
1--8
T--304 04/08
b. Condenser Fan Motor
Condenser Motor Permanent Magnet
24 VDC 12 VDC
Horsepower (kW) 1/8 (.09)
Full Load Amps (FLA) 918
Operating Speed
(RPM) 2950
Bearing Lubrication Factory Lubricated
(additional grease not required)
c. Temperature Sensors (Return Air Sensor)
Input Range: --52.6 to 158°F (--47 to 70°C)
Output: NTC 10K ohms at 77°F(25°C)
d. Ambient Sensor (Optional)
Opens at: 25°F(10°C)
Closes at: 35°F(1.7°C)
1.5 SAFETY DEVICES
System components are protected from damage
caused by unsafe operating conditions with safety
devices. Safety devices with Carrier Transport Air
Conditioning supplied equipment include high pressure
switch (HPS), low pressure switch (LPS), circuit
breakers and fuses.
a. Pressure Switches
High Pressure Switch (HPS)
During the air conditioning cycle, compressor clutch
operation will automatically stop if the HPS switch
contacts open due to an unsafe operating condition.
Opening HPS contacts de-energizes the compressor
clutchshuttingdownthecompressor.Thehighpressure
switch (HPS) is installed at the compressor assembly
(05G, 05K & TM--31).
Low Pressure Switch (LPS)
The low pressure switch is installed close to the
compressor and openson a pressure dropto shut down
the system when a low pressure condition occurs. The
lowpressureswitchisinstalledatthecompressor(05G,
05K & TM--31).
NOTE
Ondual loopsystems that usetheA--6, TM--21
& some TM31’s, the pressure switches are not
located on the compressors. They are installed
in--line.
b. Fuses and Circuit Breakers
The RelayBoardis protectedagainst high current by an
OEM supplied circuit breaker or fuse located in the bus
battery compartment (150 Amp for 12 VDC & 125 Amp
for 24 VDC systems). Independent 15 Amp, 24 VDC or
20 Amp, 12 VDC fuses protect each motor while the
output circuits are protected by an additional 5 Amp
circuit breaker. During a high current condition, the fuse
may open.
1.6 AIR CONDITIONING REFRIGERATION
CYCLE
When air conditioning (cooling) is selected by the
controller, the unit operates as a vapor compression
system using R-134a as a refrigerant (See Figure 1--6
Dual Loop & Figure 1--8 Single Loop flow diagrams).
The main components of the system are the A/C
compressor, air-cooled condenser coils, receiver,
filter-drier, thermostatic expansion valve, liquid line
solenoid valve and evaporator coils.
The compressor raises the pressure and the
temperature of the refrigerant and forces it into the
condenser tubes. The condenser fan circulates
surroundingair(whichisatatemperaturelowerthanthe
refrigerant) over the outside of the condenser tubes.
Heat transfer is established from the refrigerant (inside
the tubes) to the condenser air (flowing over the tubes).
The condenser tubes have fins designed to improve the
transfer of heat from the refrigerant gas to the air; this
removal of heat causes the refrigerant to liquefy, thus
liquid refrigerant leaves the condenser and flows to the
receiver.
The refrigerant leaves the receiver and passes through
the receiver outlet/service valve, through a filter-drier
where a descecant keeps the refrigerant clean and dry.
From the filter-drier, the liquid refrigerant then flows
through the liquid line solenoid valve to the sight--glass
and then to the thermostatic expansion valve. The
thermal expansion valve reduce pressure and
temperature of the liquid and meters the flow of liquid
refrigerant to the evaporator to obtain maximum use of
the evaporator heat transfer surface.
The low pressure, low temperature liquid that flows into
the evaporator tubes is colder than the air that is
circulated over the evaporator tubes by the evaporator
fans (fans). Heat transfer is established from the
evaporator air (flowing over the tubes) to the refrigerant
(flowing inside the tubes). The evaporator tubes have
aluminum fins to increase heat transfer from the air to
the refrigerant; therefore the cooler air is circulated to
the interior of the bus. Liquid line solenoid valve closes
during shutdown to prevent refrigerant flow.
The transfer of heat from the air to the low temperature
liquid refrigerant in the evaporator causes the liquid to
vaporize. This low temperature, low pressure vapor
passes through the suction line and returns to the
compressor where the cycle repeats.
1.7 HEATING CYCLE
Heating circuit (See Figure 1--7) components furnished
byCarrier TransportAirConditioningincludetheheater
cores and solenoid operated heat valves. Components
furnished by the bus manufacturer may include a water
temperature switch (WTS) and boost water pump.
The controller automatically controls the heat valves
during the heating mode to maintain required
temperatures inside the bus. Engine coolant (glycol
solution) is circulated through the heating circuit by the
engine and an auxiliary boost water pump. When the
heat valve solenoids are energized, the valves willopen
to allow engine coolant to flow through the heater coils.
The valves are normally closed so that if a failure
occurs, the system will be able to cool.