
Fig. 5—Label Wiring 327413-101 A05018
FIELD SELECTED TIME PERIOD
BETWEEN DEFROST CYCLES (MINUTES)
JUMPERED TEST PINS (USE METAL OBJECT), FIELD SPEED-UP CYCLE
HEAT CYCLE: 90 MIN. ACCELERATED TO 21 SEC.
60 MIN. ACCELERATED TO 14 SEC.
50 MIN. ACCELERATED TO 12 SEC.
30 MIN. ACCELERATED TO 7 SEC.
10 MIN. ACCELERATED TO 2 SEC.
DEFROST CYCLE:
90
30
SPEED
UP
FACTORYPOWERWIRING
FIELDPOWERWIRING
FACTORYCONTROLWIRING
FIELDCONTROLWIRING
CONDUCTORONCIRCUIT
BOARD
COMPONENTCONNECTION
1/4-INCHQUICKCONNECT
TERMINALS
FIELDSPLICE
JUNCTION
CAPACITOR(DUALRUN)
CRANKCASEHEATER
COMPRESSOR
CONTACTOR
CIRCUITBOARD
DEFROSTTHERMOSTAT
DEFROSTRELAYAND
CIRCUITRY
DISCHARGETEMP.SWITCH
HIGHPRESSURESWITCH
LOWPRESSURESWITCH
OUTDOORFANMOTOR
REVERSINGVALVE
SOLENOID
CAP
*CH
COMP
CONT
CB
DFT
DR
*DTS
*HPS
*LPS
OFM
RVS
*MAYBEFACTORYORFIELDINSTALLED.
-LEGEND-
327413-101 REV. B
SCHEMATIC DIAGRAM (LADDER FORM)
CONNECTION DIAGRAM
1. Compressor damage may occur if system is over
charged.
2. This unit is factory charged with R-22 in accordance
with the amount shown on the rating plate. The
charge is adequate for most systems using
matched coils and tubing not over 15 feet long.
The best performance will be achieved when the
unit operates with a suction gas superheat at the
compressor inlet of 5 ºF at normal rating conditions
of the air conditioning and refrigeration, institute
(ARI). This chart may be used to approximate the
charge if ARI rating conditions cannot be obtained.
ARI rating conditions are equivalent to DOE test "A"
conditions. See product data literature for required
indoor air flow rates and for use of line lengths over
15 Ft.
3. Relieve pressure and recover all refrigerant before
system repair or final unit disposal. Use all service
ports and open all flow-control devices, including
solenoid valves.
1. Compressor and fan motor furnished with
inherent thermal protection.
2. To be wired in accordance with National
Electric Code (N.E.C.) and local codes.
3. N.E.C. class 2, 24V circuit, min. 40 VA required.
4. Use copper conductors only, from disconnect
to unit.
5. Must use thermostat and sub-base as stated
in pre-sale literature.
6. If indoor section has a transformer with a
grounded secondary, connect the grounded
side to "C" on the circuit board.
7. If any of the original wire, as supplied, must
be replaced, use the same or equivalent wire.
8. Check all electrical connections inside control
box for tightness.
9. Do not attempt to operate unit until service
valves have been opened.
10. It is imperative to connect 3Ø field power
to unit with correct phasing. The Phase
Rotation Monitor will not allow the contactor
to be energized if thephasing is not correct.
If phasing is reversed, simply interchange any two
of the three power connections on the field side.
11. Use conductors suitable for at least 75ºC (167ºF).
NOTES:
CAU
TIO
N
COOLING ONLY
PROCEDURE
EVAPORATOR ENTERING AIR ºF WB.
TEMP °F
OUTDOOR
50
TABLE I - SUPERHEAT CHARGING TABLE
(SUPERHEAT ºF AT LOW-SIDE SERVICE PORT)
52 54 56 58 60 62 64 66 68 70 72 74 76
55 9 37
60 7
65 -- 6
70 -- -- 7
75 -- -- -- 6 9 12 15 18 21 24 28 31 34 37
80 -- -- -- -- 5 8 12 15 18 21 25 28 31 35
85 -- -- -- -- -- -- 8 11 15 19 22 26
90 -- -- -- -- -- -- --------------
-- -- -- -- -- -- --
--
--
--
--
--
----
--
----
--
----
--
------
--
-- --
--
5 9 13 16 20 24 27 31
95 6
100 8 12 15 20 23 27
5 9 13 17 22 26
68
--
--
-- --
-- -- --
105
110
115
918987858381797775
40 898785838179777573
38 878583817977757371
36 858381797775737169
34 838179777573716967
32 817977757371696765
30 797775737169676563
28 777573716967656361
26 757371696765636159
24 737169676563615957
22 71
6967656361595755
20 696765636159575553
18 676563615957555351
16 656361595755535149
14 636159575553514947
12 615957555351494745
10 595755535149474543
8575553514947454341
6555351494745434139
4535149474543413937
25149
47454341393735
0
85.782.479.276.073.070.067.164.2
SUCTION PRESSUR E AT SERVICE PORT PSIG.
TEMP. °F
61.5
SUPERHEAT
45
43
41
39
42
40
35
32
29 4038
35
3330 38
3633 3633
30
27 30
2724
33
18 29
30
22 25
14
10
23
2520
18
14
1511
2723
23
18
1512
10 26
23
20
17
14
12
24
21
19
16
13
10 21
19
16
13
10
TABLEII - REQUIREDSUCTION TUBETEMPERATURE ºF
(MEASUREDATLOW-SIDESERVICEPORT)
L3
L2
L1
GND
EQUIP
CONT
11 21
T3
T1
T2
OF2OF1
DR CONT
*CH
23 13
OFM
COMP
CAP
C
RVS
OO
W2
RR
Y
Y
C
DFT
DFT
DR
T1 C
LOGIC
*HPS
*LPS *DTS
CONT
BRN
OFM BRN
RED or BLK YEL
BLK
BLU
L2
A
LE
R
T
!
(
N
OTE
#11
)
23
13
21
11
L3
L1
EQUIP GND
SUPPLY
POWER
208/230 3Ø
CONT
CAP
COMP
T2
T1 T3
*CH
BLK
RED
or
BLK
BLK
YEL
ORG
ORG or
or
RVS
BLK
BLK
DFT BLK
or
PNK
PNK
or
BLK
WHT
YEL
CB
DR
OF1
OF2
CY OW2R
Y
T1
LOGIC
50 90
30
SPEED
UP
R
C
C
DFT
O
PNK PNK
HK32EA001
*LPS *HPS
YEL
YEL BLU
BRN
YEL
ORG
ORG
GLER
W2
OYC
TERMINAL BLOCK
INDOORUNIT
RED
ORNBLK
G
W3
LER
W2
OYC
INDOOR THERMOSTAT (NOTE #5)
YEL
or
BLU
BLK YEL
1. Operate unit a minimum of
10 minutes before checking
charge.
2. Measure suction pressure
by attaching a gage to
suction valve service port.
3. Measure suction temperature
by attaching an accurate
thermistor type or electronic
thermometer to the suction
line at service valve.
4. Measure outdoor air dry-bulb
temperature with a
thermometer.
5. Measure indoor air (entering
indoor coil) wet bulb
temperature with a sling
psychrometer.
6. Refer to table I. Find out-
door temperature and
evaporator entering air wet-
bulb temperature at this
intersection note the super-
heat.
7. Refer to table II. Find super-
heat temperature located in
step 6 and suction pressure,
at this intersection note
suction line temperature.
8. If unit has a higher suction
line temperature than charted
temperature, add refrigerant
until charted temperature
is reached.
9. If unit has a lower suction
line temperature than charted
temperature, remove and
recover refrigerant until
charted temperature is
reached.
10. If outdoor air temperature
or pressure at suction valve
changes, charge to new
suction line temperature
indicated on chart.
11. This procedure is valid when
indoor air flow is within
+/- 21% of its rated cfm.
50
**
**
** BOARD MAY HAVE 60
AS MIDDLE SELECTION
**
6