
69-1122 4
TD41 HEATING/AIR CONDITIONING THERMOSTAT
Observe system operation for at least one cycle on
both heating and air conditioning. To observe:
Place the system switch at the HEAT position and
the fan switch at AUTO. Move the temperature
setting lever 10°F (6°C) above room temperature. The
heating equipment should turn on. A short warmup period
may be required before the system fan turns on.
Place system switch at the COOL position and move
the temperature setting lever 10°F (6°C) below
room temperature. The air conditioning equipment should
turn on and the system fan should turn on.
NOTE: Some systems have a time delay that can
prevent operation up to five minutes.
Turn the fan switch to ON. The system fan should
turn on and operate continuously. The system
blower should continue to operate at any system switch or
thermostat setting.
6 THERMOSTAT SETTING
Place the system and fan switches at the desired
settings for operation.
7 TROUBLESHOOTING
Your Duracraft Thermostat requires little or no
attention; most problems occur as follows:
NOTE: If your system is heating-only or air conditioning-
only, disregard sections not applicable to your
system.
Sympton Problem Corrective Action
No heat System switch is at OFF or COOL
position. Move switch to HEAT position.
Blown fuse or tripped circuit
breaker. Replace fuse or reset circuit breaker.
Furnace power switch is at OFF. Switch to ON.
No pilot light. Relight pilot flame per furnace manufacturer
instructions.
Improper connections to
thermostat. With power to furnace off, tighten all
mounting and terminal screws. Repair frayed
or broken wires.
Defective thermostat. (Here’s how
you know: Remove the thermostat
from the wall. Disconnect wire from
W terminal. Thermostat is
defective if the burner comes on.)
Exchange the thermostat (see Warranty).
Other. Contact a qualified service technician for
assistance.
No air conditioning System switch is in OFF or HEAT
position. Move switch to COOL position.
Blown fuse or tripped circuit
breaker. Replace fuse or reset circuit breaker.
Compressor switch (located
outdoors) is turned off. Move switch to ON position.
Improper connections to
thermostat. With power to furnace off, tighten all
mounting and terminal screws. Repair broken
wires.
Defective thermostat. (Here’s how
you know: Remove the thermostat
from the wall. Disconnect wire from
Y terminal. Touch Y wire to
terminal R. Thermostat is defective
if the compressor starts. Some
systems have a time delay, so
allow at least five minutes.) See
Caution in Step 5.
Exchange the thermostat. See Warranty.
Other. Contact service technician for assistance.