Domel Invento S15 User manual

EC –Controller
Invento S Drives
Operating and installation instructions
[Sem vnesite povzetek dokumenta. Povzetek je po navadi kratek povzetek
vsebine dokumenta. Sem vnesite povzetek dokumenta. Povzetek je po
navadi kratek povzetek vsebine dokumenta.]

EC –Controller Invento S DOMEL
1 Operating and installation Instructions V1.8, december 2015
Contents
1. GENERAL SAFETY..................................................................................................................... 2
1.1. Personal Safety..................................................................................................................... 2
1.2. Approvals, standards and certifications............................................................................ 3
2. INVENTO-S DRIVE OVERVIEW ............................................................................................... 4
2.1. Operating and ambient condition....................................................................................... 4
2.2. Mechanical and electrical specification............................................................................. 4
2.3. Functions................................................................................................................................ 5
2.4. Protections............................................................................................................................. 7
3. INSTALLATION AND CONNECTION OF INVENTO-S DRIVE ............................................ 9
3.1. General installation............................................................................................................. 10
3.1.1. Mounting and sealing.................................................................................................... 10
3.1.2. Cooling........................................................................................................................... 10
3.2. Connection instructions ..................................................................................................... 11
3.3. Grounding............................................................................................................................ 13
3.4. Installation to minimize EMI / RFI..................................................................................... 13
3.5. Connecting the electrical system...................................................................................... 13
3.5.1. Mains supply connection and fuse protection.............................................................. 14
4. MODBUS RTU............................................................................................................................ 16
4.1. MODBUS overview............................................................................................................. 16
4.2. MODBUS parameters........................................................................................................ 17
5. INVENTO-S CONTROLLER SETTINGS................................................................................ 22
5.1 Factory settings................................................................................................................... 22
5.2 Additional parameter explanation..................................................................................... 22
6. ERROR STRATEGY TABLE.................................................................................................... 26

DOMEL EC –Controller Invento S
V1.8, December 2015 Operating and installation Instructions 2
1. GENERAL SAFETY
This Installation guide contains the information necessary for safety. Installation and basic
running of the EC –Controller.
Danger!
Electric voltage on the device
EC-Drive must only be connected, installed, modified or repaired by a
qualified personnel! Incorrect mounting can cause material damage and fatal
injury from electric shock! Domel is not responsible for any damage
caused by incorrect or bad circuit connection or by non-professional
installation!
Use fuses for power lines. Install all earth wires. Before operating check the
wires for short circuits. Use only cables that meet the specified installation
requirements for voltage, current, insulation material, load etc.
Warning!
Electric voltage!
Never open EC-Controller or parts of them when the main supply is
connected. It can be extremely dangerous and could cause fatal injury from
electric shock!
When it is necessary to touch high voltages lines, disconnect the main power
supply and wait at least 5 minutes before servicing the drive.
Note!
It is the responsibility of the user or installer to ensure correct grounding and
protection in accordance with national and local standards.
1.1. Personal Safety
The [Start / Stop] input on the user interface panel of the EC drive does not disconnect the
drive from the AC line. Do not use it as a safety switch.
Do not remove the terminal lines from the motor and AC line supply while the EC drive is
connected to the active AC line. Ensure that the AC line supply has been disconnected and
wait 5 minutes before removing motor and AC lines.
The motor can be started by means of digital commands, bus commands, references or local
start command whenever the drive is connected to the AC line. Therefore, an unintended start
may occur anytime power is applied (fire mode, Start/Stop switch is on, etc.). Never service
the drive or equipment when power is applied to the drive.
Before installing and operating EC-controller please read this instruction carefully!

EC –Controller Invento S DOMEL
3 Operating and installation Instructions V1.8, december 2015
1.2. Approvals, standards and certifications
General electromagnetic compatibility: EN-61800-3
Domel declares that the products are manufactured in accordance with Council Directive
92/31/EEC on electromagnetic compatibility (and subsequent amendments).
Domel guarantees that the controller will be operating within specifications, if all
directions and
recommendations are taken into consideration. Domel does not
accept any responsibility for
failures resulting from improper of use.

DOMEL EC –Controller Invento S
V1.8, December 2015 Operating and installation Instructions 4
2. INVENTO-S DRIVE OVERVIEW
2.1. Operating and ambient condition
Protection level:............................................................................................................. IP55
Vibration max:…………………...................................................................................... 0.7 g
Relative humidity:….………...………………………………….……..........................5% - 90%
Operating temperature max:..………..……………...............................+45°C without air flow
Operating temperature min: ………….…......................................................................-10°C
Storage & transport:
Temperature max:…………………..……………………………………….…………...….+70°C
Temperature min:……………… ……………...….…………………………...…………….-25°C
Relative humidity max…….…………………………………………………………......……90%
SPECIFICATIONS, FUNCTIONS AND PROTECTIONS
2.2. Mechanical and electrical specification
Dimensions………………………………..……………………….332,3 x 309,7 x 122 mm
Weight………………………………………………………………………………..…..6,9 kg
Protection level…………………………………………………………………………….IP55
Power Supply: …………………………………………………….400V (+-10%) / 50-60 Hz
Efficiency ………………………………….…….………………………………..…up to 95%
Power Factor (PF): ………………………………….………………………………..…. >0,9
RPM min: ………………………………………………..………………...…10% of Nominal
RPM max: ………………………………………………5.000 RPM (depending on motor)
Invento S
Drives
Drive Type
Output Power
Invento S15
1,5 kW
Invento S22
2,2 kW
Invento S30
3,0 kW
Invento S40
4,0 kW
Invento S55
5,5 kW
Table 1: Invento S drive family by power

EC –Controller Invento S DOMEL
5 Operating and installation Instructions V1.8, december 2015
2.3. Functions
Relay Error function: Controller is equipped with isolated Relay error function via relay
250VAC/3A, NO(17), COM(18) and NC(19).
Relay error function is always activated when error occurs.
Reset of processor is usually necessary after fixing the cause of error (depending on error
type –see error table –chapter 6. Troubleshooting)
AN1: Analog input 1 (terminals 9,10)–Input voltage from 0-10VDC. Electronics controls speed
linear from RPM min to RPM max. Maximal or minimal speed (inverted) is defined as input
voltage 9,5V ± 3%.
To start the motor via AN1 analog input, connect Start/Stop terminal pins (3 and 4) and FIRE
mode terminal pins (1 and 2) together. Make sure you are in mode 0 (speed) or mode 1
(torque).
For additional information see chapter 5. (INVENTO-S controller parameters)
Electrical parameters: Vinmax=12V, Zin=10kΩ, Resolution 10-bit, tolerance AN1±5%
Important: Wrong polarity at input AN1 could cause serious damage on the controller.
AN2: Analog input 2 (terminals 12, 13). Input Voltage from 0 –10VDC. This input is used as
output signal from sensor (usually temperature or pressure). Terminals 14 and 13 can be used
as power supply for the sensor and terminal 12 is used as measuring/process signal from
sensor.
For additional information see chapter 5. (INVENTO-S controller parameters)
Set RPM via potentiometer: Controller is be controlled by external potentiometer (4k7 to
47kΩ) connected to terminals (9 = GND), (10 = input) and (11 = +10V). If the direction of
rotary potentiometer is incorrect, change the wires on terminal (9) and (11).
Electrical parameters: Three-wire, Rpot=4k7 - 47kΩ, Zin = 10kΩ
Power supply 10VDC/10mA: Controller is equipped with 10VDC/10mA for power supply to an
external potentiometer. Power supplying other loads is not allowed. The 10 VDC supply is
galvanically isolated from the supply voltage, but has the same potential as the analogue and
digital inputs and outputs.
Electrical parameters: 10VDC +/- 5% (regulated); 10mA; Terminal number: 10.
Power supply 24VDC/40mA: Controller is equipped with 24VDC/40mA power supply for
external sensor connected to AN2, or for small external fan for cooling controller. The 24 VDC
supply is galvanically isolated from the supply voltage, but has the same potential as the
analogue and digital inputs and outputs.
Electrical parameters: 24VDC +/- 10% (not regulated); 50mA; Terminal number: 1, 4, 14.
Speed output: Controller is equipped with an Open Collector speed output signal for speed
monitoring, and offers some additional choices for process control.
For additional information see chapter 5. (INVENTO-S controller parameters)
Fire mode function: Controller is equipped with Fire mode function. In this case electronics
runs as emergency controlled unit, (for example: extract the smoke from a burning building),
with disabled protections and functions. Fire mode is activated by opening terminals 1 and 2
and enabling it via settable parameter.

DOMEL EC –Controller Invento S
V1.8, December 2015 Operating and installation Instructions 6
In Fire mode all errors are disabled, but power derating function is still active.
Electrical parameters: Operating voltage = 24V, Zin=10kΩ
Note!
Fire mode function is used only for protection in case of a burning
building, to extract the smoke from it. In normal conditions, fire mode
function is not used. In this case Domel is not responsible for damage
to the controller caused by improper use.
Star/Stop function: Controller is equipped with Start/Stop switch. If the controller has all
conditions for running, the motor starts when the terminal pins (3) and (4) are connected
together (switch ON). Reference is red from AN1 analog input. This function is enabled in
mode 0 (AN1 value = scaled speed reference), mode 1 (AN1 value = scaled torque reference)
and mode 4.
Electrical parameters: Operating voltage = 24V, Zin=10kΩ
LED indicators: LEDs are currently used to indicate code running on PIC processor and SPI
communication between processor in following manner:
RED LED blinking slow: Indicates code running on PIC processor
GREEN LED blinking fast: Indicates SPI communication between processors
This is normal state during controller operation and should be always present.
When controller is reset, green led stops blinking and only red led is active. This happens as
the PIC processor starts operating quickly after reset (red led blinking), but the SPI
communication between processor is not yet active (green led not blinking-either lit or not). As
soon as the communication between processors is established, green led starts blinking too,
usually after a few seconds after reset.
Modbus RTU 485 serial communication: Controller is equipped with Modbus RTU 485
communication. To connect controllers into chain use only shielded cables.
Fig.1:Shielded cable for ground connection between controllers is necessary

EC –Controller Invento S DOMEL
7 Operating and installation Instructions V1.8, december 2015
2.4. Protections
Thermal protection: Function that limits thermodynamic stresses on electronics by limiting
power. This function is a temperature limiter which reduces the output power, when
temperature on the controller reaches 95°C (is settable via Modbus as pderate_Tlow). The
power is decreased until it reaches a settable minimum value of torque.
Fig.2: Power derating with associated parameters
In the event that the temperature of controller is still rising the controller stops the motor.
When the temperature of controller falls below pderate_Tlow, controller automatically restarts.
Power derating function is enabled, but the overheating error is disabled in Fire mode.
Under and over voltage: Controller is equipped with under and over voltage protection.
Electronics shuts down when the main voltage is not in the required range.
Motor phase loss: Controller is equipped with power supply phase loss detection. In this case
controller stops the motor. Error is usually triggered at relatively high RPM, when the algorithm
can reliably detect 100Hz component in DC link.
Overcurrent protection: Controller is equipped with software and hardware phase
overcurrent protection. Software overcurrent error triggers when current exceeds fixed limit
(cannot be changed via modbus) and hardware overcurrent error triggers when current
exceeds limit, set by resistors on current measuring chipset .
Ground current fault: This protection triggers an error, when the sum of the motor currents is
more than 3A. Check the motor if it is damaged (cables, winding, etc.).
Parameters CRC: CRC check routine reports an error if reading/writing of parameters into
EEPROM is corrupted.
Drivers fault: This protection triggers an error, if high and low side of the motor phase
transistors are open at the same time.

DOMEL EC –Controller Invento S
V1.8, December 2015 Operating and installation Instructions 8
ADC offset fault: Error in ADC reading on current measurements or DC link voltages. Reset
of electronics is necessary.
SPI comm fault: Triggered when communication between processors is lost.
System error: Error in software(state machine error). Reset of the electronics is necessary.
Invento S Drive will not run if errors (non-autorestart) are present (see chapter 5).
Usually processor or Drive reset is required . Processor reset can be made via Modbus
( address 1 in coils tab ) or by disconnecting and reconnecting the main power supply
( hard reset ). As you disconnect the controller from power supply wait until LED
indicators stop flashing before reconnecting.
Note!
Heating the controller over the maximal temperature is not allowed.
Above 105°C (adjustable) controller stops the motor, and restarts it again
when the temperature of controller falls below 95°C (adjustable). However, if
the controller is overheating and motor was shutdown, disconnect power
supply (safety switch) and wait at least 20 minutes before you service them.
In case of controller overheating, it`s housing and components might still be
very hot and could cause serious damage to your skin.
If controller starts overheating over lower adjustable temperature limit during
running, it will limit the output power. In this case add small 24V/40mA fan on
controller or ensure air flow through the ribs. Fan can be supplied by power
from controller (page 15 –wiring diagram). Overheating problem appears in
the case of installation of the controller in the space without air flow. Avoid
installing controller on direct sunlight.

EC –Controller Invento S DOMEL
9 Operating and installation Instructions V1.8, december 2015
3. INSTALLATION AND CONNECTION OF INVENTO-S DRIVE
Use shield / armoured motor cable to comply with EMC emission specifications, and connect
this cable to both the decoupling plate and the motor metal.
Use only hard wire or fibre copper wire with ferrule (Fig 1).
Keep motor cables as short as possible to reduce the noise level and leakage currents. To
reduce the operating problems, use a shielded cable. Max length of cables is shown in the
table below.
Fig.3: Wire with ferrule
Table 1: Length of cables
Fig.4:Proper wire connection to the motor and mains terminals.
Invento S
Length
max [m]
Power supply
-
Relay Fault
-
Set RPM via
voltage
-
Set RPM via
potentiometer
20
Speed Output
-
Fire mode
40
Start/Stop
40
Modbus
40
Motor
5

DOMEL EC –Controller Invento S
V1.8, December 2015 Operating and installation Instructions 10
3.1. General installation
Correct and precise mounting of the controller is required to provide reliable and carefree
operation.
The assembly should only be carried out by qualified personnel, because proper mounting,
cooling
and sealing of controller is required. Mounting is permitted only at prescribed places.
All positions
are allowed if conditions for solid attachment and adequate cooling are fulfilled (to
prevent
overheating of electronic).
3.1.1. Mounting and sealing
We recommend horizontal (on table) or vertical (on wall, with cable glands pointing down)
attachment of the electronics. In horizontal installation we also recommend mounting on 2°-5°
angle with glands pointing down, for easier drainage of surface liquids. Suitable sealing for top
cover and all glands should be provided at mounting (whether there are cables or not). Space
between other objects and controller must be at least 20 mm (from the closest corner of the
electronics). When attaching to metal surfaces, the M5x15 screw (according to DIN912) with
spring washers is recommended. When attaching to non-metal materials the M5x70 screw for
walls is recommend.
3.1.2. Cooling
For smooth operation it is necessary to provide the required thermal conditions. We
recommend force cooling, with speed 1.5 m/s of fresh cooling air, through the cooling ribs,
although is possible to have cooling only with natural convection1. By cooling with natural
convection, the user should ensure at least 1 m of space over the highest cooling rib and also
controller may not be located in an enclosed place or placed under direct sunlight.
Note: Cooling exclusively with natural convection decreases lifetime of electronics.

EC –Controller Invento S DOMEL
11 Operating and installation Instructions V1.8, december 2015
3.2. Connection instructions
a) Remove the Top cover of the terminal strips and unscrew the cable glands No3 (Fig.2). Insert
the motor cable through and mount the shield and connect the motor wires (U, V, W) to the
corresponding terminal. Motor PE wire (yellow-green wire) can be connected to the terminal
or screwed directly to the housing (Fig.2).
b) Fig.3 shows how to properly connect wire to the motor and mains terminals
c) Remove the sealing insert for sealing cable gland No1 and insert the communication cable.
Mount the cable and carefully (fig. 4) connect desired user interface terminals. Screw the
cable gland for optimum IP protection.
d) If Fault Relay function is needed then unscrew the cable glands No2. Connect the wires for
Relay Fault to the corresponding terminals. Tighten the cable gland for optimum IP
protection. Do not use the same cable gland for Relay Fault as for communication cable. It
could cause operating problems and unstable control signals due to noise.
e) Connect mains supply wires to the corresponding terminals in the following sequence:
(1) PE ; (2) L1 ; (3) L2; (4) L3 ;
f) If there is some blank cable gland, fill it with sealing inserts.
g) Check all connections again.
h) Carefully replace the Top cover back and connect the Power supply voltage.

DOMEL EC –Controller Invento S
V1.8, December 2015 Operating and installation Instructions 12
Fig.5: How to Connect / Disconnect wire
Warning!
Use cable with minimal 7mm thickness. All unused glands must be closed.
Use appropriate sealing insert or appropriate stopper if cable is not used.
Top cover must be screwed with 1Nm of torque and all screws must be used.
These actions must be done to avoid exceesive humidity and possible fluid
leaks inside the controller.
Fig.6:How to operate correctly with terminal strips
Warning!
Press only 0,5kg max, 4mm deep at angle 45° with 3mm slot
screwdriver. Damaged terminal strips can cause serious damage on
the Controller and fatal injury from electric shock.
Note!
It is the responsibility of the user or installer to ensure correct
grounding and protection in accordance with national and local
standards.

EC –Controller Invento S DOMEL
13 Operating and installation Instructions V1.8, december 2015
3.3. Grounding
Comply with the following at installation:
Safety grounding: The drive has a high leakage current and must be grounded
properly for safety. Follow all local safety regulations.
High frequency grounding: Keep grounding cables as short as possible.
Connect all grounds to ensure the lowest possible conductor impedance. The lowest possible
conductor impedance is achieved by keeping the conductor as short as possible and by
grounding with the greatest possible surface area.
3.4. Installation to minimize EMI / RFI
To minimize conducted and radiated high frequency emissions :
Use only shielded/armoured motor cables and shielded/armoured control
cables.
Connect the shield to ground at both ends.
Use attached cable clamps for installation to provide shielding at high
frequencies.
Fig.7a: Correct grounding Fig.7b: Incorrect grounding
Correct grounding to minimize EMI/RFI emissions: Fig.7a
Control cables and cables for serial communication must be attached with cable clamps at both ends
to ensure maximum possible electrical contact.
Incorrect grounding: Fig.7b
Do not use screen ends that are twisted together –that will increase screen impendence at higher
frequencies.
3.5. Connecting the electrical system
Check whether the data on the type plate matches with the connection data.
Before connecting the device, ensure that supply voltage matches operating voltage of the
device.
Only use cables that are configured for the current according to the specification on the type
plate.
PE PE
Correct grounding
PE
PE
Incorrect grounding

DOMEL EC –Controller Invento S
V1.8, December 2015 Operating and installation Instructions 14
3.5.1. Mains supply connection and fuse protection
Invento S
Drive Type
Nominal
Nominal
output
power
Input
current
at max
load
Safety
fuse
Cable cross -
section
voltage
(max )
mm2
AWG
Power
Supply
Invento
S15
400 V
1,5 kW
3,1 A
16 A
2,5
13
Invento
S22
2,2 kW
5,0 A
16 A
Invento
S30
3,0 kW
6,3 A
16 A
Invento
S40
4,0 kW
8,4 A
16 A
4
11
Invento
S55
5,5 kW
11,5 A
16 A
User
control
0,5 - 2,5
20 - 13
Table 2: Invento S drive family electrical specifications
Install fast response gG fuses to protect the controller from damage if short circuit occur. If UL should
be complied with, use UL fuses like Bussmann type RK1 / KTS –R(x), Bussmann type J / JKS –(x),
SIBA type RK1, Ferraz –Shawmut type CC or RK1,...
Connect the device only to the circuits that can be switched off using an
all-pole disconnecting switch.
Do not try to run motor unloaded (no wheel on motor shaft) if it was
preset for a certain fan with specific moment of inertia.

EC –Controller Invento S DOMEL
15 Operating and installation Instructions V1.8, december 2015
Table 3: Terminal/Pin description
Terminal
number
Description
Control
+24V
1,4,14
+24 VDC ± 10% / Imax 40 mA
Fire
2
Digital input; FIRE mode: Enabling function –open pin;
Disabling Bridge to +24 V
Start/Stop
3
Digital input; Start/Stop mode: Disabling function –open pin;
Enabling Bridge to +24 V
A
5, 7
Bus connection RS485 –A; MODBUS RTU
B
6, 8
Bus connection RS485 –B; MODBUS RTU
GND
9, 13, 15
I/O ground
AN1
10
Analogue Input 1; Set value 0-10 V or 10-0 V; R ≥ 1 kΩ
+10V
11
+10 V ± 5 % / 10 mA for potentiometer
AN2
12
Analogue Input 2; Sensor signal ( 0-10 V )
Speed
16
Digital output; NPN open collector output
Relay Fault
NC
17
Normally close
COM
18
Common connection; Contact rating 250V / 5A
NO
19
Normally open
Motor
PE
Motor connection
U
V
W
Mains supply
PE
PE connection
L1
Supply voltage
L2
L3

DOMEL EC –Controller Invento S
V1.8, December 2015 Operating and installation Instructions 16
4. MODBUS RTU
4.1. MODBUS overview
The MODBUS RTU protocol is based on the built-in RS-485 (EIA-485) interface. RS-485 is a two-wire
bus-interface that allows multi-drop network topology i.e. nodes can be connected as a bus (daisy
chain), or via drop cables from a common trunk line.
Domel’s Invento S drives uses the two-wire system where the communication between master and
slave is half-duplex, i.e. it cannot transmit and receive at the same time. Each signal uses one twisted-
pair line —two wires twisted around themselves. The signal on one wire is ideally the exact opposite
of the signal on the second wire. Since RS-485 is a multipoint communication system, all devices are
connected to the single twisted-pair cable.
The Modbus RTU uses master/slave architecture, where each slave device has its unique address
and responds only to packets addressed to this device. The packets are generated by the master
(Controller), which periodically polls all connected slave devices. Data travels over the single line in
both directions.
One or more EC drives can be connected to a control (or master) using the RS-485 standardized
interface. Maximal number of IFT EC Drives connected to the network is 32. If more than one
frequency converter is connected to a master, use parallel connections. Modbus user interface uses
terminals (5) (6) in parallel connection with (7) (8) (see page 17).
Parallel connections
“Daisy chain” connection

EC –Controller Invento S DOMEL
17 Operating and installation Instructions V1.8, december 2015
Default Configuration (set by Domel):
MODBUS address: 80
Baud Rate: 19200
START Bit: 1
STOP Bit: 1
Parity: NONE
Supported MODBUS commands:
0x01: Read Coils
0x02: Read Input
0x03: Read Holding Registers
0x04: Read Input Register
0x05: Write Single Coil
0x06: Write Single Holding Register
To connect PC and DOMEL Invento S Drive over serial line (MODBUS) RS-232/USB to RS-485
Converter is needed. We recommend ADAM-4561 converter.
The ADAM-4561 device driver can be used in combination with Windows 2000/XP/Vista/7 (32 & 64-
bit).
4.2. MODBUS parameters
1. Configuration
MODBUS RTU: 19200-8-N-1
Slave addr: 0x50 (HEX) or 80 (DEC) (default settable by MB_ADR:009)
Coils
Address
Function
Range
Description
0
Motor ON/OFF
0-1
Indication, 1=ON, 0=OFF
1
Reset Controller
0-1
1=Reset controller
2
Fire active
0-1
1=Fire mode active

DOMEL EC –Controller Invento S
V1.8, December 2015 Operating and installation Instructions 18
Discrete status bits (inputs)
Address
Function
Range
Description
0
Under Voltage
0-1
1=Voltage too low to run
1
Over Voltage
0-1
1=Voltage too high to run
2
Over Current SW
0-1
1=Software IGBT current protection
3
Over Temperature
0-1
1=Controller too hot to operate
4
Phase Loss
0-1
1=Main power supply phase loss
5
Ground Current Fault
0-1
1=Asymmetrical Load (sum of all currents >3 A)
6
Parameters CRC
0-1
1=Parameter checksum failed (TBD)
7
Drivers Fault
0-1
1=Failed transistor driver initialization
8
ADC Fault
0-1
1=ADC conversion error
9
SPI Comm Fault
0-1
1=No communication between processors
10
Power Derate Active
0-1
1=Controller entered power derating
11
Power Derate Shut Down
0-1
1=Controller reached end temperature (motor stop)
12
Over Current HW
0-1
1=Hardware IGBT current protection
13
FLW Active
0-1
1=Field weakening active
14
System error
0-1
1=State machine fail
Input Registers
Address
Function
Resolution
Unit
0
Speed
1
RPM
1
Stator current RMS
0.01
A
2
Power
1
W
3
Torque
0.01
Nm
4
IGBT Temperature
0.01
°C
5
uC Temperature
0.01
°C
6
DC Bus Voltage
0.1
V
7
5V supply
0.001
V
8
15V supply
0.001
V
9
Analog Input 1
0.01
V
10
Analog Input 2
0.01
V
11
Speed output voltage
0.01
V
12
Speed output current
0.01
mA
13
AN2 reference
0.01
V
14
AN2 sensor signal
0.01
V
15
current ramp value
1
-
16
max ramp value
1
-
17
Torque reference
0.01
Nm
18
ErrorCode
1
-
19
Fire Minutes
1
min
20
Fire Days
1
day
21
Fire Cycles
1
-
22
Operation Minutes
1
min
23
Operation Days
1
day
24
AccessCount
1
-
25
OpDaysTotal
1
day
26
Controller version
1
-
27
Firmware version
1
-
28
Speed reference
1
RPM

EC –Controller Invento S DOMEL
19 Operating and installation Instructions V1.8, december 2015
Address min max units access level Factory value
0 0 10000 0.01% 1 10000
Sets the reference point for modes 2(SPEED), 3(TORQUE) and AN2 input.
●
SPEED reference is calculated as: (current reference value can be seen in input register tab at address 28)
●
TORQUE reference is calculated as: (current reference value can be seen in input register tab at address 17
●
AN2 : Sets reference for AN2 feedback sensor signal. Reference value can be seen in input register tab at
address 13
1 0 1 * 3 0
Sets the direction of rotation of the motor shaft.
0: (CCW) CounterClockWise direction
1: (CW) Clockwise direction
Direction cannot be changed during motor run.
2 0 5000 RPM 2 & 3 motor dep.
Sets the minimal setable RPM reference. Parameter uses value on level 3 as minimum value for level 2. Controller uses
level 2 value for operation. (level 3 minRPM = 200 => level 2 minRPM = 200+)
3 0 5000 RPM 2 & 3 motor dep.
Sets the maximal setable RPM reference. Parameter uses value on level 3 as maximum value for level 2. Controller uses
level 2 value for operation.
RPM reference can be set between minimal RPM and maximal RPM limits defined in level 2. Level 3 values are just for
limiting level 2 values.
4 1 50 RPM 2 30
Sets maximum diference between actual and reference (ramp) value.
5 1 1000 * 2 350
This parameter affects motor acceleration, by affecting ramp value in relation to difference between the actual speed
and reference. Motor accelerates faster if gap between actual and reference speed is bigger.
6 1 50 RPM 2 20
Sets maximum diference between actual and reference (ramp) value, when AN2 input is active.
7 1 1000 * 2 100
This parameter is used for ramp calculation when AN2 sensor signal is used. It directly regulates AN2 input without any
PID controllers. User sets this value depending on application. Higher values are for fast processess (pressure) and lower
for slow processess (thermodynamics)
8 0 32767 * 1 *
This parameter is used for setting access levels, restoring to factory settings, reading/writing to EEPROM.
0: Enter level 1, most parameters are locked
1: Enter level 2, user can change parameters requiring level 2 and level 1 access
31114:
Enter level 3, user can change most of the parameters
10000: store values to EEPROM at current level
10001: restore values from EEPROM (last saved values)
10002: restore default values from one level above current
10011: restore level 3 parameters from factory settings
10020: set previous value as password (will not be accepted if password matches 10000.11000 or access level is<1)
6+6666: restore all parameters from factory settings
9 2 147 * 2 80
Sets modbus address.
10 032767 * 1 0
Selects current controller operation mode. Available modes are:
0:
AN1 Speed mode: Speed reference is set as:
Operation Mode
Minimal RPM
Holding registers
Maximal RPM
Ramp gain value
Ramp gain value AN2
Password
SETPOINT
DIRECTION
Description
Speed Variation
Speed Variation AN2
Modbus Address
=010000
10000
< ; =
>; =
[] = 3
2
3
1 1 20
1 1 21
1 / 1
= + 1
1 1 ( )
This manual suits for next models
4
Table of contents
Other Domel Controllers manuals