Det-Tronics UD10 User manual

Instructions 95-8661
FlexVu®Explosion-Proof
Universal Display Unit
Model UD10
4.1 Rev: 2/13 95-8661

APPLICATION ..............................1
DESCRIPTION
..............................1
HART Communication
......................3
Magnetic Switches
........................3
Relays
..................................4
4-20 mA Output Modes ......................4
Modbus / Fieldbus Compatibility
..............4
Device Enclosure
.........................4
Device Display
...........................4
Logging
.................................5
IMPORTANT SAFETY NOTES
...................5
INSTALLATION
..............................6
Identication of Vapor(s) to be Detected
.........6
Identication of Detector Mounting Locations
.....6
WIRING
....................................7
Power Supply Requirements
.................7
Wiring Cable Requirements
..................7
Shield Connections .......................7
Jumper Setting for 4-20 mA Loop ............7
Foundation Fieldbus.......................7
Wiring Procedure
..........................8
STARTUP
.................................12
TROUBLESHOOTING .......................15
SPECIFICATIONS
...........................18
DEVICE REPAIR AND RETURN ...............20
ORDERING INFORMATION ..................21
APPENDIX A — FM APPROVAL DESCRIPTION ....A-1
APPENDIX B — CSA CERTIFICATION DESCRIPTION . B-1
APPENDIX C — ATEX APPROVAL DESCRIPTION.....C-1
APPENDIX D — IEC APPROVAL DESCRIPTION ......D-1
APPENDIX E –
UD10 WITH HANDHELD HART
COMMUNICATOR
...............................E-1
Wiring................................E-1
Menu Structure.........................E-1
APPENDIX F –
UD10 WITH GT3000 TOXIC GAS
DETECTOR
....................................F-1
Wiring................................F-1
Orientation ............................F-2
Live Maintenance .......................F-2
Calibration ............................F-3
Menu Structure.........................F-4
APPENDIX G —
UD10 WITH PIR9400 POINTWATCH
..G-1
Wiring................................G-1
Installation Notes .......................G-2
Orientation ............................G-2
Changing Operating Modes ...............G-3
Calibration ............................G-3
Menu Structure.........................G-4
APPENDIX H —
UD10 WITH MODEL PIRECL
........H-1
Wiring................................H-1
Orientation ............................H-2
Calibration ............................H-3
Menu Structure.........................H-4
APPENDIX I —
UD10 WITH OPEN PATH MODEL OPECL
.....I-1
Wiring.................................I-1
Orientation .............................I-3
Calibration .............................I-3
OPECL Transmitter Lamp Fault Condition .....I-4
Menu Structure..........................I-4
APPENDIX J —
UD10 WITH NTMOS H2S SENSOR
... J-1
Wiring................................ J-1
Installation Notes ....................... J-1
Orientation ............................ J-4
Calibration ............................ J-4
Menu Structure......................... J-5
APPENDIX K —
UD10 WITH C706X TOXIC GAS SENSOR
. K-1
Wiring................................K-1
Installation ............................K-3
Calibration ............................K-4
Menu Structure.........................K-4
APPENDIX L — UD10 WITH MODEL CGS SENSOR .....L-1
Wiring ................................L-1
Important Notes ........................L-1
Installation.............................L-3
Calibration .............................L-3
K-Factor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . L-4
Menu Structure .........................L-4
APPENDIX M —
UD10 WITH MODEL 505/CGS
. . . . . . . . .M-1
Wiring................................M-1
Installation ............................M-2
Orientation ............................M-2
Calibration ............................M-3
Menu Structure.........................M-4
APPENDIX N —
UD10 WITH GENERIC 4-20 MA SENSOR
. N-1
Operation .............................N-1
Menu Structure.........................N-1
Table of Contents

INSTRUCTIONS
FlexVu®Explosion-Proof
Universal Display Unit
Model UD10
IMPORTANT
Be sure to read and understand the entire
instruction manual before installing or operating
the gas detection system. This product can be
used with a variety of Det-Tronics gas detectors to
provide early warning of the presence of a toxic or
explosive gas mixture. Proper device installation,
operation, and maintenance is required to ensure
safe and effective operation. If this equipment
is used in a manner not specied in this manual,
safety protection may be impaired.
ApplicAtion
The FlexVu® Model UD10 is recommended for
applications that require a gas detector with digital
readout of detected gas levels as well as analog 4-20
mA output with HART, relay contacts, and Modbus
RS485 (foundation™Fieldbus option available). The
UD10 Universal Display Unit is designed for use with
Det-Tronics gas detectors listed in Table 1.
The display unit is designed and approved as a ‘stand
alone’ device and performs all the functions of a gas
controller.
When furnished with the CGS interface board, the
device can be used only with a CGS sensor for detection
of combustible gas. The UD10/CGS combination is
certified as a “Gas Detector”.
Gas concentration and unit of measurement are
displayed on a digital display. The display unit provides
a linear isolated/non-isolated 4-20 mA DC output signal
(with HART) that corresponds to the detected gas
concentration.
All electronics are enclosed in an explosion-proof
aluminum or stainless steel housing. The display unit is
used with a single detector that may be either coupled
directly to the UD10, or remotely located using a sensor
termination box.
The UD10 features non-intrusive calibration. A magnet
is used to perform calibration as well as to navigate the
UD10’s internal menu.
Description
The UD10 Universal Display can be used with various
4-20 mA gas detection devices, with or without HART.
The unit provides display, output and control capabilities
for the gas detector.
The UD10 utilizes the following I/O:
Signal Inputs:
4-20 mA loop from the sensing device
User Inputs: Magnetic switches (4) on the display
panel
HART communication (handheld field
communicator or AMS)
foundation™Fieldbus (if selected)
Signal Outputs:
4-20 mA output loop with HART
Modbus RS485 or foundation™Fieldbus
Three alarm relays and one fault relay
Visible Outputs:
Backlit LCD display
HART slave interface via HART
Communicator
4.1 ©Detector Electronics Corporation 2013 Rev: 2/13 95-8661

295-8661
4.1
Table 1—Range and Default Values for Alarms and Calibration Gas Concentration
Notes: All values are a percentage of full scale with the exception of Oxygen, which is the actual percent of Oxygen, and
OPECL, which is the value in LFL-meters.
Low alarm must be less than or equal to the high alarm.
Changing the Measurement Range will reset all alarm and Cal Gas values to the default settings for the selected range.
Alarm relays are selectable for either normally energized or normally de-energized coils, with selectable latching or
non-latching contacts. Fault relay is normally energized (with no faults).
*Does not support C7064C hydrogen sulde or C7065E oxygen, but includes C7064E hydrogen sulde,
C7067E chlorine, C7066E carbon monoxide, and C7068E sulfur dioxide.
UD10 ALARM DATA CALIBRATION
Gas Detector High Alarm Value Low Alarm Value Aux alarm Value Cal Gas
GT3000--
Hydrogen Sulde
Range 10-90% 5-50% 5-90% 30-90%
Default 40% 10% 40% 50%
GT3000--
Ammonia
Range 10-90% 5-50% 5-90% 30-90%
Default 40% 10% 40% 50%
GT3000--Chlorine Range 10-90% 5-50% 5-90% 30-90%
Default 40% 10% 40% 50%
GT3000--
Hydrogen
Range 10-60% 5-50% 5-90% 30-90%
Default 40% 10% 40% 50%
GT3000--Oxygen Range 5-20.5% v/v 5-20.5% v/v 5-20.5% v/v 20.9% v/v
Default 18% v/v 18% v/v 18% v/v 20.9% v/v
GT3000--Carbon
Monoxide
Range 10-90% 5-50% 5-90% 30-90%
Default 40% 10% 40% 50%
GT3000--Sulfur
Dioxide
Range 10-90% 5-50% 5-90% 30-90%
Default 40% 10% 40% 50%
PIR9400 Range 10-60% 5-50% 5-90% 50%
Default 40% 10% 40% 50%
PIRECL Range 10-60% 5-50% 5-90% 30-90%
Default 40% 10% 40% 50%
OPECL Range 1-3 LFL-meters 0.25-3 LFL-meters NA NA
Default 2 LFL-meters 1 LFL-meter NA NA
C706X* Range 10-90% 5-50% 5-90% 30-90%
Default 40% 10% 40% 50%
CGS
Combustible
Range 10-60% 5-50% 5-90% 50%
Default 40% 10% 40% 50%
Model 505/CGS
Combustible
Range 10-60% 5-50% 5-90% N/A
Default 40% 10% 40% N/A
NTMOS--
Hydrogen Sulde
Range 10-90% 5-50% 5-90% 50%
Default 40% 10% 40% 50%
Generic Detector Range 10-90% 5-50% 5-90% N/A
Default 40% 10% 40% 50%

395-86614.1
HART COMMUNICATION
A HART interface provides device status information
and field programming capability.
MAGNETIC SWITCHES
Four internal magnetic switches provide a non-intrusive
user interface that allows navigation through the menu
and adjustment of configuration parameters in the field
without the use of a HART handheld device. See Figure
1 for switch locations.
These switches are used for device configuration,
checking status and event logs, and performing
calibration. The switches are labeled as follows:
CANCEL / ESCAPE
ENTER / SELECT / MENU ACCESS
PREVIOUS or if on Main Screen:
Fault Shortcut
NEXT
To actuate a magnetic switch, lightly touch the magnet
to the viewing window of the UD10 directly over the
switch icon on the faceplate.
CAUTION
Handle magnets with care! Personnel wearing
pacemakers/debrillators should not handle
magnets. Modern magnet materials are extremely
strong magnetically and somewhat weak
mechanically. Injury is possible to personnel, and
magnets themselves can easily get damaged if
allowed to snap towards each other, or if nearby
metal objects are allowed to be attracted to the
magnets.
NOTE
Det-Tronics offers two magnet options for
activating internal magnetic switches. While the
two magnets can usually be used interchangeably,
the best results will be achieved if they are used
as follows: The Magnetic Tool (p/n 009700-001)
is the stronger magnet and is recommended
for activating the switches on the UD10
viewing window. The Calibration Magnet (p/n
102740-002) is recommended for applications
that involve initiating calibration or resetting the
detector by touching the side of a metal junction
box or detector housing (PIRECL, OPECL, etc).
Throughout this manual, the term “magnet” can
refer to either device.
Access To Menus
To access the menus, use the magnet to activate the
ENTER/SELECT button. This will display the Main
Menu.
The actual menu structure varies depending upon the
device that is connected to the UD10. Menus for the
various devices can be found in the corresponding
Appendix in this manual.
Some areas of the menu contain additional information,
which is indicated by the presence of an arrow on that
particular line. By placing the magnet to the glass over
the ENTER/SELECT button, the next screen with the
additional information will be shown.
The UD10 automatically returns to the main screen after
10 minutes if no activity occurs.
Quick Access/Shortcut: Fault Menu
To access the fault menu quickly, when a fault is present,
touch the magnet to the glass by the PREVIOUS button.
CANCEL / ESCAPE
ENTER / SELECT
PREVIOUS
NEXT
B2426
Figure 1—Faceplate of UD10

495-8661
4.1
RELAYS
The display unit has 4 output relays — high alarm, low
alarm, auxiliary alarm, and fault. The relays have form
C (SPDT) contacts. Low, auxiliary and high alarm relay
contacts are selectable for latching or non-latching
operation, as well as normally energized or normally
de-energized (default) coils. During normal operation,
the fault relay is energized.
IMPORTANT
Direct connection of 120/240 VAC to the
relay terminals inside the UD10 enclosure
is not allowed, since switching relay contacts
can induce electrical noise into the electronic
circuitry, possibly resulting in a false alarm or other
system malfunction. If the application requires
that AC powered equipment be controlled by the
transmitter, the use of externally located relays is
recommended.
External relays, solenoids, motors, or other devices
that can cause inductive transients should be transient
suppressed. Place a diode across the coil for DC
devices. See Figure 2.
Figure 2—Transient Suppression for Inductive Loads
RELAY
SOLENOIDS
MOTORS
INDUCTION DEVICES
1N4004
TYPICAL
B0179
POSITIVE
NEGATIVE
MOV
HOT
NEUTRAL
120 VOLT – V13OLA10A
220/240 VOLT – V275LA20A
GE
TYPICAL
{ }
+
–
DCV LOADS
A0179
4-20 MA OUTPUT MODES
The UD10 offers two operating modes for its 4-20 mA
output circuit.
NOTE
A minimum output of 1 mA is required for proper
HART communication.
In the Standard (default) Mode, the linear 4-20 mA
output corresponds to 0-100% full scale gas detected at
the sensor, with 3.8 mA indicating calibrate mode, and
3.6 mA or lower indicating a fault condition. This mode
ensures that the current level is always high enough to
support HART communication and must be selected
when using HART communication for fault diagnostics.
In Replicate Mode, the output of the UD10 matches
the output of the connected detector (except for loop
test/trim, response test, calibration, or if the UD10
has an internal fault). This mode can be used with
detectors such as PIR9400 or PIRECL where multiple
current levels below 4 mA are used for fault diagnostic
purposes.
UD10 with Model PIRECL
PIRECL supports two fault modes: PIR9400 and Eclipse
mode. PIR9400 fault mode uses fault codes below 1
mA, while Eclipse mode uses no levels below 1 mA. In
the Standard (default) mode, the UD10 programs the
PIRECL for Eclipse fault mode to ensure proper HART
communication in the event of a fault. In the Replicate
mode, the UD10 programs the PIRECL for PIR9400
fault mode.
MODBUS / FIELDBUS COMPATIBILITY
The UD10 supports RS485 Modbus RTU communi-
cation. See Addendum number 95-8639 for details. A
model with
Modbus RS485 or foundation™Fieldbus
communication (field selectable via jumpers)
is also
available.
DEVICE ENCLOSURE
The UD10 housing is a 5 port aluminum or stainless steel
explosion-proof junction box with a clear viewing window.
DEVICE DISPLAY
The UD10 is provided with a 160 x 100 dot matrix backlit
LCD display. See Figure 1.
During normal operation, the LCD continuously
displays the detected gas level, gas type, and units
of measurement. The real time clock can also be
displayed if desired.
The display shows the following alarm information:
•Highgasalarm
•Lowgasalarm
•Auxalarm
The display indicates the following fault information:
•Devicefault
•Displayfault
The UD10 has smart capabilities to allow easy access
to the following information:
•Detectorinformation
•Measurementrange
•Alarmsetpoints
•Alarmandeventlogs
For detailed HART menu structure, refer to the appropriate
Appendix.

595-86614.1
LOGGING
Events that can be logged in the UD10 include:
•Calibration(Date,timeandsuccessY/Narelogged
for detectors that do not provide their own calibration
logging capabilities.)
Faults that are logged in the UD10 include:
•Detectorfault
•Lowpower
•Generalfault
Alarms that are logged in the UD10 for gas detector inputs
include:
•Highgasalarm
•Lowgasalarm
•Auxalarm.
The UD10 has its own battery backed real time clock
(RTC) and its own event logs. The RTC in the UD10
can be set from the UD10 display, Modbus or HART
interfaces. The RTC in the gas detector (any HART
detector having an RTC) can be set independently
using the UD10 menu, or by using the synchronize
command, which will set the detector RTC to the same
time as the UD10 RTC. See Figure 3.
The UD10 can display the detector event and
calibration logs (if available). The UD10 has its own
1,000-entry event log available under the Display
Status->History->Event Log menu.
UD10 event logs can be read from the HART interface
or the Modbus interface.
Detector calibration and event logs can also be read
from the detector HART interface (where available).
importAnt sAfety notes
CAUTION
The wiring procedures in this manual are intended
to ensure proper functioning of the device under
normal conditions. However, because of the
many variations in wiring codes and regulations,
total compliance to these ordinances cannot be
guaranteed. Be certain that all wiring complies
with the NEC as well as all local codes. If in
doubt, consult the authority having jurisdiction
before wiring the system. Installation must be
done by a properly trained person.
CAUTION
This product has been tested and approved
for use in hazardous areas. However, it must
be properly installed and used only under the
conditions specied within this manual and
the specic approval certicates. Any device
modication, improper installation, or use in a
faulty or incomplete conguration will render
warranty and product certications invalid.
CAUTION
The device contains no user serviceable
components. Service or repair should never be
attempted by the user. Device repair should be
performed only by the manufacturer.
LIABILITIES
The manufacturer’s warranty for this product is
void, and all liability for proper function of the
detector is irrevocably transferred to the owner or
operator in the event that the device is serviced or
repaired by personnel not employed or authorized
by Detector Electronics Corporation, or if the
device is used in a manner not conforming to its
intended use.
CAUTION
Observe precautions for handling electrostatic
sensitive devices.
CAUTION
Unused conduit entries must be closed with
suitably certied blanking elements upon
installation.
GAS
DETECTOR UD10
CONTROL
SYSTEM
PLC/DCS
CONTROL
SYSTEM
PLC/DCS
AMS
HART
Handheld
HART
Handheld
HART
HART
MODBUS
or
FOUNDATION FIELDBUS
Figure 3—UD10 Logging

695-8661
4.1
instAllAtio n
NOTE
The gas detector housing must be electrically
connected to earth ground. A dedicated earth
ground terminal is provided on the UD10.
NOTE
Refer to the Model UD10 Safety Manual
(number 95-8668) for specic requirements
and recommendations applicable to the proper
installation, operation, and maintenance of SIL-
Certied Model UD10 displays.
The detector must always be installed per local
installation codes.
Before installing the gas detector, define the following
application details:
IDENTIFICATION OF VAPOR(S) TO BE DETECTED
It is necessary to identify the vapor(s) of interest at the
job site. The fire hazard properties of the vapor, such
as vapor density, flashpoint, and vapor pressure should
be identified and used to assist in selecting the optimum
detector mounting location within the area.
For cross sensitivity information, refer to each gas
detector’s corresponding instruction manual. Refer to
Table 5 in the Specifications section for a list of gas
detectors and their corresponding instruction manuals.
IDENTIFICATION OF DETECTOR MOUNTING
LOCATIONS
Identification of the most likely leak sources and
leak accumulation areas is typically the first step in
identifying the best detector mounting locations. In
addition, identification of air current/wind patterns
within the protected area is useful in predicting gas leak
dispersion behavior. This information should be used
to identify optimum detector installation points.
If the vapor of interest is lighter than air, place the detector
above the potential gas leak. Place the detector close
to the floor for gases that are heavier than air. Note
that air currents may cause a gas that is slightly heavier
than air to rise under some conditions. Heated gases
may also exhibit the same phenomenon.
The most effective number and placement of detectors
varies depending on the conditions on site. The individual
designing the installation must often rely on experience
and common sense to determine the detector quantity
and best locations to adequately protect the area. Note
that it is typically advantageous to locate detectors
where they are accessible for maintenance. Locations
near excessive heat or vibration sources should be
avoided.
Final suitability of possible gas detector locations
should be verified by a job site survey.
The gas detector must be mounted with the sensor in
the correct orientation as shown in Table 2.
If the UD10 faceplate is not correctly oriented, it can
be rotated at 90 degree increments by pulling the
electronic module from the four mounting posts that
secure it to the junction box and repositioning it as
desired. Note that the module is held in place by a
compression fitting – no screws are involved.
Table 2—Device Orientation
Device Orientation
GT3000
Vertical with Sensor Pointing Down
PIR9400 Horizontal
PIRECL Horizontal
OPECL Horizontal (Fixed to a vertical post)
CGS
Vertical with Sensor Pointing Down
505/CGS
Vertical with Sensor Pointing Down
C706X
Vertical with Sensor Pointing Down
NTMOS
Vertical with Sensor Pointing Down

795-86614.1
WirinG
POWER SUPPLY REQUIREMENTS
Calculate the total gas detection system power
consumption rate in watts from cold start-up. Select a
power supply with adequate capability for the calculated
load. Ensure that the selected power supply provides
regulated and filtered 24 Vdc output power for the entire
system. If a back-up power system is required, a float-type
battery charging system is recommended. If an existing
source of 24 Vdc power is being utilized, verify that system
requirements are met. The acceptable voltage range is
18-30 Vdc measured at the input to the UD10.
NOTE
The power supply must meet the noise requirements
for HART systems. If noise or ripple on the main
power source could interfere with the HART
function, an isolated power source (Figure 11) is
recommended. (For detailed information regarding
power supply specications, refer to the HART
Communication Foundation’s document “FSK
Physical Layer Specication” HCF_SPEC-54.)
WIRING CABLE REQUIREMENTS
Always use proper cabling type and diameter for input
power as well as output signal wiring. 14 to 18 AWG
shielded stranded copper wire is recommended. Correct
wire size depends on the device and wire length. Refer
to the appropriate Appendix for additional information.
The maximum cable length from power source to UD10 is
2000 feet. Maximum cable length from UD10 to sensor
is 2000 feet.
NOTE
The use of shielded cable in conduit or shielded
armored cable is highly recommended. In
applications where the wiring is installed in
conduit, dedicated conduit is recommended.
Avoid low frequency, high voltage, and
non-signaling conductors to prevent nuisance
EMI problems.
CAUTION
The use of proper conduit installation techniques,
breathers, glands, and seals is required to prevent
water ingress and/or maintain the explosion-proof
rating.
SHIELD CONNECTIONS
The UD10 provides terminals for proper grounding of
wiring cable shields (located on the sensor, 4-20 mA,
and operating power terminal blocks). These shield
terminals are not connected internally, but are connected
to ground through capacitors. The capacitors ensure an
RF ground, while preventing 50/60 Hz ground loops.
Ground all shields as shown in the wiring examples
throughout this manual.
IMPORTANT
For proper grounding, all junction boxes / metal
enclosures must be connected to earth ground.
The following are required for installations requiring CE
Mark compliance:
•Forshieldedcableinstalledinconduit,attachthewire
shields to the “shield” connections on the terminal
blocks, or to earth ground on the case.
•Forinstallationswithoutconduit,usedoubleshielded
cable. Terminate the outer shield to earth ground on
the case. Terminate the inner shield to the “shield”
connection on the terminal blocks.
JUMPER SETTING FOR 4-20 MA LOOP
In order for the 4-20 mA current loop to operate properly,
+24 Vdc must be applied to terminal P1-3. This can be
accomplished in one of two ways:
•Foranon-isolated 4-20 mA loop, set jumper plug as
shown in Figure 4. This applies +24 Vdc to P1-3 via an
internal connection to terminals P2-2 and P2-5.
•Ifthe4-20mAloopwillreceivepowerfromasource
other than the UD10’s main power source (isolated),
set the jumper plug as shown in Figure 5 to remove
the internal connection.
FOUNDATION FIELDBUS (Optional)
Some UD10 models allow the use of either RS485/
MODBUS or Foundation Fieldbus communication via
connection to J2 on the terminal board. Four jumpers
are provided to select between the two protocols. If the
device is equipped for Foundation Fieldbus, it will be
shipped from the factory with the jumpers preset for that
mode. If the user wants to switch to RS485/MODBUS
(for example, to retrieve logs), the four jumpers can
easily be moved. Figures 6 and 7 show the jumper
settings for each mode of communication.
Note that the pin identification for the J2 connector
is different for each communication protocol. For
Foundation Fieldbus it is “– +”. For RS485/MODBUS
it is “B A com”.

895-8661
4.1
WIRING PROCEDURE
NOTE
The following section shows the output of the
UD10 wired to a generic 4-20 mA signal receiver
in various congurations. Since the UD10 can be
used with a variety of different detection devices,
information that is specic to each detector model
(wiring, calibration, HART menus, etc.) is covered
in an Appendix that is dedicated to that device.
Refer to the appropriate Appendix at the back of
this manual for specic information when wiring
the detection system. For information on devices
not covered in an Appendix, refer to the manual
provided by the device’s manufacturer.
Figure 4 shows jumper plug P12 positioned to power the
4-20 mA loop from the main power source (non-isolated
output).
Figure 5 shows jumper plug P12 positioned for powering
the 4-20 mA loop from an external wire/jumper of from
a separate power source (isolated output).
Figure 6 shows the correct jumper positions and J2
terminal identification for using Foundation Fieldbus
communication.
Figure 7 shows the correct jumper positions and
J2 terminal identification for using MODBUS
communication.
Refer to Figure 8 for an illustration of the UD10 wiring
terminal board (see Figure 6 for Foundation Fieldbus
connections).
Figure 9 shows a UD10 Wired to a PLC using 3-Wire
Shielded Cable with a 4-20 mA Non-Isolated Sourcing
Output.
Figure 10 shows a UD10 Wired to a PLC using 4-Wire
Shielded Cable with a 4-20 mA Non-Isolated Sourcing
Output.
Figure 11 shows a UD10 Wired to a PLC with a 4-20 mA
Isolated Sourcing Output.
GREASE/LUBRICATION
To ease installation and future removal, ensure that all
junction box covers and sensor threads are properly
lubricated. If the need arises for additional lubrication, use
either Lubriplate grease (see Ordering Information for part
number) or Teflon tape. Avoid the use of silicone grease.
Figure 4—Position of Jumper P12 for
Non-Isolated 4-20 mA Loop Output
Sensor Connector
Power Supply Connector
Output
Loop
Connector
Fieldbus
Connector
Relay Connector
P1
J2
J3
J4
P2
4-20 mA +
4-20 mA –
SHIELD
+
–
HIGH ALARM COM
HIGH ALARM NC
HIGH ALARM NO
AUX ALARM COM
AUX ALARM NC
AUX ALARM NO
LOW ALARM COM
LOW ALARM NC
LOW ALARM NO
FAULT COM
FAULT NC
FAULT NO
24 VDC –
24 VDC +
SHIELD
24 VDC –
24 VDC +
SHIELD
SHIELD
CALIBRATE
24 VDC –
4-20 mA
24 VDC +
P1-3
P1-2
P1-1
J2-3
J2-2
J2-1
J4-1
J4-2
J4-3
J4-4
J4-5
J4-6
J4-7
J4-8
J4-9
J4-10
J4-11
J4-12
J3-1
J3-2
J3-3
J3-4
J3-5
P2-6
P2-5
P2-4
P2-3
P2-2
P2-1
P5
P9 P7
P12
P3
B2525
WHEN P12 IS
IN THIS POSITION,
P1-3 IS INTERNALLY
CONNECTED TO
P2-2 AND P2-5
Figure 5—Position of Jumper P12 for
Isolated 4-20 mA Loop Output
Sensor Connector
Power Supply Connector
Output
Loop
Connector
Fieldbus
Connector
Relay Connector
P1
J2
J3
J4
P2
4-20 mA +
4-20 mA –
SHIELD
+
–
HIGH ALARM COM
HIGH ALARM NC
HIGH ALARM NO
AUX ALARM COM
AUX ALARM NC
AUX ALARM NO
LOW ALARM COM
LOW ALARM NC
LOW ALARM NO
FAULT COM
FAULT NC
FAULT NO
24 VDC –
24 VDC +
SHIELD
24 VDC –
24 VDC +
SHIELD
SHIELD
CALIBRATE
24 VDC –
4-20 mA
24 VDC +
P1-3
P1-2
P1-1
J2-3
J2-2
J2-1
J4-1
J4-2
J4-3
J4-4
J4-5
J4-6
J4-7
J4-8
J4-9
J4-10
J4-11
J4-12
J3-1
J3-2
J3-3
J3-4
J3-5
P2-6
P2-5
P2-4
P2-3
P2-2
P2-1
P5
P9 P7
P12
P3
B2526
WHEN P12 IS IN
THIS POSITION, A
SEPARATE POWER
SOURCE IS REQUIRED
TO POWER THE
4-20 MA LOOP

995-86614.1
Figure 6—Foundation Fieldbus Communication
Sensor Connector
Power Supply Connector
Output
Loop
Connector
Fieldbus
Connector
Relay Connector
P1
J2
J3
J4
P2
4-20 mA +
4-20 mA –
SHIELD
+
–
HIGH ALARM COM
HIGH ALARM NC
HIGH ALARM NO
AUX ALARM COM
AUX ALARM NC
AUX ALARM NO
LOW ALARM COM
LOW ALARM NC
LOW ALARM NO
FAULT COM
FAULT NC
FAULT NO
24 VDC –
24 VDC +
SHIELD
24 VDC –
24 VDC +
SHIELD
SHIELD
CALIBRATE
24 VDC –
4-20 mA
24 VDC +
P1-3
P1-2
P1-1
J2-3
J2-2
J2-1
J4-1
J4-2
J4-3
J4-4
J4-5
J4-6
J4-7
J4-8
J4-9
J4-10
J4-11
J4-12
J3-1
J3-2
J3-3
J3-4
J3-5
P2-6
P2-5
P2-4
P2-3
P2-2
P2-1
P5
P9 P7
P12
P3
JUMPERS P3, P5, P7, AND P9 MUST BE POSITIONED AS SHOWN
FOR FOUNDATION FIELDBUS COMMUNICATION
B2527
Figure 7—MODBUS Communication
Sensor Connector
Power Supply Connector
Output
Loop
Connector
MODBUS
Connector
Relay Connector
P1
J2
J3
J4
P2
4-20 mA +
4-20 mA –
SHIELD
RS485 A
COM
RS485 B
HIGH ALARM COM
HIGH ALARM NC
HIGH ALARM NO
AUX ALARM COM
AUX ALARM NC
AUX ALARM NO
LOW ALARM COM
LOW ALARM NC
LOW ALARM NO
FAULT COM
FAULT NC
FAULT NO
24 VDC –
24 VDC +
SHIELD
24 VDC –
24 VDC +
SHIELD
SHIELD
CALIBRATE
24 VDC –
4-20 mA
24 VDC +
P1-3
P1-2
P1-1
J2-3
J2-2
J2-1
J4-1
J4-2
J4-3
J4-4
J4-5
J4-6
J4-7
J4-8
J4-9
J4-10
J4-11
J4-12
J3-1
J3-2
J3-3
J3-4
J3-5
P2-6
P2-5
P2-4
P2-3
P2-2
P2-1
P5
P9 P7
P12
P3
JUMPERS P3, P5, P7, AND P9 MUST BE POSITIONED AS SHOWN
FOR MODBUS/RS485 COMMUNICATION
B2528

10 95-8661
4.1
Figure 9—UD10 Wired to PLC using 3-Wire Shielded Cable with 4-20 mA Non-Isolated Sourcing Output
Sensor Connector
Power Supply Connector
Output Loop
Connector
MODBUS
Connector
Relay Connector
P1
J2
J3
J4
P2
4-20 mA +
4-20 mA –
SHIELD
COM
RS485 A
RS485 B
HIGH ALARM COM
HIGH ALARM NC
HIGH ALARM NO
AUX ALARM COM
AUX ALARM NC
AUX ALARM NO
LOW ALARM COM
LOW ALARM NC
LOW ALARM NO
FAULT COM
FAULT NC
FAULT NO
24 VDC –
24 VDC +
SHIELD
24 VDC –
24 VDC +
SHIELD
SHIELD
CALIBRATE
24 VDC –
4-20 mA
24 VDC +
P1-3
P1-2
P1-1
J2-3
J2-2
J2-1
J4-1
J4-2
J4-3
J4-4
J4-5
J4-6
J4-7
J4-8
J4-9
J4-10
J4-11
J4-12
J3-1
J3-2
J3-3
J3-4
J3-5
P2-6
P2-5
P2-4
P2-3
P2-2
P2-1
UD10
DISPLAY UNIT
C2439
24 VDC
INPUT
4-20 mA
PLC 4-20 mA INPUT CARD
–
+
250
OHMS
MINIMUM
Notes: Resistor may be external if voltage input card is used.
Sinking resistance at PLC must be 250 ohms minimum
for HART communication.
P12
Sensor Connector
Power Supply Connector
Output Loop
Connector
MODBUS
Connector
Relay Connector
P1
J2
J3
J4
P2
4-20 mA +
4-20 mA –
SHIELD
COM
RS485 A
RS485 B
HIGH ALARM COM
HIGH ALARM NC
HIGH ALARM NO
AUX ALARM COM
AUX ALARM NC
AUX ALARM NO
LOW ALARM COM
LOW ALARM NC
LOW ALARM NO
FAULT COM
FAULT NC
FAULT NO
24 VDC –
24 VDC +
SHIELD
24 VDC –
24 VDC +
SHIELD
SHIELD
CALIBRATE
24 VDC –
4-20 mA
24 VDC +
P1-3
P1-2
P1-1
J2-3
J2-2
J2-1
J4-1
J4-2
J4-3
J4-4
J4-5
J4-6
J4-7
J4-8
J4-9
J4-10
J4-11
J4-12
J3-1
J3-2
J3-3
J3-4
J3-5
P2-6
P2-5
P2-4
P2-3
P2-2
P2-1
C2399
Figure 8—Wiring Terminals on UD10 Terminal Board

11 95-86614.1
Sensor Connector
Power Supply Connector
Output Loop
Connector
MODBUS
Connector
Relay Connector
P1
J2
J3
J4
P2
4-20 mA +
4-20 mA –
SHIELD
COM
RS485 A
RS485 B
HIGH ALARM COM
HIGH ALARM NC
HIGH ALARM NO
AUX ALARM COM
AUX ALARM NC
AUX ALARM NO
LOW ALARM COM
LOW ALARM NC
LOW ALARM NO
FAULT COM
FAULT NC
FAULT NO
24 VDC –
24 VDC +
SHIELD
24 VDC –
24 VDC +
SHIELD
SHIELD
CALIBRATE
24 VDC –
4-20 mA
24 VDC +
P1-3
P1-2
P1-1
J2-3
J2-2
J2-1
J4-1
J4-2
J4-3
J4-4
J4-5
J4-6
J4-7
J4-8
J4-9
J4-10
J4-11
J4-12
J3-1
J3-2
J3-3
J3-4
J3-5
P2-6
P2-5
P2-4
P2-3
P2-2
P2-1
UD10
DISPLAY UNIT
D2440
24 VDC
INPUT
4-20 mA
PLC 4-20 mA INPUT CARD
–
+
250
OHMS
MINIMUM
Notes: Resistor may be external if voltage input card is used.
Sinking resistance at PLC must be 250 ohms minimum
for HART communication.
P12
Figure 10—UD10 Wired to PLC using 4-Wire Shielded Cable with 4-20 mA Non-Isolated Sourcing Output
Figure 11—UD10 Wired to PLC with 4-20 mA Isolated Sourcing Output
Sensor Connector
Power Supply Connector
Output Loop
Connector
MODBUS
Connector
Relay Connector
P1
J2
J3
J4
P2
4-20 mA +
4-20 mA –
SHIELD
COM
RS485 A
RS485 B
HIGH ALARM COM
HIGH ALARM NC
HIGH ALARM NO
AUX ALARM COM
AUX ALARM NC
AUX ALARM NO
LOW ALARM COM
LOW ALARM NC
LOW ALARM NO
FAULT COM
FAULT NC
FAULT NO
24 VDC –
24 VDC +
SHIELD
24 VDC –
24 VDC +
SHIELD
SHIELD
CALIBRATE
24 VDC –
4-20 mA
24 VDC +
P1-3
P1-2
P1-1
J2-3
J2-2
J2-1
J4-1
J4-2
J4-3
J4-4
J4-5
J4-6
J4-7
J4-8
J4-9
J4-10
J4-11
J4-12
J3-1
J3-2
J3-3
J3-4
J3-5
P2-6
P2-5
P2-4
P2-3
P2-2
P2-1
UD10
DISPLAY UNIT
C2441
24 VDC
24 VDC
INPUT
4-20 mA
PLC 4-20 mA INPUT CARD
–
–
+
+
250
OHMS
MINIMUM
Notes: Resistor may be external if voltage input card is used.
Sinking resistance at PLC must be 250 ohms minimum
for HART communication.
P12
IMPORTANT
Isolated operation is highly recommended to prevent noise or ripple on the main power source from interfering
with the HART function.

12 95-8661
4.1
stArtup
After power has been applied and the warm-up period
is complete, select the UD10 operating mode. To do
this:
1. Access the Main Menu by touching the magnet to
the ENTER/SELECT button. From there, navigate to
the
“Mode Select” menu
.
Main Menu
Process Vars
Display Status
Device Status
Display Setup
Device Setup
Device Cal
Display Test
Device Test
Display Setup
Write Protect
Alarm Setting
Mode Select
HART Option
RTC
Display RS485
Input Loop Cal
Mode Select
HART Device
PIR9400
C706X
505
NTMOS
CGS
Generic Device
2. From the “Mode Select” menu, select and enter the
appropriate operating mode based on the type of
detector being used.
NOTE
If using a PIR9400, note that changing the gas
type on the UD10 does not change the gas type at
the PIR9400. This change is made using a switch
located in the PIR9400. Refer to the PIR9400
instruction manual (95-8440) for details.
NOTE
If using a C706X detector, navigate to the “Device
Setup” menu and select the appropriate gas type
and unit of measurement.
3. To exit, activate CANCEL/ESCAPE three times to
return to the main display screen.
4. If the detector is replaced with another detector
type, the UD10 will not recognize it until the mode is
changed.
5. If the UD10 Display is in PIR9400 mode and if:
a. The connection between PIR9400 and the UD10
is removed, the UD10 will show a FAULT on the
Gas Screen. When the connection between
PIR9400 and UD10 is restored, the UD10 will
remove the FAULT indication when current
increases beyond 3.6 mA.
b. Someone removes the PIR9400 & connects
a HART enabled Gas Detector, it will not be
recognized by the UD10 Display until the mode
is changed to HART.
RTC
NOTE
The UD10 is set at the factory for US Central
Standard time.
To display and set the Real Time Clock and Date for
the UD10:
1. Using the magnet to activate the switches on the
UD10 display, navigate to the RTC menu.
Main Menu
Process Vars
Display Status
Device Status
Display Setup
Device Setup
Device Cal
Display Test
Device Test
Display Setup
Write Protect
Alarm Setting
Mode Select
HART Option
RTC
Display RS485
Input Loop Cal
RTC
Displayed
Seconds
Minutes
Hours
Day
Month
Year
2.
The first item on the RTC screen is “Displayed”.
Y (Yes) or N (NO) is shown to indicate whether
the time and date will be displayed on the main
screen. To change the setting, use the ENTER/
SELECT button to go to the next screen, then use
the PREVIOUS or NEXT buttons to toggle between
YandN.Oncethechoseninputisselected,use
the ENTER/SELECT button to enter the selection.
Use the CANCEL/ESCAPE button to exit without
changing.
3. Use the same method to set time and date.
Specifically for the GT3000 Transmitter, the RTC for
the transmitter can be synchronized to the RTC of
the display by going through the Main Menu->Device
Setup->RTC-> 1st slot “Sync W/Disp”.
Latching Alarms
The high, auxiliary and low alarm relay settings
are programmable and can be set for latching or
non-latching operation. Alarm configuration can be
done using the local display menu or external HART
interface. Latched alarms on the display can be cleared
through the Display Setup > Alarm Setting submenu
using the magnet or external HART interface.
4-20 mA LOOP CALIBRATION
Both the input and output current loops of the UD10
are trimmed at the factory. They can also be trimmed
in the field for maximum accuracy using the following
procedures. If the detector connected to the UD10 is
HART enabled, its 4-20 mA output signal can also be
trimmed.

13 95-86614.1
When the UD10 is used with a detector that supports
HART communication, the output of the detector should
be calibrated first.
HART Detector Signal Calibration
Navigate down the menu to Device Test > D/A (Digital
to Analog) Trim.
Main Menu
Process Vars
Display Status
Device Status
Display Setup
Device Setup
Device Cal
Display Test
Device Test
Device Test
Self Test
Response Test
Loop Test
D/A Trim
D/A Trim
Zero Trim
Gain Trim
Select Zero Trim. When this screen is entered, a
warning message is presented. Select ENTER to
continue. When the message “Connect Reference
Meter” is presented, install the current meter on the mA
line between the detector and UD10. Select ENTER
to continue. When the message “Set Input Current to
4mA?” is presented, select ENTER to begin the Zero
Trim function. The detector will now set its 4 mA output
value. If the value indicated on the current meter is not
4.00 mA, enter the measured value into the UD10 using
the Previous and Next switches. The UD10 calculates
and corrects for the difference between the actual and
entered values. When the current meter value is at the
desired 4.00 mA, select ENTER to accept the new zero
trim value.
Select Gain Trim. Follow the same procedure for gain/
span calibration.
UD10 Input Trim
When the UD10 is used with a detector that supports
HART communication, an automated process can be
used to trim the UD10 input. Navigate down the menu
to “Input Loop Cal”.
Main Menu
Process Vars
Display Status
Device Status
Display Setup
Device Setup
Device Cal
Display Test
Device Test
Display Setup
Alarm Setting
Mode Select
HART Option
RTC
RS485
Input Loop Cal
Upon entering Input Loop Cal, the UD10 commands
the detector to output 4 mA, and then automatically
calibrates its own input. The UD10 then commands the
detector to output 20 mA and subsequently calibrates
its own input.
If a non-HART detector is being used, the Input Loop
Cal may be performed with a mA current source or loop
calibrator connected to the UD10 Sensor Connector.
Follow the loop calibration instructions shown by the
UD10 for this procedure.
UD10 Output Trim
To calibrate the UD10 output loop, navigate down the
menu to Display Test > D/A Trim.
Main Menu
Process Vars
Display Status
Device Status
Display Setup
Device Setup
Device Cal
Display Test
Device Test
Display Test
Self Test
Response Test
Loop Test
D/A Trim
D/A Trim
Zero Trim
Gain Trim
Select Zero Trim. When this screen is entered, a warning
message is presented. Select ENTER to continue.
When the message “Connect Reference Meter” is
presented, install the current meter on the UD10 mA
output. Select ENTER to continue. When the message
“Set Output Current to 4mA?” is presented, select
ENTER to begin the Zero Trim function. The UD10
will now set its 4 mA output value. If the measured
value on the current meter is not 4.00 mA, enter the
measured value into the UD10 using the Previous and
Next switches. The UD10 calculates and corrects for
the difference between the actual and entered values.
When the current meter value is at the desired 4.00 mA,
select ENTER to accept the new zero trim value.
Select Gain Trim. Follow the same procedure for gain/
span calibration.

14 95-8661
4.1
OPTIONAL SYSTEM TESTS
The following tests are available for verifying proper
operation of various functions of the gas detection
system. The first three are accessed from the Display
Test screen. (A “Device Test” screen is available
for performing the same tests on HART enabled
detectors.)
Main Menu
Process Vars
Display Status
Device Status
Display Setup
Device Setup
Device Cal
Display Test
Device Test
Display Test
Self Test
Response Test
Loop Test
D/A Trim
Self-Test
This test commands the UD10 to perform a fully
automatic internal test. At the completion of the test,
the UD10 will indicate a pass or fail.
Response Test
This test inhibits the UD10’s outputs, thereby providing
a means of testing the system by applying gas to the
detector without activating any alarms or affecting the
output.
Loop Test
This test temporarily forces the UD10’s 4-20 mA output
to a specific level. This is an easy way to test the
output signal of the UD10 for accuracy, to verify the
capabilities of the system, and to verify the input signal
of a receiver. To perform this test, connect a current
meter to the output loop. Navigate to Display Test and
select Loop Test, then follow the prompts on the UD10
Screen.
NOTE
If the Response Test and Loop Test are
not terminated by the operator, the test will
automatically time out after ten minutes and the
UD10 will return to normal operation.
Proof Test
A Proof Test (bump test) can be performed at any time
to verify proper operation and calibration of the system.
Since this test does not inhibit the UD10’s outputs, secure
any output devices prior to performing the test to prevent
unwanted actuation.
HISTORY
There are two separate histories, one for the display
and one for the detector (if available). Both will state
the number of hours that the unit has been operating,
and the highest and lowest recorded temperature (with
time and date stamp).
PASSWORD PROTECTION
The UD10 allows the use of a password for restricting
changes to configuration parameters and limiting
access to safety critical commands. The UD10 is
shipped from the factory with the password protection
(Write Protect) feature disabled.
The following are locked when Write Protect security is
enabled:
Alarm Setting screen – All options except “RST Latch
Alarms”
Mode Select screen – All options
HART Option – All options
RTC–AlloptionsexceptDisplayedY/N
Output Mode
Display Test screen – All options
To enable the Write Protect feature, navigate to the Write
Protect screen.
Select “Change State” to toggle between Enabled and
Disabled.
Select “Change Password” to enter a new password.
“Write Protect” indicates whether password protection
is Enabled or Disabled.
The default password is 1*******.
IMPORTANT
Take care not to lose the password. Future
changes cannot be made without a password.
Main Menu
Process Vars
Display Status
Device Status
Display Setup
Device Setup
Device Cal
Display Test
Display Setup
Alarm Setting
Mode Select
HART Option
RTC
RS485
Input Loop Cal
Contrast Contrl
Output Mode
Backlight Ctrl
Write Protect
Write Protect
Change State
Change Password
Write Protect xxx

15 95-86614.1
troubleshootinG
If a Fault condition is indicated on the UD10 faceplate,
the nature of the fault can be determined by using
the magnetic tool to navigate to the appropriate Fault
screen.
NOTE
Refer to the Menu in the appropriate Appendix
of this manual for the path to the proper Fault
screen.
Shortcut: From the main display screen, touch
the magnet to the “Previous” switch to go directly
to the Fault screen.
Example:
For a Display (UD10) related fault:
Main Menu > Display Status > Fault/Status > Fault
For a Device (Sensor) related fault:
Main Menu > Device Status > Fault/Status > Sensor Fault
When the active fault has been identified, refer to the
Troubleshooting Tables for a description of the fault and
suggested corrective action.
Refer to Table 3 for Display Faults and Table 4 for Device
Faults.
Display Faults Description Recommended Action
Input Loop FLT Fault in sensor or sensor loop
Check sensor wiring.
Calibrate sensor.
Ensure that sensor type matches conguration.
Output Loop FLT Fault in 4-20 mA output loop Check 4-20 mA loop wiring for shorts or opens.
EE Fault Fault in non-volatile memory Return to factory.
ADC Ref Fault ADC reference voltage too high or low Return to factory.
24V Fault Problem in 24 volt power supply or power wiring Check power wiring and output voltage of power
supply.
Flash Fault FLASH memory Fault Return to factory.
RAM Fault Fault in volatile memory Return to factory.
WDT Fault Watchdog timer is non-functional Return to factory.
12V Fault 12 volt internal power supply out of tolerance Check power source.
Return to factory.
5V Fault 5 volt internal power supply out of tolerance Check power source.
Return to factory.
3V Fault 3 volt internal power supply out of tolerance Check power source.
Return to factory.
Table 3—Troubleshooting Guide - Display Faults
Note: A fault condition will cause an oxygen detector to generate an alarm output as the decreasing 4-20 mA signal passes
through the alarm range.

16 95-8661
4.1
Table 4—Troubleshooting Guide - Device Faults
Device Faults Description Recommended Action
Loop Fault Current loop below fault threshold Check 4-20 mA loop wiring for shorts or opens.
Supply Voltage
Fault 24 volt power supply voltage too low Verify proper wiring to the device and correct
voltage output from the power supply.
Calibration Fault Bad calibration
This fault can be caused if the calibration is
allowed to time out. If so, recalibrate.
Ensure that there is enough gas in the calibration
bottle to complete the calibration.
Ensure that the gas being used for calibration is
the correct type and concentration. It must match
the congured setting.
Memory Fault Self-detected memory fault Return to factory.
ADC Fault Self-detected ADC fault Return to factory.
Internal Voltage
Fault Self-detected voltage fault Check supply voltage.
Return to factory.
Zero Drift Sensor signal has drifted negative
Device may have been calibrated with background
gas present. Recalibrate the detector. Purge with
clean air if needed.
Temperature
Sensor Fault Temperature sensor is out of range Return to factory.
Wrong Sensor
Type Wrong sensor type is installed Sensor type must match conguration. Change
sensor or conguration.
Lamp Fault Open or shorted lamp Replace lamp.
Return to factory.
Alignment Fault Open path alignment problem Align the device as specied in the instruction
manual.
Blocked Optic
Fault Optical path is blocked Locate and remove obstruction from the optical
path.
Cal Line Active Cal line is active at start-up Ensure that the Cal line wiring is not shorted and
the switch is open.
Low Cal Line Cal line is shorted. Check wiring.
Sensor Fault Self-detected fault with the sensor
Check sensor wiring.
Calibrate sensor.
Ensure that sensor type matches conguration.
Noise Fault* Excessive noise on signal Check OPECL alignment.
Align ADC Fault* Alignment ADC saturated Check OPECL alignment.
Align Fault* Alignment fault Check OPECL alignment.
Align Warning* Alignment warning Check OPECL alignment.
DAC Fault DAC fault detected Return to factory.
General Fault Unspecied fault Verify correct power wiring and supply voltage.
Consult the factory.
High Fault Detector output is higher than specied limit Verify correct sensor type and calibration.
Low Fault Detector output is lower than specied limit Verify correct sensor type and calibration.
Dirty Optics Detector optics are dirty Perform the cleaning procedure as described in
the detector manual, then perform calibration.
Start Cal Fault Calibration fault Verify correct sensor type and calibrate.
*OPECL only.

17 95-86614.1
Device Faults Description Recommended Action
EE Fault Fault in non-volatile memory
Power may have been interrupted while the device
was updating its internal data logs. Recycle
power.
Ref ADC Sat Sensor signal level is outside the range of the AD
converter Return to factory.
Active ADC Sat Sensor signal level is outside the range of the AD
converter Return to factory.
24V Fault Problem in 24 volt power supply or power wiring Check power wiring and output voltage of power
supply.
Flash CRC Fault Memory fault Return to factory.
RAM Fault Fault in volatile memory Return to factory.
Low Voltage Power supply voltage outside of limits Check power supply voltage.
Return to factory.
Temp Fault Temperature sensor fault Return to factory.
Software Fault Internal software fault Return to factory.
EE Safety Fault Internal conguration fault Return to factory.
Gas Under Range Sensor signal has drifted negative
Device may have been calibrated with background
gas present. Recalibrate the detector. Purge with
clean air if needed.
Sensor Mismatch Wrong sensor type is installed Sensor type must match conguration. Change
sensor or conguration.
ADC CNTR Fault Internal hardware fault Return to factory.
3V Fault 3 volt internal power supply out of tolerance Return to factory.
Comm Fault Communication fault Check detector wiring and power supply.
GEN Fault Unspecied fault Verify correct power wiring and supply voltage.
Consult the factory.
12V Fault 12 volt internal power supply out of tolerance Return to factory.
5V Fault 5 volt internal power supply out of tolerance Return to factory.
Table 4—Troubleshooting Guide - Device Faults, Continued

18 95-8661
4.1
specificAtions
OPERATING VOLTAGE—
24 Vdc nominal, operating range is 18 to 30 Vdc.
Ripple cannot exceed 0.5 volt P-P.
OPERATING POWER—
Standard model, with heater and backlight off:
No alarm: 1.5 watts @ 24 Vdc.
Alarm: 3 watts @ 24 Vdc (20 mA current
loop output, and all 3 alarm relays
energized.)
Backlight on: 0.5 watt additional.
Heater on: 3.5 watts additional.
CGS model: Add 4 watts with CGS interface
board and CGS sensor installed.
Maximum power in alarm, with heater and backlight on:
7 watts @ 30 Vdc (Standard model)
11 watts @ 30 Vdc (CGS model)
NOTE
Heater turns on when the internal temperature
drops below –10°C (default operation). Heater
function can be disabled to save power.
NOTE
Appropriate relays will be activated when a fault
or alarm occurs.
CURRENT OUTPUT—
Linear isolated 4-20 mA output with HART.
3.8 mA indicates calibrate mode.
3.6 mA or less indicates a fault condition.
Maximum loop resistance is 600 ohms at 18 to 30 Vdc.
CURRENT OUTPUT RESPONSE TIME—
Toxic gas mode: T90 ≤5 seconds.
Combustible gas mode: T90 ≤4 seconds.
Combustible gas - open path mode: T90 ≤4 seconds.
UD10 w CGS: T90 <12 seconds.
CURRENT OUTPUT ACCURACY—
Toxic gas mode: <1% error.
Combustible gas mode: <1% error.
Combustible gas - open path mode: ≤0.01 LFL/M.
UD10 w CGS: ±3% LFL 0-50 range,
±5% LFL 51-100 range.
RELAY CONTACTS—
Three Alarm Relays: Form C, 5 amperes at 30 Vdc.
Selectable energized/de-energized.
Selectable latching or non-latching.
Refer to Table 1 for range and
default settings.
WARNING
When in non-latching mode, the control device
must latch the alarm output.
One Fault Relay: Form C, 5 amperes at 30 Vdc.
Normally energized for no fault
condition with power applied.
RELAY RESPONSE TIME—
≤ 2 seconds.
WIRING TERMINALS—
14 to 18 AWG wire can be used.
OPERATING TEMPERATURE—
–55°C to +75°C.
STORAGE TEMPERATURE—
–55°C to +75°C.
HUMIDITY RANGE—
5 to 95% RH (Det-Tronics verified).
ELECTRO-MAGNETIC COMPATIBILITY—
EMC Directive 2004/108/EC
EN55011 (Emissions)
EN50270 (Immunity)
DIMENSIONS—
See Figures 12 and 13.
Table of contents
Other Det-Tronics Monitor manuals