manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Carrier
  6. •
  7. Heat Pump
  8. •
  9. Carrier 50JS User manual

Carrier 50JS User manual

50JS
Single-Packaged
50Hz Electric Heat Pump Units
A Guide to Operating and Maintaining Your
Single-Packaged Electric Heat Pump Units
NOTE: Read the entire instruction manual before starting the
installation.
SAFETY CONSIDERATIONS
Note to Installer:This manual should be left with the equipment
user.
Do not store or use gasoline or other flammable vapors and
liquids in the vicinity of these or any other appliances. Failure
to follow this warning could result in fire, serious injury, or
death.
Do not use this unit if any part has been under water.
Immediately call a qualified service technician to inspect the
unit and to replace any part of the control system which has
been under water. Failure to follow this warning could result
in electrical shock, fire, serious injury, or death.
Before performing recommended maintenance, be sure the
main power switch to unit is turned off and lock-out tag
installed. Electric shock could cause serious injury or death.
STARTING OR SHUTTING UNITS OFF
1. To start this unit:
a. Turn on the electrical power supply to unit.
b. Select temperature and set SYSTEM switch or MODE
control to desired mode.
2. To shut this unit off:
NOTE: If the unit is being shut down because of a malfunction,
call your dealer as soon as possible.
a. Set system SWITCH or MODE control to OFF.
b. Turn off the electrical power supply to unit and install
lock-out tag.
OPERATING YOUR HEAT PUMP
The operation of your heat pump system is controlled by the
indoor thermostat. You simply adjust the thermostat and it
maintains the indoor temperature at the level you select. Most
thermostats of heat pump systems have 3 controls: a temperature
control selector, a FAN control, and a SYSTEM or MODE control.
Refer to your thermostat owner’s manual for more information.
To better protect your investment and to eliminate unnecessary
service calls, familiarize yourself with the following facts:
1. During heating, increasing the thermostat setting more than
2°F/1.1°C may cause the supplemental heaters to be turned on
for a short period of time to satisfy the thermostat. Needless
use of the supplementary heat reduces potential energy sav-
ings.
2. Ice or frost tends to form on the coil during winter heating
operation. Your heat pump is designed to automatically melt
the ice. When in this defrost cycle, it is normal for steam or
fog to rise from the outdoor unit. Do not be alarmed!
Step 1—Cooling Mode
With the SYSTEM or MODE control set to COOL, your heat
pump will run in cooling mode until the indoor temperature is
lowered to the level you have selected. On extremely hot days,
your heat pump will run for longer periods at a time and have
shorter “off” periods than on moderate days.
Step 2—Heating Mode
With the SYSTEM or MODE control of your indoor thermostat set
to HEAT, your heat pump will run in heating mode until room
temperature is raised to the level you have selected. Of course,
your heat pump will run for longer periods to maintain a
comfortable environment on cooler days and nights than on
moderate ones.
Step 3—Supplemental Heat
Your heat pump is your primary heating source. Your system may
also be equipped with a supplemental heating source such as
electric heat. On cold days and nights, your system will automati-
cally turn on the supplemental heat in order to maintain the level
of comfort you have selected.
When your heat pump needs additional heat to keep you comfort-
able, your Carrier electronic thermostat will turn on the supple-
mental heat (if equipped) and display the “AUX HT” message.
Fig. 1—Unit 50JS (50Hz)
C99001
Visit www.carrier.com
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
PC 101 Catalog No. 005–00001 Printed in U.S.A. Form OM50-30 Pg 1 12–01 Replaces: New
Step 4—Defrost Mode
When your heat pump is providing heat to your home or office and
the outdoor temperature drops below 45°F/7.2°C, moisture may
begin to freeze on the surface of the coil. If allowed to build up,
this ice would impede airflow across the coil and reduce the
amount of heat absorbed from the outside air. So, to maintain
energy-efficient operation, your heat pump has an automatic
defrost mode.
The defrost mode starts at a factory selected interval of 30 minutes,
although, it may be reset to 50 or 90 minutes. Defrost will start at
the preset time only if the ice is sufficient to interfere with normal
heating operation.
After the ice is melted from the coil, or after a maximum of 10
minutes in defrost mode, these units automatically switch back to
normal heating operation.
Do not be alarmed if steam or fog appears at the outdoor unit
during defrost mode. Water vapor from the melting ice may
condense into a mist in the cold outside air.
During certain weather conditions such as heavy snow and
freezing rain it is not uncommon for ice to build up on the unit
grille. This is normal for these weather conditions. Do not attempt
to remove the ice from the unit grille. This condition will not affect
the proper function of the unit and will clear within a few days.
Step 5—Emergency Heat Mode
This allows your supplemental heating source to keep your home
or office warm until your heat pump can be serviced.
MAINTENANCE AND SERVICE
This section discusses maintenance that should be performed by
your dealer and with care you, as the owner, may wish to handle
for your new heat pump.
ROUTINE MAINTENANCE
All routine maintenance should be handled by skilled, experienced
personnel. Your dealer can help you establish a standard proce-
dure.
For your safety, keep your unit area clear and free of combustible
materials, gasoline, and other flammable liquids and vapors.
To assure proper functioning of your unit, flow of condenser air
must not be obstructed from reaching the unit. Minimum clearance
from the top of the unit is 48 in./1219 mm. Clearance of at least 36
in./914 mm is required on sides except the power entry side (42
in./1067 mm clearance) and the duct side (12 in./305 mm mini-
mum clearance).
MAINTENANCE AND CARE FOR THE EQUIPMENT
OWNER
Before proceeding with those things you might want to maintain
yourself, please carefully consider the following:
1. TURN OFF ELECTRICAL POWER TO YOUR UNIT
AND INSTALL LOCK-OUT TAG BEFORE SERVIC-
ING OR PERFORMING MAINTENANCE. ELECTRIC
SHOCK COULD CAUSE SERIOUS INJURY OR
DEATH.
2. When removing access panels or performing maintenance
functions inside your unit, be aware of sharp sheet metal
parts and screws. Although special care is taken to keep
sharp edges to a minimum, be extremely careful when
handling parts or reaching into the unit.
Air Filters
The air filter(s) should be checked at least every 3 or 4 weeks and
changed or cleaned whenever it becomes dirty. Dirty filters
produce excessive stress on the blower motor and can cause the
motor to overheat and shut down. Table 1 indicates the correct
filter size for your unit. Refer to Fig. 2 to access the filters.
To replace or inspect filters (or accessory filter rack when
supplied):
1. Remove the filter access panel using a 5/16-in. (7.9 mm) nut
driver or wrench.
2. Remove the filter(s) by pulling it out of the unit. If the filter(s)
is dirty, clean or replace with a new one.
When installing the new filter(s), note the direction of the airflow
arrows on the filter frame.
If you have difficulty locating your air filter(s) or have questions
concerning proper filter maintenance, contact your dealer for
instructions. When replacing filters, always use the same size and
type of filter that was supplied, originally, by the installer.
Table 1—Indoor-Air Filter Data
UNIT SIZE
50JS (50HZ) 024 030 036 048 060
RETURN-AIR
FILTERS (mm.)
Throwaway
20” x 20”
(508 x 508) 20” x 20”
(508 x 508) 20” x 24”
(508 x 609.6) 24” x 30”
(609.6 x 762) 24” x 30”
(609.6 x 762)
Fig. 2—Filter Access Panel-Vertical Supply Shown
(Unit Shown with Optional Louvered Grille)
C99094
ACCESS PANEL
FILTER ACCESS
PANEL*
*For accessory filter rack.
2
Never operate your unit without the filter(s) in place. Failure
to heed this warning may result in damage to the blower
motor and/or compressor. An accumulation of dust and lint on
internal parts of your unit can cause loss of efficiency and , in
some cases, a fire.
Fans and Fan Motor
Periodically, check the condition of fan wheels and housings and
fan-motor shaft bearings. Contact your dealer for the required
annual maintenance.
Indoor and Outdoor Coils
Cleaning of the coils should only be done by qualified service
personnel. Contact your dealer for the required annual mainte-
nance.
Condensate Drain
The drain pan and condensate drain line should be checked and
cleaned at the same time the cooling coils are checked by your
dealer.
Compressor
All compressors are factory-shipped with a normal charge of the
correct type refrigeration grade oil. A compressor should rarely
require additional oil.
Condenser Fan
Do not poke sticks, screwdrivers, or any other objects into
revolving fan blades. Injury or equipment damage may result.
The fan must be kept free of all obstructions to ensure proper
cooling. Contact your dealer for any required service.
Electrical Controls and Wiring
Electrical controls are difficult to check without proper instrumen-
tations. If there are any discrepancies in the operating cycle,
contact your dealer and request service.
Refrigerant Circuit
The refrigerant circuit is difficult to check for leaks without the
proper equipment. If inadequate cooling is suspected, contact your
local dealer for service.
System under pressure. Relieve pressure and recover all
refrigerant before system repair or final unit disposal to avoid
serious injury or death. Use all service ports and open all
flow-control devices, including solenoid valves.
Unit Panels
After performing any maintenance or service on either of these
units, be sure all panels are fastened securely in place to prevent
rain from entering unit cabinet and to prevent disruption of the
correct unit airflow pattern.
REGULAR DEALER MAINTENANCE
In addition to the type of routine maintenance you might be willing
to perform, your unit should be inspected regularly by a properly
trained service technician. An inspection (preferably each year, but
at least every other year) should include the following:
1. Inspection and, if required, cleaning of the outdoor and indoor
coils.
2. Inspection and, if required, cleaning of the indoor coil drain.
3. Inspection and cleaning of blower wheel housing and motor.
4. Inspection of all supply-air and return-air ducts for leaks,
obstructions, and insulation integrity. Any problems found
should be resolved at this time.
5. Inspection of the unit base to ensure that no cracks, gaps, etc.,
exist which may cause a hazardous condition.
6. Inspection of the unit casing for signs of deterioration.
7. Inspection of all electrical wiring and components to assure
proper connection.
8. Inspection for leaks in the refrigerant circuit. Pressure-check
to determine appropriate refrigerant charge.
9. Inspection of compressor oil level by service person to ensure
proper oil level is maintained in the compressor when it is
installed and running.
10. Operational check of the unit to determine working condi-
tions. Repair or adjustment should be made at this time.
Your servicing dealer may offer an economical service contract
that covers seasonal inspections. Ask for further details.
Complete service instructions can be found in each unit’s Instal-
lation, Start-Up and Service Instructions.
BEFORE YOU CALL FOR SERVICE ...
...check for several easily-solved problems.
If insufficient heating or cooling is suspected:
( ) Check for sufficient airflow. Check the air filter for dirt. Check
for blocked return-air or supply-air grilles. Be sure they are open
and unobstructed. If these checks do not reveal the cause, call your
servicing dealer.
If your unit is not operating at all, check the following list for
easy solutions:
( ) Check to be sure that your thermostat temperature selector is set
below the indoor temperature during the cooling season or above
the indoor temperature during heating season. Be sure the SYS-
TEM switch or MODE control is in the COOL or HEAT position
and not in the OFF position.
( ) If your unit still fails to operate, call your servicing dealer for
troubleshooting and repairs. Specify the model and serial numbers
of your unit. (Record them in this manual in the space provided.)
If the dealer knows exactly which unit you have, he may be able
to offer suggestions over the phone, or save valuable time through
knowledgeable preparation for the service call.
IN CASE OF TROUBLE
If you perform the steps above and unit performance is still
unsatisfactory, shut off the unit and call your dealer.
Dealer’s Name ______________________________________
Telephone___________________________________________
UnitModel__________________________________________
UnitSerialNumber___________________________________
3
Date of Installation ___________________________________
Copyright 2001 CARRIER Corp. • 7310 W. Morris St. • Indianapolis, IN 46231 om50-30
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
PC 101 Catalog No. 005–00001 Printed in U.S.A. Form OM50-30 Pg 4 12–01 Replaces: New

Other manuals for 50JS

3

Other Carrier Heat Pump manuals

Carrier 25HNB5 User manual

Carrier

Carrier 25HNB5 User manual

Carrier Aquazone 50PCH007 Dimensions and installation guide

Carrier

Carrier Aquazone 50PCH007 Dimensions and installation guide

Carrier CPHEATER001A00 User manual

Carrier

Carrier CPHEATER001A00 User manual

Carrier 50YDV Manual

Carrier

Carrier 50YDV Manual

Carrier 50ZHK Instruction Manual

Carrier

Carrier 50ZHK Instruction Manual

Carrier 50JZ 024-060 Assembly Instructions

Carrier

Carrier 50JZ 024-060 Assembly Instructions

Carrier 38EYA Operation manual

Carrier

Carrier 38EYA Operation manual

Carrier 19PV550 Manual

Carrier

Carrier 19PV550 Manual

Carrier Comfort 48VT Instruction Manual

Carrier

Carrier Comfort 48VT Instruction Manual

Carrier 50WQ Dimensions and installation guide

Carrier

Carrier 50WQ Dimensions and installation guide

Carrier 50JZ024 Dimensions and installation guide

Carrier

Carrier 50JZ024 Dimensions and installation guide

Carrier 50QEH Dimensions and installation guide

Carrier

Carrier 50QEH Dimensions and installation guide

Carrier AQUAZONE 50PCH Quick guide

Carrier

Carrier AQUAZONE 50PCH Quick guide

Carrier 38HDV009 Dimensions and installation guide

Carrier

Carrier 38HDV009 Dimensions and installation guide

Carrier 38HDR User manual

Carrier

Carrier 38HDR User manual

Carrier SOPRANO 50 User manual

Carrier

Carrier SOPRANO 50 User manual

Carrier 38MARB User manual

Carrier

Carrier 38MARB User manual

Carrier Deluxe 38YZA Operation manual

Carrier

Carrier Deluxe 38YZA Operation manual

Carrier 50ZHA Guide User manual

Carrier

Carrier 50ZHA Guide User manual

Carrier 38YH Operation manual

Carrier

Carrier 38YH Operation manual

Carrier 38BQ Dimensions and installation guide

Carrier

Carrier 38BQ Dimensions and installation guide

Carrier 38QN Instructions and recipes

Carrier

Carrier 38QN Instructions and recipes

Carrier Infinity 50CR Series User manual

Carrier

Carrier Infinity 50CR Series User manual

Carrier 50PEC09-18 Aquazone Dimensions and installation guide

Carrier

Carrier 50PEC09-18 Aquazone Dimensions and installation guide

Popular Heat Pump manuals by other brands

Ochsner AIR 85 Design and installation manual

Ochsner

Ochsner AIR 85 Design and installation manual

Dimplex WI 140TUR+ Installation and operating insctructions

Dimplex

Dimplex WI 140TUR+ Installation and operating insctructions

Bard WH421 installation instructions

Bard

Bard WH421 installation instructions

Daikin VRVIII Operation manual

Daikin

Daikin VRVIII Operation manual

Genvex Optima 300 user manual

Genvex

Genvex Optima 300 user manual

Daikin Altherma 3 R F Operation manual

Daikin

Daikin Altherma 3 R F Operation manual

Daikin FWXT Series Installation and user manual

Daikin

Daikin FWXT Series Installation and user manual

Trane 4TTB6018A Installer's guide

Trane

Trane 4TTB6018A Installer's guide

Panasonic UX09*E5 Series installation manual

Panasonic

Panasonic UX09*E5 Series installation manual

York PHE6B36 installation manual

York

York PHE6B36 installation manual

AERMEC SWP200 Installation and Maintenance

AERMEC

AERMEC SWP200 Installation and Maintenance

LG THERMA V ZHNW16B0 Engineering product data book

LG

LG THERMA V ZHNW16B0 Engineering product data book

York YLCA user manual

York

York YLCA user manual

Lennox XP15 installation instructions

Lennox

Lennox XP15 installation instructions

emmeti Mirai SMI EH0614DC Installation and use manual

emmeti

emmeti Mirai SMI EH0614DC Installation and use manual

Trane CXAO Installation operation & maintenance

Trane

Trane CXAO Installation operation & maintenance

AHRI RC Series installation manual

AHRI

AHRI RC Series installation manual

Daikin VRV RXYMQ-A Series Service manual

Daikin

Daikin VRV RXYMQ-A Series Service manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.