
14
Clearance to Combustibles
The distance to be maintained from the surfaces of the replace
to combustibles must be observed. Below is a list of the most
common combustible materials to name a few:
Drywall Wood ooring Plywood
Sub-ooring Wood Framing Particle board
Mill board Plywood paneling
Maintain the following minimum clearances:
Unit front, sides, rear 2” (50,8 mm)
Combustible oor 6” (152,4mm)
Sheathing or trim to opening sides 8” (203,2mm)
Combustible sheathing above opening top 8” (203,2mm)
Mantel above opening 12” (304,8mm)
Opening to side wall 20” (508 mm)
Insulation from rebox 0” (0 mm)
Due to high temperatures, never install this replace in a
recreational vehicle, in high trac areas, drafty areas, or where
curtains, furniture, clothing, or other ammable objects are
less than 36” from the front or side and 42” from the top of the
replace.
CAUTION: This gas replace attains high temperatures. Keep
children and adults away from hot surfaces to avoid ignition of
clothing and/or burns. Even after the replace is shutdown it will
remain hot for a time afterward. Allow the surface to cool before
touching it.
Carefully supervise young children when they are in the room
with the replace.
All replace openings for both combustion air and exhaust must
remain open and unobstructed at all times when the replace
is in operation. Adequate clearances around air openings into
combustion chamber must be maintained.
Adequate accessible clearances for servicing and proper
operation must also be maintained.
The Artisan Series replace has been designed, tested and
approved for 6 inch clearance to combustible oors.
Be certain that the Artisan Series replace is installed with
the nished re brick oor of the replace so that it is at least 11”
(eleven inches) above the combustible oor system.
Warning to the structural engineer and/or building contractor:
It is your responsibility to be certain that the replace can be
properly supported by the combustible oor system on which the
replace will rest. Be advised that this engineering equation will
be in addition to any live or dead weights that the oor has to
carry.
Artisan Series Fireplace & Chimney Systems
Before Getting Started…
Even if you consider yourself an expert in the eld of replace
installation, we at Capo Fireside, LLC caution you to take the
time to totally familiarize yourself with the instructions to follow.
We can assure you that there will be information that will
make the installation go smoother and, above all, safer, for
everyone concerned. At the least, reading these procedures will
save you time and, at the most, it will prevent any malfunction
that could result in property damage or serious injury.
Do not start the installation until you have checked out all
the local, regional, state and national rulings, laws and codes
as they apply to replaces and replace installations. Every
community is dierent so do not assume that because you
know the requirements for one locality, it will be the same in the
next. Avoid bureaucratic hassles and do your homework WELL
BEFORE you start your project!
1) The Artisan Series gas replace is designed to be installed
with a B-vent metal chimney system. Such chimney systems
are acceptable where any traditional masonry replace has
been specied. Note that the chimney system must always
vent to the outside of the building.
2) This Artisan Series replace is intended as a supplemental
heat source only. It is not intended as a primary heat source.
3) It is the responsibility of the contractor installer (not the
manufacturer) to ensure that adequate combustion air is
provided for proper function of this replace. Fireplaces take
up a large volume of replacement air from outside the house
and if the house is of airtight construction, smoke spillage
may occur if proper draft is not achieved.
4) There are many conditions beyond a manufacturer’s
control when it comes to the operation of the replace.
The manufacturer cannot be responsible for “smoke free”
operation, nor can the manufacturer take on the responsibility
for problems with surrounding construction; chimneys that
have not been built at the right heights; system drafts caused
by faulty mechanical systems; adverse weather conditions or
any other inclement environmental situations over which the
manufacturer has no control.
5) Inspect all replace & chimney components for evidence
of damage prior to starting installation. Consult your local
distributor for replacement parts if necessary.
6) Under no circumstances should you make any adjustments
or modications to the chimney system during the installation
procedure. If you do, you are not only liable for negating the
warranty, but you could very well cause a serious malfunction
of the replace. You must follow these chimney instructions.