2 11/2018 Subject to technical changes. domat R560
All module settings are backed up in an EEPROM chip. The module is equipped with
a watchdog circuit.
See domat - Technical application notes for connection examples. R560 is a more
universal replacement of M550 (which has 8 inputs for passive sensors) and it can be
used also as a replacement of M500 (8 voltage inputs) for most of the applications.
Please note that the R560, unlike M500, has asymmetrical inputs (0 to 10 V rather
than -10...10 V).
____________________________________________________________________
10 V ÷ 35 V DC, 14 V ÷ 24 V AC
Communication
Galvanic isolation
Max. bus length
Max. amount of modules on the bus
Modbus RTU RS485, 1200 ... 115200 bit/s
1 kV
1200 m
256
Number of analogue inputs
Pt1000* (-50...150 °C), 20...1600 Ohm, 20...5000 Ohm, 0...10
V, 0...20 mA
*Resistance ranges may be used for temperature
measurement with Pt100, Pt1000, Ni1000/5000 and
Ni100/6180 passive sensors. Linearisation must be done in
controllers (Domat PLC… for example) just like at e.g. MCIO2
module. In the R560 module there is recalculation to °C for
the Pt1000 sensor only.
The measurement deviation for all measured variables is
0.25% of the whole range.
ModComTool 4.2.3.9 or higher parameters setting, GUI
Merbon IDE, SoftPLC IDE –predefined modbus devices
Polycarbonate box (certification UL94V0)
elbox 4
screw terminals M3 (bus, power), M2 (AI inputs)
71 (l) x 90 (w) x 58 (h) mm
External conditions: -5 –45 °C; 5 – 95 % relative humidity;
non-condensing gases and chemically non-aggressive
conditions (according to EN 60721-3-3 climatic class 3K5)
Storage: -5 –45 °C; 5 – 95 % relative humidity; non-
condensing gases and chemically non-aggressive conditions
(according to EN 60721-3-1 climatic class 1K3)