coastTec 750 User manual

c o a s t T e c _ O T Q G _ S U T 1 _ 2 0 1 8 0 8 1 7 V 1 . 0 Page 1
Operation & Troubleshooting Quick Guide
Smart-UPS Rack (VA): 750, 1000, 1500, 2000, 2200, 3000, 5000
Figure 1
Figure 2
Figure 3
Connect the UPS’s Internal Batteries (Figure 1):
NOTE: The Battery Connector may vary depending
on the UPS model, Figure 1 illustrates a couple
variations. Please follow the illustration which best
resembles your UPS.
Procedure 1 (top diagram – SUA/SMX):
1.1 Remove the front bezel by pulling it away from the UPS. The
fastening clips will automatically disengage ❶
1.2 Connect the battery by pressing the Anderson connector into the
plug located on the UPS. A snapwill be felt as the connector
engages the jack.
1.3 Some models will require loosening thumb-screw/s and opening
the metal battery door to access the battery connector ❷
Specific to SMX750 models:
Remove the battery pack, and reinsert
with the electrical connector pins facing inwards.
1.4 Close the metal battery door (replace the screws) and reinstall the
front bezel. OR
Procedure 2 (bottom diagram – SUA3000/5000):
1.1 Remove the front bezel by pulling it away from the UPS. The
fastening clips will automatically disengage ❸
1.2 Connect the battery by pressing the Anderson connector into the
plug at the top of the battery compartment.
A snap will be felt as the connector engages the jack ❹
1.3 Reinstall the front bezel.
Install UPS accessories (Figure 2):
NOTE: Ensure the UPS is turned off prior to
installing any additional accessories. Please
contact APC or coastTec for more information
on compatible parts.
2.1 Install SmartSlot accessory (if applicable) ❶
2.2 Install Step-down transformer (if applicable).
2.3 Install all external Battery Packs (if applicable). The External
Battery Pack connector is located on the rear panel of the UPS,
and is either BLACK (120V), BLUE (48V) or GREY (24V).
If the Connector is obstructed by a metal cover, remove the
fastening screws and cover ❷
Connect wiring & charge UPS (Figure 3):
NOTE: Ensure equipment is turned off.
3.1 Connect equipment to the UPS
(computer, network switches etc.) ❶
3.2 Connect the UPS’s Power Cord to a suitable
power receptacle ❷
3.3 Set UPS circuit breakers to the ‘ON’ position (if applicable) ❸
3.4 Turn on the UPS by pressing the power button:
or
3.5 Wait for the UPS’s Self-Test to complete, then power-up any
equipment.
3.6 Allow UPS to charge batteries for 24 hours prior to operating on
battery or performing additional Self-Test or Calibration tests.
STEP 1:
STEP 2:
STEP 3:
❶
❸
❹
❷
❶
❷
OR
❶
❸
❷

c o a s t T e c _ O T Q G _ S U T 1 _ 2 0 1 8 0 8 1 7 V 1 . 0 Page 2
UPS Front Panel (Figure 4):
NOTE: Symbols & functions may differ on some UPS models.
Figure 4 illustrates some of the variations in displays.
Please use the illustration which best resembles your UPS.
Figure 4
❶
POWER ‘ON’ BUTTON - Button to turn
the UPS on. If UPS on and connected to
utility power, press and hold to self-test. ❿
AVR BOOST- UPS is compensating for a low
utility input voltage.
❷
POWER ‘OFF’ BUTTON - Button to turn
the UPS off. ⓫
AVR TRIM - UPS is compensating for a high utility
input voltage.
❸
POWER ‘ON/OFF’ BUTTON - Button to
turn the UPS on or off. ⓬
OVERLOAD - The power demand from the load
(connected equipment) has exceeded the
capacity of the UPS. A sustained alarm tone is
also emitted.
❹
ESCAPE BUTTON - Button to exit a sub-
menu. ⓭
LOAD CAPACITY - The load is indicated by the
number of sections illuminated, one to five. Each
bar represents 20% of the load.
❺
ENTER BUTTON - Button to confirm a
selection on the menu. ⓮
BATTERY CHARGE - The battery charge level is
indicated by the number of sections illuminated.
When all five blocks are illuminated, the UPS is at
full charge.
❻
UP/DOWN BUTTONS – Buttons to scroll
though menu options. ⓯
SYSTEM FAULTS - The system has a fault. For
some models, a fault number will appear on the
display interface. See “UPS Troubleshooting” on
page 3
❼
ONLINE - UPS is supplying utility power
to the connected equipment. If not lit, the
UPS is either supplying battery power or
not turned ON. ⓰
DISPLAY SCREEN – Displays important
information about the UPS and connected
equipment.
❽
ON BATTERY - UPS is supplying battery
backup power to the connected
equipment. UPS will beep four times
every 30 seconds.
❾
REPLACE BATTERY - UPS has failed a self-test, or the battery is bad. UPS will also produce short beeps
for a minute.
BATTERY DISCONNECTED - Flashes to indicate the battery is disconnected. UPS will beep every two
seconds.
UPS Back Panel (Figure 5):
NOTE: Layout may differ on some models.
❶USB port
❷UPS monitoring port (RJ45 connector)
❸Serial Port (DB-9 connector)
❹TVSS GND (Chassis ground connection screw)
❺SmartSlot for optional NMC accessory card
❻Circuit breaker/Overload protection
❼UPS Power Cord
❽Power Outlets
❾EPO connector (Emergency Power Off)
❿Battery Connector / Battery Disconnect
Figure 5
❹
❷
❶
❺
❻
❾
❻
❷
⓭
❿
⓫
❼
❶
❽
⓬
❾
⓮
❷
❸
❽
⓯
❾
❼
⓰
❹
❺
❻
❺
❼
❽
❾
❸
❼
❽
❽
❽
❿
❿
❹
c o a s t T e c _ O T Q G _ S U T 1 _ 2 0 1 8 0 8 1 7 V 1 . 0 Page 3
UPS Troubleshooting:
NOTE: Troubleshooting procedures may differ depending on UPS model.
UPS will not turn on
Power/Test button not pushed. Press the Power/Test button once to power the UPS and the load.
UPS not connected to AC power supply. Check that the power cable from the UPS to the wall outlet is securely
connected.
UPS input circuit breaker tripped. Reduce the load on the UPS by unplugging equipment. If available, reset
the circuit breaker (on back of UPS): for the plunger-type, press the
plunger back in. For the toggle-type, flip the switch to the ‘ON’ position.
Very low or no utility voltage. Check the AC power supply to the UPS with a multimeter or table lamp.
If the meter reads a voltage below the UPS’s acceptable operating range,
or the light bulb is dimly lit, have the utility voltage checked.
Battery not connected properly. Confirm the external Battery Connector / Disconnect, or internal
connections. A connectormay appear to be connected, additional
insertion force may be required to firmly seat any loose connections.
UPS will not turn off
Internal UPS fault. Do not attempt to use the UPS. Unplug the UPS and have it serviced
immediately.
UPS operates on
-
battery although normal line voltage exists
UPS’s input circuit breaker tripped. Reduce the load on the UPS by unplugging equipment and reset the
circuit breaker (on the back of UPS): for the plunger-type, press the
plunger back in. For the toggle-type, flip the switch to the ‘ON’ position.
Very high, low, or distorted utility line voltage.
Generator sets with poor line regulation.
Move the UPS to a different outlet on a different circuit. Test the input
voltage with the utility voltage display. If acceptable to the load, reduce
the UPS’s sensitivity. See User’s Manual for procedures.
UPS beeps occasionally
Normal UPS operation. None. The UPS is protecting the load.
UPS does not provide expected backup time
The UPS’s battery is weak due to a recent
outage or is near the end of its service life.
Allow the UPS time to charge the battery, batteries require recharging
after extended outages. Also, batteries wear faster when put into service
often or when operated at elevated temperatures. If the battery is near the
end of its service life, consider replacing the battery even if the ‘replace
battery’ indicator is not yet lit.
The UPS is overloaded. Check the UPS’s load display. Unplug less needed equipment, such as
printers or reconsider the sizing requirements of the setup – a larger VA
capable UPS might be required.
Front panel indicators flash sequentially
The UPS has been shut down by remote control. None. The UPS will restart automatically when utility power returns.
All indicators are lit
(or Fault LED & message)
and UPS emits a constant beeping
sound
Internal UPS fault. Do not attempt to use the UPS. Turn the UPS off and have it serviced
immediately.
All indicators are off and UPS is plugged into wall outlet
The UPS is shut down and the batteries are
discharged from an extended outage. None. The UPS will return to normal operation when the power is
restored and the battery has a sufficient charge.
The replace battery light is lit
Weak batteries. Perform an additional self-test to see if the warning clears.
Replacement batteries not connected properly. Confirm the battery connections.
The display has a Site Warning Fault message
Wiring faults detected includemissing ground,
hot-neutral (polarity reversal), and overload
neutral circuit.
If the UPS indicates a site wiring fault, have a qualified electrician inspect
the building wiring.
For the complete User Manual or comprehensive troubleshooting, please visit the following websites:
APC: http://www.apc.com or coastTec: http://www.coasttec.com
Problem:
Solution:
This manual suits for next models
6