Elnur powered by Gabarrón | MATTIRA | Installation Guide 4
3.4 Safety Devices
Safe operation under various conditions is ensured \by
the following controls fitted inside the boiler:
• Water flow switch that monitors water flow in the
heating system and will prevent operation in case
of a blockage, if the system flow rate is below the
permitted level, error E3 will appear. Installation of
a system by-pass may be necessary (see 7.3
HEATING SYSTEM FLOW SWITCH – E3 ERROR & SYSTEM
BY-PASS REQUIREMENTS).
• Heating system high limit safety thermostat will
prevent operation if the temperature exceeds 100ºC.
It requires re-setting manually.
• Heating system pressure relief valve will discharge
to relieve excess pressure at 3 bar. (Requires piping
to a safe external discharge point.)
4. INSTALLATION
IMPORTANT PRE- INSTALLATION POINTS
In order to ensure the successful installation
and operation of your Gabarrón boiler,
please consider the following points before
commencing.
SITING THE BOILER
Allow sufficient clearance and access for operating,
maintenance and repair work.
Boiler must be protected from any water, moisture or
dampness. Where installations are in a bathroom, the
installation must comply with the relevant electrical
regulations.
Boiler electrical protection rating is IP20/IP2X. This boiler
is not designed to be installed in the open air.
The boiler must be installed in the upright position.
ELECTRICAL POWER SUPPLY & WIRING
Competency for electrical installation is required.
The power supply must meet the capacity for the
heat output required plus all other appliance that
may be supplied. The cable, MCB and RCD must be of
sufficient capacity to carry the required load.
HEATING SYSTEM & CONTROLS
Any existing system must be suitable for sealed system
operation at up to 3bar pressure and will require
flushing/cleansing in accordance with the Building
Regulations. Any new heating system must be flushed
and cleansed in accordance with the Building Regulations.
A SYSTEM filling loop, isolation valves and drain point
are required.
A time clock/room thermostat should be installed
(Necessary to activate automatic power modulation).
A bypass circuit (min 2m recommended) incorporating
an automatic bypass valve must be installed on all
central heating systems where TRV’s are fitted to
every radiator. Note - A bypass circuit incorporating
an automatic bypass valve is recommended for all
installations. The correct heat requirement for the
dwelling should be calculated.
4.1 General Requirements
Installation should also be in accordance with the
relevant British Standards and Codes of Practice
including the following:
BS7074 Application, selection and installation of
expansion vessels and ancillary equipment for sealed
water systems.
BS 7671 Requirements for electrical installations,
IEE Wiring Regulations.
4.2 Unpacking & Contents
WARNING: Wall and fixings must
be suitable to support the total
weight; MATTIRA MAS boiler when
full is 50kg.
!
WARNING: Before carrying out any
work inside the boiler and obtaining
access to terminals, all supply
circuits must be disconnected.
WARNING Earth the appliance. If the
appliance is not earthed, it may hold
voltage if a defect occurs.
!
Boiler is supplied set at maximum
output and must be adjusted to suit
the incoming supply before being
switched on. (See 5.2 LIMITING
BOILER MAXIMUM OUTPUT).
!
3.4 SAFETY DEVICES
Safe operation under various conditions is ensured by the
following controls fitted inside the boiler:
oWater flow switch that monitors water flow in the
heating system and will prevent operation in case of a
blockage, if the system flow rate is below the permitted
level, error E3 will appear. Installation of a system by-pass
may be necessary (see 7.3 HEATING SYSTEM FLOW
SWITCH –E3 ERROR & SYSTEM BY-PASS
REQUIREMENTS).
oHeating system high limit safety thermostat will prevent
operation if the temperature exceeds 100ºC. It requires
re-setting manually.
oHeating system pressure relief valve will discharge to
relieve excess pressure at 3 bar. (Requires piping to a
safe external discharge point.)
4 INSTALLATION
IMPORTANT PRE- INSTALLATION POINTS
In order to ensure the successful installation
and operation of your Gabarrón boiler, please
consider the following points before commencing.
SITING THE BOILER
WARNING Wall and fixings must besuitable to
support the total weight; MATTIRA MAS boiler
when full is 50kg.
Allow sufficient clearance and access for operating,
maintenance and repair work.
Boiler must be protected from any water, moisture or
dampness.
Where installations are in a bathroom, the installation must
comply with the relevant electrical regulations.
Boiler electrical protection rating is IP20/IP2X. This boiler is
not designed to be installed in the open air.
The boiler must be installed in the upright position.
ELECTRICAL POWER SUPPLY & WIRING
WARNING Before carrying out any work inside
the boiler and obtaining access to terminals, all
supply circuits must be disconnected.
WARNING Earth the appliance. If the appliance is
not earthed, it may hold voltage if a defect occurs.
Competency for electrical installation is required.
The power supply must meet the capacity for the heat
output required plus all other appliance that may be supplied.
The cable, MCB and RCD must be of sufficient capacity to
carry the required load.
Boiler is supplied set at maximum output and must be
adjusted to suit the incoming supply before being switched
on. (See 5.2 LIMITING BOILER MAXIMUM OUTPUT).
HEATING SYSTEM & CONTROLS
Any existing system must be suitable for sealed system
operation at up to 3bar pressure and will require
flushing/cleansing in accordance with the Building Regulations.
Any new heating system must be flushed and cleansed in
accordance with the Building Regulations.
A SYSTEM filling loop, isolation valves and drain point are
required.
A time clock/room thermostat should be installed
(Necessary to activate automatic power modulation).
A bypass circuit (min 2m recommended) incorporating an
automatic bypass valve must be installed on all central
heating systems where TRV's are fitted to every radiator.
Note - A bypass circuit incorporating an automatic
bypass valve is recommended for all installations.
The correct heat requirement for the dwelling should be
calculated.
4.1 GENERAL REQUIREMENTS
Installation should also be in accordance with the relevant
British Standards and Codes of Practice including the
following:
BS7074 Application, selection and installation of expansion
vessels and ancillary equipment for sealed water
systems.
BS 7671 Requirements for electrical installations, IEE Wiring
Regulations
4.2 UNPACKING & CONTENTS
Dispose of the cardboard packaging at a cardboard
recycling site. Observe national regulations.
- Wall bracket with template.
- Boiler.
- Documentation.
- Bag with connecting links.
Dispose of the cardboard packaging
at a cardboard recycling site.
Observe national regulations.
!