Cavecool CC34SB User manual

Service Manual for Cavecool
Single zone model#CC34SB&CC62SB&CC102SB
Dual one model#CC29DB&CC54DB&CC102DB
CC34SB CC62SB CC102SB
CC29DB CC54DB CC102DB

The following lists the bar in the course of various failures that may occur,aswellastofindandfix
these faults. Please corresponds fault item and then find the corresponding page number information.
Maintenance Preparing:
○Tools
1.Vise 2.Cross screwdriver 3.goggles 4.Clamp Meter 5. Multimeter
(5A)
5.
Wrench 6.
Electric iron 7.
Strippers 8.Sealing jaws 10. The protective gloves
○ Equipment
1.Vacuum p um p 2.Soldering equipment 3. Pressure gauge / refrigerant metering device

Content
1.Precautions………………………………………………………………4
2.Technical specification………………………………………………5
2.Schematic diagram……………………………………………………6
3. NTC value…………………………………………………………………8
4.Control panel……………………………………………………………10
5.The fault diagnosis……………………………………………………11
6.Disassembly instruction of main components………………17

4
1. Repair work safety precautions (please follow below precautions before maintenance)
DANGER
• Do not use open flames indoor or smoke during reqairing.
• Do not perform welding in poorly ventilated and confined areas
• Do not have children nearby when reparing
WA R N I N G
•Always unplug the power cord first before carrying out maintenance
Otherwise, it may result in electric shock and injuries.
•Please be careful not to get electric shock during reparing.
Unplug the power cord before maintenance. If needs to check the circuit while the
power is on,do not touch the live electrical parts! If electric wires are damaged, it
must be replaced by qualified technician in time.
• Use original parts which shown in the part list, do not use parts from other models
or other brands, never modify the parts
• Use appropriate maintenance tools, improper use of tools may cause insecure
assembly
• If wires are cut during maintenance. Remember to reconnect the wire and seal with
insulating tape
•When discharging the refrigerant, make sure the room is in good ventilation
condition.
•When cutting off the compressor pipes, pay attention to the remaining refrigerant
and internal pressure.
• After maintenance finished, use multimeter to check the insulation, makesurethe
insulation resistance is over 2 MΩ before connecting to power.
•After repair, it is necessary to check whether the grounding is in good condition

5
NOTICE
Be careful to the high temperature of compressor and refrigeration pipes when
product is on or just after the production was power off.
Be careful to the high temperature after soldering
Be careful not to let liquid refrigerant directly touches the skin,it may cause
frostbit
Metal parts and plastic parts burr may scratch the hand.
1.
Technical specification
Single zone model
Model no. CC34SB CC62SB CC102SB
Product type
Single zone compressor
wine cooler
Single zone compressor
wine cooler
Single zone compressor
wine cooler
Installation Type Free standing only Free standing only Free standing only
Gross / Net Volume 91L / 89L 152L / 148L 247L / 242L
Bottle Loading Capacity 34 bordeaux bottles 62 bordeaux bottles 121 bordeaux bottles
Voltage
&Frequency
220‐240V / 50Hz 220‐240V / 50Hz 220‐240V / 50Hz
Power 90W 90W 100W
Set temperature 5℃~20℃5℃~20℃5℃~20℃
Gas refrigerant R600a R600a R600a
Weight of gas 25g 30g 38g
Defrosting type Auto defrost Auto defrost Auto defrost
Climate class SN/N/ST SN/N/ST/T SN/N/ST/T
Product dimension
(W*D*H ) 480×430×508 480×565×850 550×565×1277

6
Dual zone model:
2.
Schematic diagram
2.1.Single zone model
Model no. CC29DB CC54DB CC102DB
Product name
Dual zone compressor
wine cooler
Dual zone compressor
wine cooler
Dual zone compressor
wine cooler
Installation Type Free standing only Free standing only Free standing only
Gross / Net Volume 85L / 80L 142L / 138L 240L / 232L
Bottle Loading Capacity 34 bordeaux bottles 62 bordeaux bottles 102 bordeaux bottles
Voltage
&Frequency
220‐240V / 50Hz 220‐240V / 50Hz 220‐240V / 50Hz
Power 90W 90W 100W
Temperature
Setting
Upper: 5℃~12℃
Lower:12℃~18℃
Upper: 5℃~12℃
Lower:12℃~18℃
Upper: 5℃~12℃
Lower:12℃~18℃
Gas refrigerant R600a R600a R600a
Weight of gas 22g 22g 22g
Defrosting type Auto defrost Auto defrost Auto defrost
Climate class N/ST SN/N/ST SN/N/ST
Product dimension
(W*D*H ) 480×430×508 480×565×850 550×565×1277

7
2.2 Dual zone model
、
3. Cooling system schematic diagram:
3.Cooling system schematic diagram:
2.3 Cooling system schematic diagram:

8
3.NTC value

9
4.Structure diagram
4.1 Single zone model
4.2 Dual zone model
1Fan
2Control panel and LED light
3Shelf
4Feet
5Lower hinge
6Door
7Gasket
8Upper hinge
1Fan
2LED light
3Shelf
4Control panel
5Feet
6Lower hinge
7Door
8Gasket
9Upper hinge

10
5.Control Panel
5.1 Single zone model
13
24
Temperature range is 5‐20°C.
‐ 1. Press ON/OFF button to turn on the appliance, and press ON/OFF for 3 seconds to turn off the appliance.
‐ 2. Press LIGHT button to turn on or turn off the light
‐3.Press UP button to increase the setting temepreture
‐4.Press down button to decrease the setting temepreture
Press temperature control button “UP” and “DOWN” together for 3 seconds to change the LED display from
Celsius to Fahrenheit
Important note: After selecting the desired temperature, the display will continue to show the real
temperature inside the equipment, which will vary gradually until it reaches the selected temperature.
5.2 Dual zone model
Temperature range for upper zone is 5‐12°Candforlowerzone
is
12‐18°C.
-Press power switch button for 3 seconds to turn on or turn off the appliance
-Press light button to turn on or turn off the light in both zones

11
-Press lower zone temperature contol button and together for 3 seconds to change the LED
display from Celsius to Fahrenheit.
-You can set the desired temperature by pressing or of each zone
The temperature selected will increase/decrease by 1°C with each press of the buttons.
Notice: Important note: after selecting the desired temperature, the display will continue to show the real
temperature inside the equipment, which will vary gradually until it reaches the selected temperature.
6.The fault diagnosis
6.1 List of self-diagnostic code (Single Zone)
6.2 List of self-diagnostic code(Dual Zone)
Code Content Description Processing opinion
E1 Temperature sensor
short-circuit fault
Check the wire connection of the temperature
sensor socket and connection to the main PCB
For short-circuit,to replace a new
part.
For open circuit,check the
connection and re-connect that
part
L1 Temperature sensor
open-circuit fault
Check the wire connection of the temperature
senso
r
socket and connection to the main PCB
HOO High temperature
alrm
When inside temperature is higher than 25°C
and over 6 hours,it will display “HOO” and
compressor stop working
Check below 5.3 Handling of
common problems and 5.4
Diagnosis of problems
LOO Low temperature
alrm
When inside temperature is lower than 2 °C
and over 6 hours,it will display “LOO” and
compressor stop working
Code Content Description Processing opinion
E1 Temperature sensor
short-circuit fault
Check the wire connection of the temperature
sensor socket and connection to the main PCB For short-circuit,to replace a new
part.
For open circuit,check the
connection and re-connect that
part
L1 Temperature sensor
open-circuit fault
Check the wire connection of the temperature
senso
r
socket and connection to the main PCB
F1 Upper zone
faninopencircuit
Check the connection of the upper fan socket
and connection to the PCB
F2 Lower zone
faninopencircuit
Check the connection of the lower fan socket
and connection to the PCB
HOO High temperature
alrm
When inside temperature is higher than 25°C
and over 6 hours,it will display “HOO” and
compressor stop working
Check below 5.3 Handling of
common problems and 5.4
Diagnosis of problems
LOO Low temperature
alrm
When inside temperature is lower than 2 °C
and over 6 hours,it will display “LOO” and
compressor stop working

13
6.3 Handling of common problems
PROBLEM POSSIBLE CAUSES
Appliance is not cooling Appliance is not plugged in
Appliance is not turned on
Check if voltage of the installation
Check the circuit breaker or if fuse has blown
Appliance is not cold
enough Check the temperature control setting
Check if ambient temperature is beyond appliance operating temperature
The door is opened too frequently
The door is not closed properly
The door is not sealing properly
Check if wine cooler is exposed to sunlight or there has a heat source nearby
Insufficient free space around the appliance
Check if too many wine bottles have block the air ventilation hole
The compressor starts
and stops frequently The external temperature is high.
A large quantity of bottles has been put into the cellar.
The appliance is opened frequently.
The door is not properly closed.
The cellar has not been correctly set.
LED lights do not operate The appliance is not plugged in
The fuse has blown
LED lights are not broken
The light switch is off
Vibration Check and ensure that the appliance is leve
l
The appliance makes a
lot of noise A noise resembling circulating water is produced by the coolant gas and this
is normal.
At the end of a cooling cycle, you can hear the noise of water circulating.
Expansion and contraction of the internal walls may cause a cracking sound.
The appliance is not level
Check if fan is in good condition
The door does not close
properly The appliance is not level.
The door seal is dirty or damaged.
The shelves are not positioned correctly.
A part of the contents is preventing the door from closing.
LED display is not
working properly Controlpanelfailed
Power PCB has broken
The appliance is not plugged in
The probe is not working
Condensed water on the
door glass It’s normal when ambient temperature is too high or ambient humidity is too
high.

14
Check the main power is on and display
works or not?
6.4 Diagnosis of problems
●Screen not display
Y
Y
Is there a display window of the
product?
The simple way (check the power
supply)
Test the power (power cord, plugs,
sockets)
Check the display board to see if
there is input voltage?
Check the control board and display
board
Display board Broken
N
●Compressor doesn’t work
YN
Is setting temperature lower
than ambient temperature?
YN
Defrost or not Check the connectors in the power
PCB box if it is well‐connected
NY
Cut the power,measure the
Re‐set the
temperature
Does compressor work after
replace the compressor
protector?
Nimpedance of the compressor Y
protector if is <1Ω
(at room temperature)
Y
N
Measure the impedance of
compressor to check if
it can meet the corresponding
impedance standard
Y
N
Connect the power, measure whether
the compressor output terminals P1,
P2 on the main PCB have 220V output
to the compressor
N
Replace the main PCB
Replace the compres
N
Re
p
lace PTC starte
r
Re
p
lace com
p
resso
r

15
●Not cooling or not cooling enough:
Compressor work or not? NRefer to above situation A
Y
Y
Setting temperature is
higher than ambient temp.?
Lower down the setting
temperature
N
N
Refrigerant gas leak
or not?
Checking the cooling parts if is
blocked?(pipe of evaporator
and condenser)
Y
re‐welding and refill the
Refrigerant gas

16
●Over cooling
Setting temperature is
too low?
Y
Turn up the setting
temperature
NAmbient temperature
is too low
N
Y
NTC probe was blocked
by something?
Do not put objects too
close to NTC probe
N
Replace the NTC probe
●.LED light-failure
check the control
panel keys are workable or
not?
N
Replace the
control PCB
YCheck the light wire is
well connected?
Y
Check whether there is Y
DC12V power supply
N
Replace the light components
N
Positive and negative
power supply is reversed?
Y
The connector is loose?
otherwise replace the main
circuit board
Reconnect positive
and negative wire

17
7.Disassembly instruction of main components
Turn off and unplug the appliance before replacing the parts to ensure safety operation
7.1.Control PCB & LED light for single zone
1)Unscrew the two bolts,then take off the control panel box and LED light cover.
2) Pull off the wire connectors and then can replace the control PCB and LED light board
12
7.2.Control PCB & LED light for dual zone model
7.2.1 Control PCB
1)Unscrew the 4 bolts on the control panel box.

18
2)Take off the control panel box and the wire connector,then can replace thenewcontrolPCB
7.2.2 LED light
1)Remove the screws and and take off the light cover,then replace the new LED light board.
Fan&NTC probe
Unscrew the 4 bolts on the
control panel box.

19
7.3.Fan&NTC probe
7.3.1 Single zone
Fan NTC probe

20
7.3.2 Dual zone
Upper zone fan&NTC probe
Remove the fan mask,and then can replace the fan and NTC probe.
NTC probe
FAN NTC probe

21
7.4Lower zone NTC probe
7.5Lower zone fan & LED light
Unscrews and remove upper &front cover of the separation zone
Remove the foam in the separation zone,then can replace the fan and LED light.
Lower zone LED light
LOWER ZONE FAN
LOWER ZONE LED LIGHT
This manual suits for next models
5
Table of contents
Popular Chiller manuals by other brands

Cornelius
Cornelius CH 551 Operator's & installation manual

Marrone & Co
Marrone & Co Cold Shot Chillers ACWC-060-EM-DR-LT-M20-5 Installation, operation and maintenance instructions

USA Lab
USA Lab UHC-7/20 manual

Carrier
Carrier AquaSnap 30MPA050 installation instructions

Emerson
Emerson Fluid Chiller user manual

Lennox
Lennox ECOLEAN EAC Series Installation, operating and maintenance