
7800 Neutralizer Installation & Startup Guide
Page 10 www.cleanwaterstore.com Rev 120215
7800 Neutralizer up to 4 feet above the top of the tank. If the drain line will be more than 20
feet, use larger diameter tubing such as ¾” or 1”. Note that it is desirable to be able to run the
drain line into a bucket in order to test the backwash flow rate in the future. This is why hard
piping the drain line is discouraged: however, if you do use hard PVC piping for the drain line,
and you are able to remove the hard PVC drain piping and attach flexible tubing should you ever
desire for testing purposes, it is OK to use rigid PVC pipe for the drain. Make sure the drain
tubing is firmly clamped to the barbed fitting with a hose clamp to prevent leaks.
15. Plug your 7800 control valve into an outlet. After being plugged in, the screen may display
“WAITING PLEASE” while it finds the service position. By default, the control valve will be set to
work like a Water Softener, but that’s not correct for this application. So, next you will need to
program the system to work as a Neutralizer Filter. There are a few settings that must be
changed before the system can be put into service.
Initial Programming
1. Plug in your 7800 control valve to an outlet
2. From the display screen, press and hold the settings button for three seconds to access the
programming menu.
3. Set Time of Day –Use the up and down arrows to select the proper value. Once the proper
value is set, press the Settings button (Enter) to proceed to the next setting. Hitting the Manual
Regen button at any time will take you out of the programming and back to the main menu
4. Set Year - Use the up and down arrows to select the proper value. Once the proper value is set,
press the Settings button (Enter) to proceed to the next setting
5. Set Month - Use the up and down arrows to select the proper value. Once the proper value is
set, press the Settings button (Enter) to proceed to the next setting
6. Set Day - Use the up and down arrows to select the proper value. Once the proper value is set,
press the Settings button (Enter) to proceed to the next setting
7. Set Regen Days - This tells the Neutralizer filter how often to regenerate in days. It can be set for
any setting from 1 to 10, with 7 being the recommended common setting.
8. Gallons On/Off –Select Off to program it to be used as a neutralizer filter
9. Regen Time - Set the time of the night that you want the neutralizer filter to backwash. The
default time is 2:00 am. Adjust the time by pushing the up or down arrow if you want.
10. Programming Complete –If you need to go back and change anything, simply press and hold
the Settings button to go through the programming menu again.