manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Cyberstat
  6. •
  7. Thermostat
  8. •
  9. Cyberstat CY1201 User manual

Cyberstat CY1201 User manual

Motison
CyberStat® CY1201
Due to continuous improvement, some features and appearance may have changed
User’s Manual
2-year limited warranty: Motison warrants this product to be free
from defects in the workmanship, construction and materials, under nor-
mal use and service, for a period of two year from the date of purchase
by the consumer. If at any time during the warranty period the product
is determined to be defective, Motison will replace or repair it.
This warranty does not cover removal or re-installation costs. This war-
ranty shall not apply if it is shown by Motison that the defect or malfunc-
tion was caused by damage which occurred while the product was in
the possession of a consumer.
Motison's sole responsibility shall be to repair or replace the product
within the terms stated above. Motison shall not be liable for any loss or
damage of any kind, including any incidental or consequential damages
resulting, directly or indirectly, from any breach of any warranty, ex-
press or implied, or any failure of this product. Some states do not allow
the exclusion or limitation of incidental or consequential damages, so
this limitation may not apply to you.
If the product is defective, please contact Motison immediately. To
make a claim, email to support@motison.com
Warranty
2
 Internet connected through 2.4 GHz Wi-Fi (WEP/WPA/WPA2)
 Monitor and control from anywhere anytime
 Three independent 7 day programs + manual mode
 Auto recover after power outage
 Temporary and permanent hold
 Auto switchover between heating and cooling modes
 Customize programs from a desktop or tablet computer
 No batteries required (but requires a common or ‘C’ wire)1
 Works with Heat Pump and Conventional systems2,3
 Heat pump with auxiliary heat: 1 cooling and 2 heating stages
 Conventional system: 1 cooling and 1 heating stages
 Maximum control current: 400 mA (any terminal)
 Temperature accuracy ±1°F
1. If you do not have a ‘C’ wire, you can: 1. use fan wire as ‘C’ wire
(you will not be able to use fan independently) or 2. use an external
power supply.
2. CyberStat does not work with line-voltage baseboard heaters.
3. CyberStat will not work if you have separate Rc and Rh wires. This
limitation does not apply if there is a jumper between Rc and Rh
terminals.
Features & Compatibility
3
Remove Old Thermostat
4
1. Turn off the old thermostat.
2. Turn off power to the heating and cooling system.
3. Remove any locking screw and then remove the face plate.
4. Record the terminal names and corresponding wire colors below.
(Depending on your system, you may not have all the wires listed here)
5. Now remove the wires and the old wall plate.
Old Thermostat Terminal Wire Color
(please fill in) CyberStat
Terminal
Terminal Purpose
CCommon or Ground C
R, Rc or Rh 24 V AC Hot R
O or B Reversing Valve O/B
YCompressor Y
WHeat or Aux Heat W
GFan G
Install CyberStat
5
1. Detach the back cover of CyberStat and place it on the wall. Mark
the mounting hole locations with a pencil. You may want to use a level
at this time.
2. Use a #2 Philips head screwdriver to screw-in the provided drywall
anchors at marked locations. If the old thermostat did not use drywall
anchors then most likely there is a wood bracing behind the drywall. In
that case you should skip this step.
Tip: The drywall anchor does not require pre-
drilling. However, making a dimple with the tip of
a screw driver at the marked location will make
the placement more accurate.
3. Mount the back cover on the wall.
4. Connect the wires to the terminals matching the terminal names. See
wiring diagrams for your system on pages 6-13.
Conventional Heat/Cool
6
Wiring option 1 for Conventional Heat and/or Cool system
 Use this wiring option if you have a C wire
 Yellow and green wires are not required for a heat-only system
 White wire is not required for a cool-only system
Notes on C wire:
Make sure that C wire is
connected to C terminal
on the furnace.
You will not get stable
power if C wire is not
connected to C terminal
on the furnace.
A previously unused
wire can be used as C
wire. Simply connect it
to C terminal on furnace
and C terminal on the
thermostat.
24 V AC neutral (C wire)
24 V AC hot
Heat
Cool
Fan
C
R
O/B/W1
Y
G
W2
Conventional Heat/Cool
7
Wiring option 2 for Conventional Heat and/or Cool system
 Use this wiring option to re-purpose green wire as C wire
 Re-purposing requires some wiring changes on the furnace side
 With this option, you will not be able to use fan independently
Furnace side wiring
to re-purpose green
wire as C wire
1. Move green wire
to C terminal and
2. Put a jumper
across Y and G
terminals
24 V AC neutral (C wire)
24 V AC hot
Heat
Cool
C
R
W
Y
G
Furnace CyberStat
C
R
O/B/W1
Y
G
W2
Conventional Heat/Cool
8
Wiring option 3 for Conventional Heat and/or Cool system
 Use external power supply if you do not have a C wire
 Yellow and green wires are not required for a heat-only system
 White wire is not required for a cool-only system
24 V AC adapter is
required if you do
not have a C wire.
If using an external
power supply, you
will have two wires
going to R terminal.
24 V AC hot
Heat
Cool
Fan
C
R
O/B/W1
Y
G
W2
Heat Pump
9
Wiring option 1 for Heat Pump
 Use this wiring option if you have a C wire
 Reversing valve wire is typically orange or blue color
 If there is a conflict between wire color and terminal name, use terminal names
Notes on C wire:
Make sure that C wire is
connected to C terminal
on the air-handler.
You will not get stable
power if C wire is not
connected to C terminal
on the air-handler.
A previously unused
wire can be used as C
wire. Simply connect it
to C terminal on air-
handler and C terminal
on thermostat.
24 V AC neutral (C wire)
24 V AC hot
Reversing Valve
Compressor
Fan
Aux Heat
C
R
O/B/W1
Y
G
W2
Heat Pump
10
Wiring option 2 for Heat Pump
 Use this wiring option to re-purpose green wire as C wire
 Re-purposing requires some wiring changes on the air-handler side
 With this option, you will not be able to use fan independently
Air-handler wiring
to re-purpose green
wire as C wire
1. Move green wire
to C terminal and
2. Put a jumper
across Y and G
terminals
24 V AC neutral (C wire)
24 V AC hot
Reversing Valve
Compressor
C
R
O/B
Y
G
Air-Handler CyberStat
C
R
O/B/W1
Y
G
W2
Aux Heat
Aux
Heat Pump
11
Wiring option 3 for Heat Pump
 Use external power supply if you do not have a C wire
 Use Elk TRG2440 or similar transformer
24 V AC adapter is
required if you do
not have a C wire.
If using an external
power supply, you
will have two wires
going to R terminal.
24 V AC hot
Reversing Valve
Compressor
Fan
Aux Heat
C
R
O/B/W1
Y
G
W2
Two-Wire Heating
12
Wiring two-wire heat-only system
 Use Elk TRG2440 or similar transformer
24 V AC adapter is
required with a two
wire heating system.
You will have two
wires going to R
terminal.
24 V AC hot
Heat
C
R
O/B/W1
Y
G
W2
Milli Volt Heating
13
Wiring Milli Volt system
 An isolated 24 V AC transformer will not interfere with Milli Volt system
 Use Elk TRG2440 or similar transformer
Milli Volt Wire 1
Milli Volt Wire 2
C
R
O/B/W1
Y
G
W2
24 V AC adapter is
required with a Milli
Volt system.
You will have two
wires going to R
terminal.
Install CyberStat
14
5. Trim and tape unused wires. Please do not leave unused exposed
wires in the area. Tuck all wires such that they stay below the terminal
level.
6. Attach the front assembly to the wall plate. First, hook the tabs on the
top of front assembly to the slots on the wall plate then snap the bottom
in place.
7. Turn on the power to the heating and cooling system.
8. CyberStat will now show the room temperature.
* Additional configuration on page 16 is required for Heat Pump.
Wiring Troubleshooting
15
Caution: Turn off power to furnace/air-handler before you open its wiring panel.
CyberStat does not power up:
1. Touch the two leads of 24 V test lamp to R and C terminals of Cyber-
Stat. Be careful not to short the lamp wires. If the lamp does not light
up, your C wire is not connected to C terminal on furnace or air-handler.
Please note that the lamp test is useful for detecting unconnected
wires. It does not detect wrong connections. A wrong connection can
still produce a false positive.
2. If you had opened your furnace or air-handler panel, be sure to close
it. Often there is a switch on the panel cover. This switch cuts off power
when panel is open.
CyberStat keeps resetting to 00:
1. Make sure that C wire is connected to C terminal on furnace or air
handler. If you connect C wire to any other terminal, you will not get a
stable power.
2. If you do not have a C wire, you must use an external power supply.
Only fan (green) or a previously-unused wire can be re-purposed or
used as C wire. Any other wire that was used earlier for other purpose
cannot be used as C wire.
System Configuration
16
Tip: You could also complete this step using a smart-phone, tablet or
laptop computer. See Wi-Fi setup on page 21.
Configure CyberStat to work with your heating/cooling System. Press
mode and up buttons simultaneously to enter configuration mode.
Press up or down buttons to select a setting for current item.
Press mode button again to save your selection and move on to the
next item. For conventional systems, there is only one configuration
item to fill in. For these systems, pressing mode button will bring back
the normal display immediately.
Use the configuration chart on the next page as a guide to select cor-
rect settings for your heating and cooling system. If you are not sure
about your system, check the label on the indoor and outdoor units.
If your heating and cooling are reversed, please double check your
reversing valve settings. Also make sure that you are not using
Heat Pump setting while you have a conventional system.
1. If you have an A/C with gas furnace or heat-only or cool-only system,
then select conventional.
2. If you have a Heat Pump plus a gas furnace, then select Dual Fuel.
3. For Rheem or Ruud brand heat pumps, reversing valve is energized
for heating (pick 0). For most other brands, reversing valve is energized
for cooling (pick 1). To verify your settings, run a cooling test described
on the next page. Heating test is not suitable for this purpose.
Configuration item Possible settings
H: HVAC System type 0: Heat Pump
1: Conventional1
2: Dual Fuel2
L: Reversing vaLve type3
(applicable for heat pump only) 0: Energized for Heating
1: Energized for Cooling
Configuration Chart
17
Fan test – Press the mode button repeatedly until the fan light comes
on. The fan should turn on. Note: if you have re-purposed your fan
(green) wire to be used as ‘C’ wire then this test will not work.
Cooling test – Press the mode button repeatedly until the cool light
comes on. Press the up or down buttons to select a temperature lower
than the room temperature. The air conditioner should turn on.
Heating test – Press the mode button repeatedly until the heat light
comes on. Press up or down buttons to select a temperature higher
than the room temperature. The first stage heater should turn on. After
some time, second stage heater (if available) should turn on.
Note: For system safety and performance, heating and cooling cannot
be used back to back. Please allow at least fifteen minutes between
heating and cooling tests. Power cycling CyberStat will overcome this
time delay.
System Test
18
CyberStat is now ready to use. Press the mode button repeatedly to
select an appropriate mode and the up or down buttons to set desired
temperature. Operation in various modes are described below:
More advanced features of CyberStat will become available after you
setup Wi-Fi.
Auto CyberStat automatically sets heating or cooling modes to
maintain set temperature
Heat If the room temperature goes below set temperature then
the heater is turned on
Fan Fan is turned on for air circulation
Cool If the room temperature goes above set temperature then
the air conditioner is turned on
Off Mode indicators and the system are turned off. Wi-Fi status
indicator and temperature display stay on.
Basic Use
19
CyberStat can store up to with three programs for three seasons: P1 for
spring/fall, P2 for summer and P3 for winter. You can access and cus-
tomize these programs from your computer. P0 puts CyberStat into
manual mode.
To switch between programs, press and hold mode button for two sec-
onds. Then press up or down buttons to select a program suitable for
the current season. New program will be effective at next scheduled
point.
Overrides: Press up or down buttons to change set temperature. The
settings indicator turns on when the display shows set temperature.
Press mode button to cycle through different modes. The overrides will
take effect after a ten-second delay.
In manual mode P0, no program is running and any change you make
is permanent - it will stay there until you change it again.
In a programmed mode P1-P3, any change you make is temporary -
it will expire at next program point and the program will resume.
Program & Overrides
20

Popular Thermostat manuals by other brands

Pentair Nuheat Signature operating instructions

Pentair

Pentair Nuheat Signature operating instructions

Honeywell Home T3 quick start guide

Honeywell Home

Honeywell Home T3 quick start guide

olympia electronics BS-812 manual

olympia electronics

olympia electronics BS-812 manual

Venstar T0130 owner's manual

Venstar

Venstar T0130 owner's manual

Vemer Mithos RF user manual

Vemer

Vemer Mithos RF user manual

Danfoss BasicPlus2 WT-DM installation guide

Danfoss

Danfoss BasicPlus2 WT-DM installation guide

American Standard Copeland T005.730 installation instructions

American Standard

American Standard Copeland T005.730 installation instructions

Honeywell CM707 user manual

Honeywell

Honeywell CM707 user manual

Warmup TH115 A user guide

Warmup

Warmup TH115 A user guide

OJ Microline ETR2 instructions

OJ

OJ Microline ETR2 instructions

Purmo Unisenza Installation and user manual

Purmo

Purmo Unisenza Installation and user manual

Carrier 33CS420-01 owner's manual

Carrier

Carrier 33CS420-01 owner's manual

TUTTOKool TK-701W Operation manual

TUTTOKool

TUTTOKool TK-701W Operation manual

Crestron CHV-TSTAT-FCU Supplemental guide

Crestron

Crestron CHV-TSTAT-FCU Supplemental guide

VDH ALFA 59 user manual

VDH

VDH ALFA 59 user manual

Savant CLI-W210 01 Series quick start guide

Savant

Savant CLI-W210 01 Series quick start guide

Honeywell T8700B Product data

Honeywell

Honeywell T8700B Product data

Amber DT-two user guide

Amber

Amber DT-two user guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.