2
Commercial Defrost Control . . . . . . . . . . . . . . . . . . . 26
• REVERSING VALVE CONTROL
• COMPRESSOR CONTROL
•DEFROST
• DEFROST THERMOSTAT
• DEFROST SPEEDUP FUNCTIONS
COMFORT ALERT DIAGNOSTIC MODULE . . . . . . . 30
Outdoor Fans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Lubrication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
•FANMOTORS
• COMPRESSOR
Outdoor Coil Maintenance and Cleaning
Recommendation . . . . . . . . . . . . . . . . . . . . . . . . . 32
• REMOVE SURFACE LOADED FIBERS
• PERIODIC CLEAN WATER RINSE
• ROUTINE CLEANING OF INDOOR COIL SURFACES
Service Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
FASTENER TORQUE VALUES . . . . . . . . . . . . . . . . . 34
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . 35
APPENDIX A — AIR CONDITIONER AND HEAT
PUMP WITH PURON®—
QUICK REFERENCE GUIDE . . . . . . . . . . . . . . . . . 36
APPENDIX B — WIRING DIAGRAM LIST . . . . . . . . . 36
APPENDIX C — LOW AMBIENT OPTION —
FACTORY INSTALLED . . . . . . . . . . . . . . . . . . . . . 44
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, mainte-
nance, or use can cause explosion, fire, electrical shock or other
conditions which may cause personal injury or property damage.
Consult a qualified installer, service agency, or your distributor or
branch for information or assistance. The qualified installer or
agency must use factory-authorized kits or accessories when mod-
ifying this product. Refer to the individual instructions package.
Follow all safety codes. Wear safety glasses and work gloves. Use
quenching cloths for brazing operations and have a fire extin-
guisher available. Read these instructions thoroughly and follow
all warnings or cautions attached to the unit. Consult local build-
ing codes and appropriate national electrical codes (in USA,
ANSI/NFPA70, National Electrical Code (NEC); in Canada, CSA
C22.1) for special requirements.
It is important to recognize safety information. This is the safety-
alert symbol . When you see this symbol on the unit and in in-
structions or manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, CAUTION,
and NOTE. These words are used with the safety-alert symbol.
DANGER identifies the most serious hazards which will result in
severe personal injury or death. WARNING signifies hazards
which could result in personal injury or death. CAUTION is used
to identify unsafe practices, which may result in minor personal
injury or product and property damage. NOTE is used to highlight
suggestions which will result in enhanced installation, reliability,
or operation.
GENERAL
See Fig. 1for unit dimensions. For physical data, see Tables 2-3.
For model number nomenclature, see Fig. 2. For date of unit man-
ufacture, see Fig. 3.
Rated Indoor Airflow (cfm)
Table 1below lists the rated indoor airflow used for the AHRI ef-
ficiency rating for the units covered in this document.
INSTALLATION GUIDELINE
Replacement /Retrofit — R-22 to Puron Refrigerant
Split system heat pumps are intended to be installed with match-
ing indoor sections only. The 38AUQ heat pump outdoor units are
matched only with same-size 40RFQ indoor sections. Existing
R-22 indoor coils cannot be converted to Puron®R-410A heat
pump duty. Only the existing refrigerant piping is a candidate for
retrofit use.
ACID TEST
If the existing system is being replaced because of a compressor
electrical failure, assume acid is in system. If system is being re-
placed for any other reason, use an approved acid test kit to deter-
mine acid level. If even low levels of acid are detected, install a
100 percent activated alumina suction line filter drier in addition to
the replacement liquid-line filter drier. Operate this system in
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could cause personal injury or
death.
Before performing service or maintenance operations on unit,
turn off main power switch to unit and install lock(s) and lock-
out tag(s). Ensure electrical service to rooftop unit agrees with
voltage and amperage listed on the unit rating plate. Unit may
have more than one power switch.
WARNING
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could cause personal injury,
death and/or equipment damage.
Puron®(R-410A) refrigerant systems operate at higher pres-
sures than standard R-22 systems. Do not use R-22 service
equipment or components on Puron refrigerant equipment.
WARNING
PERSONAL INJURY AND ENVIRONMENTAL
HAZARD
Failure to follow this warning could cause personal injury or
death.
Relieve pressure and recover all refrigerant before system
repair or final unit disposal.
Wear safety glasses and gloves when handling refrigerants.
Keep torches and other ignition sources away from
refrigerants and oils.
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and
wear appropriate protective clothing, safety glasses and gloves
when handling parts and servicing 38AUQ units.
Table 1 — 38AUQ with 40RFQ
MODEL NUMBERS FULL LOAD AIRFLOW (cfm)
38AUQD/E07 - 40RFQ*07 2400
38AUQM/N08 - 40RFQ*08 3000
38AUQD/E12 - 40RFQ*12 3000