4. Maintenance
The equipment must be cleaned regularly with a clean, dry cloth (no detergent) to
avoid obstructing its ventilation grids.
5. Installation guidelines
This equipment is intended to be integrated into a electrical housing.
Wiring terminal block on the back of the device must be accessible to the end user.
No electrical conductor must not come into contact with the internal circuitry of the
device to avoid the risk of electrocution for the operator.
A breaker must be installed between the power source and the device to facilitate the
power-on or off.
This circuit breaker or fuse must be installed so as to be easily accessible to the
operator.
The appliance must not be installed in an environment not meeting the conditions
mentioned in this document.
Protection against over-currents: This unit contains no internal fuse. The installation
of an external fuse 1 A / 275 Vac is highly recommended.
The evacuation of the heat generated by the internal circuitry of the apparatus is
effected by the air vents in the electrical housing. These vents must not be blocked.
I / O device must be connected to loads whose magnitudes (voltage, current, ...)
meet the maximum values specified in this document..
5.1. Mounting
The housing is built to DIN panel 96 x 48.
•Prepare the panel with opening according to the dimensions shown below
(mm).
•Remove the brackets and insert the unit into the opening and cut. Reinsert the
brackets then screw them so well plate rubber seal against the panel
Be careful ! Once in position, the unit should not be too close to a
heat source or exposure to vapors or spray liquids.
Electromagnetic precautions: Power cables connected to terminals
must be kept away from any electromagnetic source possible.