12 months warranty from the date of purchase, for domestic or commercial installations
This Warranty Covers :
Replacement Parts and Labour for Gas Control Components due to Manufacturing Defects Only.
Repair or Replacement of the Burner or Firebox Components due to Manufacturing Defects Only.
Warranty cover will be considered void if the product is subject to incorrect installation, failure to operate the appliance in accordance with the
supplied instructions and specifications or is subject to damage or misuse beyond the expected conditions of normal use.
All Installations and servicing must be carried out by and approved Broady’s dealer or Gas Fitter.
Your Broady`s Gas Decorative Fire operates on the principle of dual radiant and convected heat. Therefore it is important to observe the following precautions associated
with any heating appliance or open fire.
• Do not cover or restrict the fireplace upper or lower vents in any way as this may result in a build-up of hazardous gases within the room.
• The fire is not intended for the drying of clothing, bedding etc.
• Avoid installing this appliance in high traffic areas, strong draughts or near drapes or furniture.
• The use of an approved fireguard is recommended for the protection of young children.
• Avoid using aerosols when the appliance is operating.
• Avoid anyone leaning against or lying directly in front of the fire while operating.
• Do not place anything objects into or against the gas fire at any stage.
• The fire may release a small amount of smoke on its first start up which may take 1or 2 hours to dissipate . This is part of the curing process so ensure there is
adequate ventilation within the room.
• Always use a registered Gas Fitter or Electrician for installing and maintenance work
• Always use certified gas cylinders that have been tested and are safe to use.
• Never modify your gas appliance or its settings from those specified by the manufacturer.
APPLIANCE SAFETY Any gas fire appliance shall comply with the safety requirements of NZS 5262 or any one of the Standards listed or referred to in "related docu-
ments" of this Standard.
ELECTRONIC CONTROL SYSTEMS Any gas fire appliance fitted with manual or programmable electronic control systems shall be tested and/or approved by a recog-
nised person or authority.
MAINTENANCE : All burner setting, Coals placement, Vermiculite is to be checked and set in accordance with
this specification by the service person/Gas fitter

14 December 2010
Due to continued product improvement, Broady’s reserves the right to change product specifications without prior notification.
All Dimension are in mm………….Copyright ©
18
AS SHOWEN FROM THE FRONT OF THE BURNER.
This Control Panel is Located on the Bottom Left Hand Side of your decorative Gas Fire.
Press and Release the Power Button. This will Start the Electronic Spark and the Power LED will be on
Permanently . The Pilot will Ignite First, once this is on, it will ignite the Main Burner. Pressing and
Releasing the Power Button again will Switch Off the Appliance.
When the Appliance is Turned On again, the Gas Fire will resume the previous Flame and Fan set-
tings , unless the Appliance was Switched Off due to Power Failure. In the circumstance of a Power
Failure the Remote Control System will return to the default settings which is a Low Flame and the
Fan Turned Off.
If the Gas Fails to light, the Appliance it will go into Lock Out Mode , after trying to ignite for 1 minute
(approx.) . In Lock Out Mode the Power LED will remain illuminated. To start the Appliance again
Press and Release the Power Button Twice after the Gas Supply Resumes.
Press and Hold the + button to Increase the Main Burner Flame . Press and Hold the - button to De-
crease the Main Burner Flame. By holding the + or -Flame Button for up to 10-15 sec this will Increase
or Decrease the Main Burner Flame to it’s Max or Min .
OPERATION OF YOUR FpE.G GAS BURNER IGNITER ONLY
FOR MANUAL OPERATION OF YOUR FpEG DECORATIVE FIRE
FLAME OPERATION

14 December 2010
Due to continued product improvement, Broady’s reserves the right to change product specifications without prior notification.
All Dimension are in mm………….Copyright ©
19
This Decorative Gas Fire has a 3 Speed Fan and its operated independent from the Main Burner.
This is done by pressing and releasing the fan + or – button will Increase or Decrease the Fan
Speed. The LED on the Front Panel will indicate the Fan Settings at Low, Medium, or High Speed.
Pressing and Releasing of the button will Lower the Speed until the Fan is Turned Off .
Your Remote Control has all the features of the Control Receiver situated on the Front Panel of the
Burner .
By pressing Timer Button , the Power LED will start flashing and after 30 minutes the appliance will
Shut Off Automatically .
By pressing the Timer Button again within the 30 minute period, this will reset the Timer and the
power LED will Stop Flashing .
Warranty Cover will be considered void if failure to operate the appliance in accordance with the
supplied Instructions and Specifications, or is subject to damage or misuse beyond the expected
conditions of normal use which could result in injury or property damage .
FAN OPERATION
REMOTE CONTROL FEATURES
IMPORTANT NOTE ABOUT YOUR DECORATIVE FIRE

14 December 2010
Due to continued product improvement, Broady’s reserves the right to change product specifications without prior notification.
All Dimension are in mm………….Copyright ©
20
PROCEDURE FOR THE TEST AND COMISSIONING OF YOUR DECORATIVE FIRE.
Ensure Gas Supply and the Power Supply (caution 240V) to the Unit.
• Refer to Data Plate on this Specification for settings. The Data Plate is attached to the under carriage of
the Burner .
• Remove Front Grate ensure the CAT5 cable to the Control Receiver is still connected.
• Loosen the Jet Test point and attach manometer (Digital is preferred). The Test Point is on the Right
Hand Side of the Gas Burner , as Shown Below .
• Light Appliance, adjust to High Flame setting and check pressure, adjust to Low Flame and check pres-
sure.
NOTE : If setting the Pressure is required it is to be carried out by a Certified Gas Fitter.
• If adjustments are necessary, remove the cap . The Pressure Adjustment Screw and Nut are on the
Front Side of the Gas Control Valve (shown in Diagram B in this specification) and are Factory set.
High Pressure Setting: Set the modulator to Maximum Condition. Screw in “Nut A” to Increase the Outlet
Pressure then screw “Nut A” out to Decrease the Pressure to the desired settings . Use 10mm spanner.
Low Pressure Setting: Turn Off the Power to the Modulator (by disconnecting the Modulator Harness Connec-
tion at the Valve - See Wiring Diagram in Page 17 .) and, keep Nut A stationary . Use a screwdriver to screw in
“Screw B” to Increase the Pressure and Screw it Out to Decrease the Pressure . Carefully replace the Modula-
tor Plastic Cap .
WARNING: To ensure the Correct Operation of the Modulator it is necessary that the Plastic Cap is returned to
its original location .
Gas Test Nipples
for SG / EG Fires
This manual suits for next models
3
Table of contents
Popular Indoor Fireplace manuals by other brands

Evonicfires
Evonicfires Alisio 850 instruction manual

Dimplex
Dimplex HAR20 Installation and operating instructions

Valcourt
Valcourt Beaumont Installation and operation manual

Desa
Desa CDCFNR OWNER'S OPERATION AND INSTALLATION MANUAL

Dru
Dru Maestro 75XTU RCH installation manual

Jøtul
Jøtul S17-I400 installation manual

Jensen
Jensen 13045LP owner's manual

RSF Woodburning Fireplaces
RSF Woodburning Fireplaces Opel AP owner's manual

Mirage
Mirage SERIES A Installation and operating instructions

Quadra-Fire
Quadra-Fire CASTILE Owner's manual installation and operation

Regency
Regency P33CE-NG Owners & installation manual

Nordpeis
Nordpeis Havanna user manual