CH550 and CH551 Chiller Operator’s & Installation Manual
© 2002-2010, IMI Cornelius Inc. - 3 - Publication Number: 91272
Standard Thermostat Eliwell IC902
The following procedure should be followed to adjust the Eliwell IC902 thremostat termperature setting:
1. To set the SET POINT, press and release the SET button. SET displays.
2. Press the SET button again, the current SET POINT is displayed. Press the UP or DOWN button to
change the SET POINT to the desired temperature.
3. Pres the fnc button twice to exit the program. The current liquid temperature is displayed.
The thermostat has a range that is pre-set at the factory. The range is 40° F (5° C) to 100° F (38° C). If operation
outside of this range is required, please contact the Cornelius Technical Service Department.
When the flow rate to the process is critical, a flow meter and valve should be installed in the line in order to
obtain the proper flow rate. On Units with optional bypass valve, the aforementioned valve can be omitted and the
flow can be adjusted with this valve. Turning the valve clockwise increases the flow to the process whereas
turning the valve counterclockwise decrease the flow to the process.
Once these start–up procedures are complete, the chiller is ready for standard operation.
NOTE:
1. Never operate the chiller with enclosure panels removed.
2. Always use the illuminated switch to turn off the chiller when it is not being used.
3. Always ensure that all air inlets and outlets are free of obstructions.
MAINTENANCE
The chiller requires very little normal maintenance. The condenser fins should be cleaned by blowing
compressed air through the condenser. from the fan side as required to prevent blockage of air flow by dirt and
debris that may accumulate over time. The positive displacement pump motor should be lubricated with thirty
drops of SAE 20 oil once each year. The circulation system should be drained and flushed periodically to avoid
build up and possible restriction of flow contaminants. Following these simple procedures will ensure many
trouble free hours of chiller operation.
SERVICE
Service of the chiller is limited to replacing the switch, the thermostat, the fan motor, and the pump. Charging and
other refrigeration problems must be performed by a qualified refrigeration technician.
Removing Wrapper
1. Disconnect electrical power from the unit.
2. Remove the seven screws from each side of the wrapper and the two screws that secure the
wrapper to the front and back panels. Retain all hardware and lift the wrapper off the unit.
Replacing Swtich
1. Remove the wrapper, as described in Removing Wrapper.
2. Remove the spade lugs from the existing switch and note connection points.
3. Remove the switch from the front panel.
4. Install the new switch in the front panel and connect the leads to the new switch.
5. Install the wrapper.
WARNING: Disconnect electrical power to the chiller to prevent personal injury before
attempting the following maintenance procedures.