Columbia Lighting BLD-RM30 Series User manual

CRN2 EM Battery Instruction Manual
EMERGENCY LED DRIVER
30W/40W/60W
currentlighting.com/columbialighting
© 2022 HLI Solutions, Inc. All rights reserved. Information and specifications subject to change
without notice. All values are design or typical values when measured under laboratory conditions.
Page 1 of 5
Rev 01/06/23
COL_CRN2_LSCS EM Batery_inst_R01
CAUTION RISK OF SHOCKDisconnect emergency and normal input power sources before servicing.
Assembly and Field Installation Wiring: Warning AC power must be o before proceeding with assembly or installation of emergency driver.
IMPORTANT: An unswitched AC power source is required (100-347 VAC, 50/60 Hz).
This device is designed for fixtures listed for dry, damp or wet locations.
IMPORTANT: Customers are advised to charge emergency LED driver 24 hours every 6 months during storage
IMPORTANT: For BLD-RM30X-YYY suggested to use for LED lamp less than 200W(when diming to minimum.
The power needs to be less than 25W).
For BLD-RM40X-YYY suggested to use for LED lamp less than 300W (when dimming to minimum the power needs to be less than 35W)
IMPORTANT: Make sure all connections are in accordance with the National Electrical Code or Canadian Electrical Code and any local regulations.
CAUTION: To reduce the risk of electric shock disconnect both normal and emergency sources within this unit before servicing any equipment
connected to this unit.
CAUTION: Do not mount near gas or electric heaters
CAUTION: Equipment should be mounted in locations and at heights where it will not be subjected to tampering by unauthorized personnel.
CAUTION: The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
CAUTION: Do not use this equipment for other than its intended use
CAUTION: Use with grounded, UL Listed, dry or damp location rated fixtures. Case should also be grounded.
CAUTION: This product is for use in indoor fixtures only. Do NOT use near heated air handling outlets or hazardous locations
CAUTION: Battery is rechargeable Li-ion type and must be recycled or disposed of properly.
Do not use this emergency driver with accessory equipment other than recommended by the manufacturer.
Failure to follow this may cuase an unsafe condition and will void warranty.
Servicing of this equipment should be performed by qualified personnel only.
IMPORTANT: Illuminated Indicator (LED light) means battery is in charge mode when AC power is applied. It is recommended and required by
applicable code to test emergency function to ensure proper operation of the system; press the remote controller ON button every 30 days to
ensure the emergency driver is functioning and LED light source is illuminated. Conduct a ninety minute (90) discharge test one time (1) per year;
LED light source should be illuminated for a minimum of ninety minutes (90).
TESTING SYSTEM: The emergency battery requires a minimum charge of one (1) hour before testing the circuit.
A full charge requires twenty four (24) hours.
FEATURES
• Simple wiring: directly connect to LED driver AC input
• Constant power output 30W/40W/60W
• Universal input range, 100-347VAC, 50/60HZ
• High output voltage DC 170V
• Optimized design for UFO highbay, private mold patent design
• Built-in integrated junction box
• Protection: over-voltage, short circuit, over-load, open-circuit
• Wireless remote control or non-remote control for emergency test
are optional
• UL Listed for field factory installation
• Comply with UL924 standard and CSA 22.2, No. 141 for USA and
Canada.
• California Energy Commission (CEC) Title 20 with BC compliant
IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should always be followed including the following.
PLEASE READ AND FOLLOW ALL SAFETY INSTRUCTIONS
Li- ion
THIS PRODUCT CONTAINS A RECHARGEABLE LITHIUM BATTERY.
THE BATTERY MUST BE RECYCLED OR DISPOSED OFF
PROPERLY.
E493915
Model NO.
Model Number Input Voltage Emergency Power Emergency Time
BLD-RM30XY-YY 100-347VAC 30 90 Minutes
BLD-RM40XY-YY 100-347VAC 40 90 Minutes
BLD-RM60XY-YY 100-347VAC 60 90 Minutes
Specifications
Input Voltage 100-347VAC 50/60 Hz Test switch/charging
indicator light
Remote Control
Non-Remote Control
Output Voltage 170V DC Battery Li-ion battery
Input Current ≥ 200mA Charging Time ≥ 24 hours
Input Power 15W Output Power 30W 40W 60W
Emergency Time 90 minutes
Warranty 5 Years Weight 3.3 kg
Ambient Temp. 5°C-50°C Dimensions 273.26 x 142.3mm

CRN2
WET LOCATION HIGH BAY
CRN2 Remote Instruction Manual
currentlighting.com/columbialighting
© 2022 HLI Solutions, Inc. All rights reserved. Information and specifications subject to change
without notice. All values are design or typical values when measured under laboratory conditions.
Page 2 of 5
Rev 01/06/23
COL_CRN2_LSCS EM Batery_inst_R01
For UFO LED Highbay ≤300W and has 0-10V dimming
For UFO LED Highbay ≤300W and has 0-10V dimming
With Dimmer
With Wall Switch (Without Dimmer)
WIRING DIAGRAMS
1
2
IMPORTANT
Dimming wires must be connected to UFO LED Driver
dimming wires for EM to function properly.
WILL NOT operate if not connected
RECOMMENDATION
Emergency output power ≥ 20% Output power of UFO LED High Bay
IMPORTANT
Dimming wires must be connected to UFO LED Driver
dimming wires for EM to function properly.
WILL NOT operate if not connected
RECOMMENDATION
Emergency output power ≥ 20% Output power of UFO LED High Bay

CRN2
WET LOCATION HIGH BAY
CRN2 Remote Instruction Manual
currentlighting.com/columbialighting
© 2022 HLI Solutions, Inc. All rights reserved. Information and specifications subject to change
without notice. All values are design or typical values when measured under laboratory conditions.
Page 3 of 5
Rev 01/06/23
COL_CRN2_LSCS EM Batery_inst_R01
For UFO LED Highbay ≤ 300W and has 0-10V dimming
For UFO LED Highbay ≤ 300W and has 0-10V dimming
Without Wall Switch & Dimmer, 24 hour lighting
With Sensor (100-277/347VAC)
WIRING DIAGRAMS
3
4
IMPORTANT
Dimming wires must be connected to UFO LED Driver
dimming wires for EM to function properly.
WILL NOT operate if not connected
RECOMMENDATION
Emergency output power ≥ 20% Output power of UFO LED High Bay
IMPORTANT
Dimming wires must be connected to UFO LED Driver
dimming wires for EM to function properly.
WILL NOT operate if not connected
RECOMMENDATION
Emergency output power ≥ 20% Output power of UFO LED High Bay

CRN2
WET LOCATION HIGH BAY
CRN2 Remote Instruction Manual
currentlighting.com/columbialighting
© 2022 HLI Solutions, Inc. All rights reserved. Information and specifications subject to change
without notice. All values are design or typical values when measured under laboratory conditions.
Page 4 of 5
Rev 01/06/23
COL_CRN2_LSCS EM Batery_inst_R01
WIRING DIAGRAMS
For UFO LED Highbay ≤ 300W and has 0-10V dimming
With 12VDC Sensor
5
IMPORTANT
Dimming wires must be connected to UFO LED Driver
dimming wires for EM to function properly.
WILL NOT operate if not connected
RECOMMENDATION
Emergency output power ≥ 20% Output power of UFO LED High Bay
INSTALLATION
Step 1
Disconnect all power sources to the lighting fixture and ensure they are locked out during installation and maintenance
The LED driver must be sourced from the LED emergency driver.
Select a suitable location on the ceiling with hangable device.
Step 2
(A): Install the ring bolt to the top thread hole of LED emergency driver and fix it with a screw.
(B1): Install the G-hook/ring bolt/m-10-rod/m 12-rod to the bottom thread hold of LED emergency driver and fix it with a
screw.
(B2): Install the Rod to the bottom thread hole of LED emergency driver and fix it with a screw.
(C): Install the LED emergency driver to UFO highbay fixture with a screw.
Open the LED emergency cover and remove the plastic covers and install the waterproof connectors.
Step 3
Pull all wires through the waterproof connectors into the cavity of the emergency driver
(A): Connect the AC output wires (Brown, Blue and Green) of emergency driver with AC input wires of LED lighting fixture
(B): Connect the dimming output wires (Purple and Pink) of emergency driver with the dimming input wires of LED Driver.
(C): Connect AC input wires (Black, White and Red) of the emergency driver with AC main power cord.
(D): Connect the inpu dimming wires (Purple, Grey) of emergency driver with dimming wires from dimmer.
Make sure all connections are with orange wirign caps in accordance with manufacture's installation manual.
Lock up the cover of the junction box.

CRN2
WET LOCATION HIGH BAY
CRN2 Remote Instruction Manual
currentlighting.com/columbialighting
© 2022 HLI Solutions, Inc. All rights reserved. Information and specifications subject to change
without notice. All values are design or typical values when measured under laboratory conditions.
Page 5 of 5
Rev 01/06/23
COL_CRN2_LSCS EM Batery_inst_R01
MOUNTING DIAGRAMS
INSTRUCTIONS FOR REMOTE CONTROL
DIMENSIONS
G-hook Ring Bolt M10-Rod M12-Rod
Hollow Pole Hollow Pole
Ring Bolt
Rings
Type A Pole Mount
See instruction manual for typical installation and select appropriate mounting method.
Press the ON button to test emergency function. This light will switch to its emergency lighting mode and the
indicator will turn o.
Press the OFF button, the light will revert to normal lighting mode.
When main power supply is o (emergency mode), press the o button to turn o the emergency function.
Type B Pole Mount Type C Ring Mount
Test Switch & Indicator
RED ON: Charging mode
RED OFF: Discharging mode
Note: remote controller must be pointed at the indicator light and be
within 45° angle to receive signal.
Remote controller needs two AAA batteries to operate (not included)
273.26mm
This manual suits for next models
2