4. Conguration and commissioning
Thecongurationandcommissioningofthedeviceismadewith
theETS®(EngineeringToolSoftware).Forthecongurationof
the device parameters the corresponding application program or
the whole eelectron® product database must be loaded in the
ETS® program.
The commissioning of the device requires the following steps:
• connect the bus KNX (1)
• turn on the bus power supply
• press the programming button (2); the red programming
LED (visible through the device lens) turns ON
• download into the device the physical address and the con-
gurationwiththeETS®program
5. General parameters
Communication objects involved:
“<General> Heartbeat” 1 Bit CRT
“<General> Primary Heartbeat” 1 Bit CW
“<General> Primary Alarm” 1 Bit CRT
“<General> Alarms x - y” 4 Bytes CRT
KNX PARAMETER SETTINGS
Delay in sending telegrams on
power-up 5 ÷ 15 seconds
Through this parameter it is possible to set the telegram transmission
delay after switch-on by selecting the time beyond which the device is
authorized to send telegrams.
In large systems after a power outage or shutdown, this delay avoids
generatingexcessivetraconthebus,causingslowperformanceor
a transmission crash.
If there are several devices that require telegrams to be sent on the
busafterareset,thesedelaysmustbeprogrammedtopreventtrac
congestion during the initialization phase.
Input detection and object values are updated at the end of the trans-
mission delay time
At the end of ETS programming, the device behaves as it did after it
was switched on.
Heartbeat
(periodic alive notication)
nothing
periodic
on request
Through this parameter you can enable the object “<General> Heart-
beat”fornoticationofthecorrectoperationofthedevice:
• nothing: heartbeat function disabled;
• periodic:youcandenetheintervalandthemessagesentonthe
busforthenoticationofthestatus;
• on request: no message is sent but the object can be read through
the object “<General> Heartbeat”.
Telegram value o/on/toggle
This parameter denes the telegram sent by the object “<General>
Heartbeat”. The value “toggle” is only available in case of periodic
sending.
Period - time unit seconds / minutes / hours
ThisparameterdenestheunitofmeasuresoftheHeartbeatperiod.
Period - time value 1 ... 255
Thisparameter denes thetime intervalfor sendingthe “<General>
Heartbeat” object.
Physical address main line 0 ... 15
This parameter denes the physical main address of the surveilled
devices (e.g. 10.13.x --> 10).
Physical address sub line 0 ... 15
Thisparameterdenesthephysicalsubaddressofthesurveilledde-
vices (e.g. 10.13.x --> 13).
Alarm time - hours 0 ... 23
Thisparameterdenesthe surveillance time(hours)before sending
the alarm. Used by the surveillance modules when the alarm function
is enabled.
Alarm time - minutes 0 ... 59
Thisparameterdenesthesurveillancetime(minutes)beforesending
the alarm. Used by the surveillance modules when the alarm function
is enabled.
Warning time - seconds 20 ... 255
Thisparameterdenesthewarningtime(seconds).Thistimeindicates
how much before the end of the surveillance time a group value read is
sent on the bus through the “Warning Read Request” object. Used by
the surveillance modules when the warning function is enabled.
Surveillance priority primary / secondary
Thisparameterdenesifthedeviceistheprimarysurveillancedevice
or if it is the secondary one. If secondary is selected, the heartbeat
period of the primary device must be aligned to the one of the primary
device itself. If no message is received in the period an alarm message
is sent on the object “<General> Primary Alarm” and the secondary
device starts to surveil the plant.
Primary period - time unit seconds / minutes / hours
ThisparameterdenestheunitofmeasuresofthePrimaryHeartbeat
period.
Primary period - time value 1 ... 255
Thisparameter denes thetime intervalfor sendingthe “<General>
Primary Heartbeat” object.
Number of surveillances
Thisparameterdenesthenumberofsurveillancemodules.
Button function
none
reset alarms and start surveil-
lance
Deneswhethertousethe
LOGIC MODULE BLOCCO CAD
Data / Date
Descrizione / Description Scala / Scale
Nome del file / File name
Codice acquisto / Purchase code
Revisione / Revision
Via Claudio Monteverdi 6
20025 Legnano (MI)
email: info@eelectron.com
Disegnatore / Designer
1:1
1.0
1/1
Questo disegno è di proprietà di Eelectron Spa -Via Caludio Monteverdi 6, 20025 Legnano (MI). Senza l'espressa autorizzazione scritta, non può essere riprodotto nè divulgato a terzi.
Property of Eelectron SpA - Via Caludio Monteverdi 6, 20025 Legnano (MI). The copy or forward to third parties without permission is forbidden.
29/03/2022
Federica Gusa
Claudio Crespi
LM00B01KNXDM00030100
CA4V_REV1
Foglio / Sheet
Supervisore / Supervisor
1
2