BI0xF01KNX
4BI0xF01KNXFI00020100_UM_EN_1.0
1. Introduction to the user manual
This manual is intended for use by KNX installers and describes
functions and parameters of the BI04F01KNX and BI08F01KNX
devicesandhowthesettingsandcongurationscanbechanged
using the ETS software tool.
For the technical data of the device and the compatible accesso-
ries, please refer to the datasheet of the device itself.
Meaning of the symbols used
WARNING - The operation or phase described must be
carried out in compliance with the instructions provided
and with the safety standards.
IMPORTANT NOTE - Detailsandspecicationstobere-
spected for the correct functioning of the device.
2. Product overview
The BI04F01KNX and BI08F01KNX devices are equipped
with 4(8) inputs for interfacing dry contacts, for example sen-
sors,switchbuttonsandcanbeconguredforsendingon/o
commands, dimmers, roller shutters, scene recall and sequen-
ces to the bus.
Thedigitalinputscanbecongured for long or short distan-
ces.
The lines (long distance) can be monitored using an end of
line resistor (EOL) of1.8KΩ[1/8W]valuewhichallowsthede-
vice to manage sensors with a higher level of safety such as
magnetic contacts, motion detectors.
The pulse counter function is also available for counting the
switching on inputs congured as digital at short distance. On
the front panel there is a LED to display the status of each input.
Theinputs(forBI08F01KNXonlyinputs1,3,5,7)canbecon-
gured as analogue for the connection of NTC temperature pro-
bes(seeeelectronprobescodeTS01A01ACC/TS01B01ACC
/TS01D01ACC) withwhich tosend thetemperature measure-
ment on the bus or manage a complete thermostat module. The
thermostat manages 2 stages with an integrated PI controller for
controlling heating and cooling equipment, valves, 2 and 4-pipe
fan coils, etc.
Twoinputscanbeconguredas“smart sensor” for connection
of the plug-in sensors: SM03E01ACC that includes a di tempera-
ture sensor (range from -5°C to +50°C) and a CO2 sensor (range
from 10 ppm to 1000 ppm) and SM03E02ACC that includes a
temperature sensor (range from -5°C to +50°C) and a VOC sen-
sor for measuring Indoor Air Quality (IAQ) and CO2 equivalent
(eCO2).
Moreover, 10 logic blocks are available to implement sim-
ple expressions with logical or threshold operator or complex
expressions with algebraic and conditional operators; It is possi-
bletousepredenedalgorithmsasproportionalcontrolsoftem-
perature and humidity or dew point calculation.
Device is equipped with KNX communication interface and is in-
tended for installation on DIN rail in LV distribution switchboards.
3. Installation instructions
The device can be used for permanent internal installations in
dry places.
WARNING
• When a clear separation between the low voltage (SELV)
and the dangerous voltage (230V) is NOT possible, the de-
vice must be installed maintaining a minimum guaranteed
distance of 4 mm between the dangerous voltage lines or
cables (230V not SELV) and the cables connected to the
EIB/KNXBUS(SELV).
• The device must be mounted and commissioned by an au-
thorized installer.
• The applicable safety and accident prevention regulations
must be observed.
• The device must not be opened. Any faulty devices should
be returned to manufacturer.
• For planning and construction of electric installations, the re-
levant guidelines, regulations and standards of the respecti-
ve country are to be considered.
• KNX bus allows you to remotely send commands to the
system actuators. Always make sure that the execution of
remote commands do not lead to hazardous situations, and
that the user always has a warning about which commands
can be activated remotely.
For more information: www.eelectron.com.