When replacing the battery, press and hold the center button while plugging in the
new battery connector. This will reset the battery gauge. When the display appears,
release the button.
The following tasks must be performed after replacing batteries:
•Press any button to power on the WPT.
•Perform an OTAA bind. Refer to Figure 8 for the menu structure.
•Confirm calibration and if needed, perform a manual calibration, see section 2.3.
•(Optional) Resend temperature setpoints, setpoint limits and auto calibration
values from the WPT Green Box Controller. Refer to the appropriate WPT Green
Box manual for instructions.
Note: If any of the steps above fail, refer to the Additional Troubleshooting section at
the end of this manual for further details.
2.1.4 Battery Handling Precautions
Replace battery only with the approved Tadiran TL-5920 lithium metal battery. This
battery meets UL-1642, as evidenced by UL component listing. Use of any other
battery may present a risk of fire or explosion. See Figure 7 for correct polarity of
connector.
•Underwriters Laboratories Recognition Mark:
•Caution: The battery used in this device may present a fire or chemical burn
hazard if mis-treated. Keep away from children and/or other untrained personnel.
Do not recharge, disassemble, heat above 100 ºC (212 ºF), or dispose of in fire.
•Dispose of used battery promptly in accordance with local regulations (place in
plastic bag and recycle if possible).
•Do not insert batteries with the and polarities reversed.
•Do not short-circuit.
•Be sure to wrap each battery when disposing or storing to avoid short circuit.
•If leaked liquid gets in the eyes, wash them with clean water and consult a
physician immediately.
•Do not apply strong pressure to the battery nor handle roughly.
•Do not use or leave the battery in direct sunlight or in high-temperature areas.