INSTRUCTION MANUAL PA 28 AND PA 45 PACKAGED UNIT
Page 12
10. Failure cascading
Input point of failure cascading, in order to detect external alarm signal, such as re and so on.
FAILURE INPUT AND PROTECTION ALARMING
FAILURE LIST
All ports are normally closed according system set, if the port makes a loop with COM(Public port) of the relevant
socket, it means ok; or it means failure. If you need to shield this switch input fault, only need to short of jumpers of
the corresponding failure ports. System will display the error code when error happen. (*means the parameter can
be set).
Failure Condition Delay Duration Corresponding
action Reset Remark
Supply fan error
Blower overload Any time 0 sec 2 sec Shut o unit Manual
If error exist before unit turn on,
fail to turn on, alarm alarming
and display error;
HP protection Any time 0 sec 2 sec Shut o corresponding
comp Manual
If error exist before unit turn on,
fail to start comp, alarming and
display error;
LP protection When comp
start *120 sec 2 sec Shut o corresponding
comp Manual Delay check after comp turn on,
alarming and display error;
Condenser Fan
overload Any time 0 sec 2 sec Shut o all comp Manual
If error exist before unit turn on,
fail to start comp, alarming and
display error;
Supply T.High When system
start 0 sec 2 sec Shut o all E-heater Auto
Check when heating, if temp
di between inlet and outlet is
3ºC, reset
Supply T.low When system
start 0 sec 2 sec Shut o all comp Auto
Check when cooling, if temp
di between inlet and outlet is
3ºC, reset, comp restart 10 min
delay.
Insu heat When start
heating 0 sec 10 min Shut o unit Auto /
Manual
Check when heating,keep the
set temp of supply air for 10
min, protect turn o, reset if
temp di between inlet and
outlet, or manual recovery.
Return T. sensor Any time 0 sec 2 sec Shut o unit Auto After reset
Supply T. sensor Any time 0 sec 2 sec Alarming Auto No action
Ambient T.
sensor Any time 0 sec 2 sec Alarming Auto
If error happen, not considering
temp di when defrost, not
considering start logic when
heating;
Fin sensor Any time 0 sec 2 sec
Alarming, condenser
fan turn to compressor
link control
Auto