orDownarrowbuttonswillallowselection
ofsixdifferentfixedlouverpositionsor
auto(oscillation)mode.Thesequenceis
01,02,03,04,05,06andAuto.Oncethe
desiredsettingisselected,presstheFan/
Louverbuttonmomentarilyorletidlefor
10secondstoexitthelouversetmode.
WhilethecontrolisintheOnmode,
thelouverwillremainin theselected
louverposition.IfAutolouveroperation
isselected,thelouverwilloscillateonly
whenthefanisrunning.Whenthecontrol
isturnedoffviatheON/OFFbuttonthe
louverwillreturntotheclosedposition.
Forcoolingoperationfirstturntheunit
onviatheON/OFFbutton.SelectCool
modeviatheMODEbutton.Theroom
temperatureandsetpointtemperature
willbedisplayed.Thesetpointtempera-
turecanbechangedwitheachsucces-
sivepressoftheUporDownarrowbut-
tonsorbyholdingthebuttonin.
Placethesetpointtemperaturebelow
theroomtemperature.Thecompressor
willstartandcoolingwillcontinuefora
minimumoftwominutesandaslongas
thesetpointremainsbelowroomtemper-
ature.Oncetheroomtemperatureissat-
isfiedforatleast60secondsandthetwo-
minuteminimumruntimehaselapsed
thecompressorwillcycleoff.Thefanwill
operateasdescribedin"FanOperation".
OTE:Once the compressor is_'_
witched off, or after a power outage |
here is a three-minute delay before |
he compressor will re-start. J
J
_,_Optional Electric Heat Operation
(Non Heat pump condenser units only):
For operation with electric heat the
control must first be configured properly
(Heat source - "ON", Heat pump -"OFF").
See: Configuration Interface mode.
For electric heat operation, first turn the
unit on via the ON/OFF button. Then se-
lect Heat mode via the MODE button. The
room temperature and setpoint tempera-
ture will be displayed. Press either the
Up or Down arrow buttons to change the
setpoint temperature. The setpoint tem-
perature will change by one degree with
each successive press of the Up or Down
arrow buttons. Holding the button in will
change the temperature rapidly.
Place the setpoint temperature above
room temperature. The electric heat will
energize and heating will continue as
long as the setpoint remains above room
temperature. When the room temperature
has been satisfied for at least 60 seconds
and the two minute minimum on time has
expired, the electric heat will switch off.
The fan will operate as described in "Fan
Operation".
_'_ Optional Heat Pump With Electric
Heat (2-stage heating):
For heat pump operation with electric
heat the control must first be configured
properly (Heat source - "ON", Heat pump -
"ON"). See: Configuration Interface mode.
For heat pump operation with backup
electric heat, first turn the unit on via the
ON/OFF button. Then select Heat mode
via the Mode button.
The room temperature and setpoint
temperature will be displayed. Press either
the Up or Down arrow buttons to change
the setpoint temperature. The setpoint
temperature will change by one degree
with each successive press of the Up or
Down arrow buttons. Holding the button in
will change the temperature rapidly.
Place the setpoint temperature above
the room temperature by one degree. The
compressor will start and heating will con-
tinue for a minimum of two minutes and as
long as the setpoint remains above room
temperature. When the room temperature
has been satisfied for at least 60 seconds
and the minimum on time has elapsed,
the compressor will switch off. The fan will
operate as described in "Fan Operation".
Next, place the setpoint temperature
above the room temperature by at least
two degrees. The compressor will start
and, the electric will also energize after a
30 second delay, thus two-stage heating.
The electric heat will run for a minimum
of two minutes and until the deviation