Empire Comfort Systems DV-210-7SG Quick start guide

INSTALLATION INSTRUCTIONS
AND
OWNER'S MANUAL
R-1917 Page 1
WARNING: If the information in
this manual is not followed exactly, a
fire or explosion may result causing
property damage, personal injury or
loss of life.
— Do not store or use gasoline or other
flammable vapors and liquids in the
vicinityofthisoranyotherappliance.
— WHATTODOIFYOUSMELLGAS
•Do not try to light any appliance.
•Donottouchanyelectricalswitch;
donotuseanyphoneinyourbuild-
ing.
•Immediatelycallyourgassupplier
from a neighbor's phone. Follow
the gas supplier's instructions.
•If you cannot reach your gas sup-
plier, call the fire department.
— Installation and service must be per-
formedbyaqualifiedinstaller,service
agency or the gas supplier.
WARNING:Ifnotinstalled,operatedand
maintainedinaccordancewiththemanu-
facturer'sinstructions,thisproductcould
expose you to substances in fuel or from
fuelcombustionwhichcancausedeathor
serious illness.
DIRECT VENT
WALL FURNACE
MODELS
DV-210-7SG
DV-215-7SG
EFFECTIVE DATE
NOVEMBER, 2000
This appliance may be installed in an
aftermarketpermanentlylocated,manu-
factured (mobile) home, where not pro-
hibited by state or local codes.
This appliance is only for use with the
type of gas indicated on the rating plate.
This appliance is not convertible for use
with other gases, unless a certified kit is
used.

Introduction
Always consult your local Building Department regarding regulations,
codes or ordinances which apply to the installation of a direct vent wall
furnace.
Instructions to Installer
1. Installermustleaveinstructionmanualwithownerafterinstallation.
2. Installer must have owner fill out and mail warranty card supplied
with furnace.
3. Installer should show owner how to start and operate furnace and
thermostat.
Warning:
Any change to this furnace or its control can be dangerous.
This is a heating appliance and any panel, door or guard
removed for servicing an appliance must be replaced prior to
operating the appliance.
General Information
This furnace is design certified in accordance with American
National Standard/CSA Standard Z21.86b-1998 and CSA
2.32b-M98 by the American Gas Association and Canadian
Gas Association, as a Gravity Direct Vent Wall Furnace to be
installed on an outside wall according to these instructions.
Any alteration of the original design, installed other than as shown
intheseinstructionsorusewithatypeofgasnotshownontherating
plate is the responsibility of the person and company making the
change.
R-1917Page 2
•Due to high temperatures the appliance should be lo-
cated out of traffic and away from furniture and drap-
eries.
• Children and adults should be alerted to the hazards of
high surface temperatures and should stay away to
avoid burns or clothing ignition.
• Young children should be carefully supervised when
they are in the same room as the appliance.
• Clothing or other flammable material should not be
placed on or near the appliance.
• Any safety screen or guard removed for servicing an
appliancemustbereplacedpriortooperatingtheappli-
ance.
• Keep burner and control compartment clean.
• Vent cap hot while furnace is in operation.
• Installation and repair should be done by a QUALI-
FIED SERVICE PERSON. The appliance should be
inspectedbeforeuseandatleast annually by aqualified
service person.
Morefrequentcleaningmayberequireddue toexcessive
lint from carpeting, bedding materials, etc. It is impera-
tivethat controlcompartments,burners andcirculating
air passageways of the appliance be kept clean.
• DO NOT put anything around the furnace that will
obstruct the flow of combustion and ventilation air.
• DOkeep theappliancearea clearand freefrom combus-
tible material, gasoline and other flammable vapors and
liquids.
• DO examine venting system periodically and replace
damaged parts.
• DO examine burners periodically. Clean and replace
damaged parts.
• CAUTION:Pilotholecovermustbekepttightlyclosed
during operation.
• DONOTusethisheaterifanyparthasbeenunderwater.
Immediatelycall aqualified servicetechnician toinspect
the heater and to replace any part of the control system
and any gas control which has been under water.
THIS IS A HEATING APPLIANCE
DO NOT OPERATE THIS APPLIANCE WITHOUT FRONT PANEL INSTALLED.
Important
All correspondence should refer to complete Model No., Serial No. and
type of gas.
Notice: During initial firing of this unit, its paint will bake out and
smoke will occur. To prevent triggering of smoke alarms, ventilate the
room in which the unit is installed.
Installation in Residential Garages
Gasutilizationequipmentinresidentialgaragesshallbeinstalledsothat
all burners and burner ignition devices are located not less than 18"
(457mm) above the floor.
Such equipment shall be located, or protected, so it is not subject to
physical damage by a moving vehicle.
Specifications
Model DV-210 DV-215
Input BTU/HR (KW/H) 10,000 (2.9) 15,000 (4.4)
Height 21 3/8" (543mm) 24 7/8"(632mm)
Width 16 1/4" (413mm) 20 1/4" (514mm)
Depth 9 3/8" (239mm) 9 3/8" (239mm)
Gas Inlet 1/2" (13mm) 1/2" (13mm)
Options for Above Furnaces
Blower DVB-1
Vinyl Siding Vent Kit DV-822

Some people cannot smell well. Some people cannot smell
the odor of the chemical stench put into the gas. You must
findoutifyoucansmelltheodorantinpropane. Smokingcan
decrease your ability to smell. Being around an odor for a time
can affect your sensitivity or ability to detect that odor. Some-
times other odors in the area mask the gas odor. People may not
smell the gas odor or their minds are on something else. Think-
ing about smelling a gas odor can make it easier to smell.
The odorant in LP-gas is colorless, and it can fade under
some circumstances. For example, if there is an underground
leak,themovementofthegasthroughsoilcanfiltertheodorant.
Odorants in LP-Gas also are subject to oxidation. This fading
by point with the members of your household. Someday
whentheremaynotbeaminutetolose,everyone'ssafetywill
depend on knowing exactly what to do. If, after reading the
followinginformation, youfeel youstill needmore informa-
tion, please contact your gas supplier.
Propane (LP-Gas) is a flammable gas which can cause fires
and explosions. In its natural state, propane is odorless and
colorless. Youmaynotknowallthefollowingsafetyprecau-
tions which can protect both you and your family from an
accident. Read them carefully now, then review them point
can occur if there is rust inside the storage tank or in iron gas
pipes.
The odorant in escaped gas can adsorb or absorb onto or into
walls, masonry and other materials and fabrics in a room. That
will take some of the odorant out of the gas, reducing its odor
intensity.
LP-Gasmaystratifyinaclosedarea,andtheodorintensitycould
varyat differentlevels. Since itis heavier thanair, theremay be
more odor at lower levels. Always be sensitive to the slightest
gas odor. If you detect any odor, treat it as a serious leak.
Immediately go into action as instructed earlier.
•LearntorecognizetheodorofLP-gas. YourlocalLP-Gas
Dealer can give you a "Scratch and Sniff" pamphlet. Use it
to find out what the propane odor smells like. If you suspect
thatyourLP-Gashas a weakorabnormalodor,callyourLP-
Gas Dealer.
• If you are not qualified, do not light pilot lights, perform
service, or make adjustments to appliances on the LP-Gas
system. Ifyouarequalified,consciouslythinkabouttheodor
ofLP-Gas priortoand whilelightingpilot lights orperform-
ing service or making adjustments.
• Sometimes a basement or a closed-up house has a musty
smell that can cover up the LP-Gas odor. Do not try to light
pilot lights, perform service, or make adjustments in an area
where the conditions are such that you may not detect the
odor if there has been a leak of LP-Gas.
• Odor fade, due to oxidation by rust or adsorption on walls of
new cylinders and tanks, is possible. Therefore, people
should be particularly alert and careful when new tanks or
cylinders are placed in service. Odor fade can occur in new
tanks, or reinstalled old tanks, if they are filled and allowed
to set too long before refilling. Cylinders and tanks which
have been out of service for a time may develop internal rust
whichwill causeodor fade. If suchconditions aresuspected
to exist, a periodic sniff test of the gas is advisable. If you
have any question about the gas odor, call your LP-gas
dealer. Aperiodic snifftest oftheLP-gas isa goodsafety
measure under any condition.
• If, at any time, you do not smell the LP-Gas odorant and you
think you should, assume you have a leak. Then take the
sameimmediateactionrecommendedabovefortheoccasion
when you do detect the odorized LP-Gas.
• If you experience a complete "gas out," (the container is
under no vapor pressure), turn the tank valve off immedi-
ately. Ifthecontainervalveislefton,thecontainermaydraw
in some air through openings such as pilot light orifices. If
this occurs, some new internal rusting could occur. If the
valve is left open, then treat the container as a new tank.
Always be sure your container is under vapor pressure by
turningitoffatthecontainerbeforeitgoescompletelyempty
or having it refilled before it is completely empty.
SAFETY INFORMATION FOR USERS OF LP-GAS
• Do not operate electric switches, light matches, use your
phone. Do not do anything that could ignite the gas.
• Geteveryoneoutofthebuilding,vehicle,trailer,orarea. Do
that IMMEDIATELY.
• Close all gas tank or cylinder supply valves.
• LP-Gas is heavier than air and may settle in low areas such
as basements. When you have reason to suspect a gas leak,
keep out of basements and other low areas. Stay out until
firefighters declare them to be safe.
• Useyourneighbor'sphoneandcallatrainedLP-Gasservice
person and the fire department. Even though you may not
continue to smell gas, do not turn on the gas again. Do not
re-enter the building, vehicle, trailer, or area.
•Finally, let the service man and firefighters check for
escaped gas. Have them air out the area before you return.
Properly trained LP-Gas service people should repair the
leak, then check and relight the gas appliance for you.
SOME POINTS TO REMEMBER
NO ODOR DETECTED - ODOR FADE
LP-GAS WARNING ODOR
If a gas leak happens, you should be able to smell the gas because of the odorant put in the LP-Gas.
That's your signal to go into immediate action!
R-1917 Page 3

Figure 1
Installing Inside Wall Plate
After the wall opening has been located and cut, center and level inside
wall plate in wall opening. The collar on the inside wall plate is to be
placedwithinthe wall opening. On solid wallorwall stud, attach inside
wallplate with(6) #10 x1 1/2"(38mm) screwsprovided. On sheetrock
wall, by using wall opening for access, attach inside wall plate with (6)
#10 x 1 1/2" (38mm) screws and (6) Tinnerman nuts provided.
Attaching Furnace To Inside Wall Plate
Alignand attachmountingclips onfurnaceback withmountingslots on
insidewallplate. Thefurnacesupportbracketlocatedatfurnacebottom
is to be secured to wall. On solid wall, secure furnace support bracket
with(1)#10x11/2"(38mm)screwprovided. Onsheetrockwall,secure
furnace support bracket with (1) toggle bolt provided.
Figure 2
Cutting Vent Tubes
This is the most important part of the installation. With the furnace
installed on wall the 5" (127mm) diameter air inlet tube and 3" (76mm)
diameter flue outlet tube are to be marked and cut using the following
procedure.
R-1917
Qualified Installing Agency
Installation and replacement of gas piping, gas utilization equipment or
accessories and repair and servicing of equipment shall be performed
only by a qualified agency. The term "qualified agency" means any
individual, firm, corporation or company which either in person or
through a representative is engaged in and is responsible for (a) the
installationorreplacementofgaspipingor(b)theconnection,installation,
repair or servicing of equipment, who is experienced in such work,
familiar with all precautions required and has complied with all the
requirements of the authority having jurisdiction.
The installation must conform with local codes or, in the absence of
local codes, with the National Fuel Gas Code ANSI Z223.1*/
Canadian Installation Code, CAN/CGA B149.
*Available from the American National Standards Institute, Inc., 11 West 42nd St., New
York, N.Y. 10036.
Clearances
1. In selecting a location for installation, it is necessary to provide
adequateaccessibilityclearancesforservicingandproperinstallation.
2. Although certified for 0 clearance to the floor , the unit is held in
place by a wall bracket. Enough clearance [2" (51mm) suggested]
to allow changing or adding floor covering is recommended. Other
clearances to combustible construction:
Sides 1" (25mm) and 12" (305mm) from the top.
3. Note the position of the vent relative to the center of the unit. The
DV-210 has the vent in the center. The DV-215 vent is 2" (51mm)
off center to the right.
4. The minimum distance from the center of the outside vent to the
nearest outside corner or obstruction is 16" (406mm).
5. TheDV-210/DV-215minimumwalldepthis41/2"(114mm)and
maximum wall depth is 13" (330mm). The use of tubes not
supplied by the manufacturer result in unsatisfactory
performance.
Theventterminal ofadirectvent appliance,withaninput of10,000Btu
perhour(3 kW) or lessshallbelocated at least 6"(150mm)from any air
openingintoabuilding,andsuchanappliancewithaninputover10,000
Btu per hour (3 kW) but not over 50,000 Btu per hour (14.7 kW) shall
be installed with a 9" (229mm) vent terminal clearance and the bottom
of the vent terminal and the air intake shall be located at least 12"
(305mm) above grade.
WARNING: The nearest point of the vent cap should be a
minimum horizontal distant of six (6) feet (1.8m) from any
pressureregulator. Incaseofregulatormalfunction,thesix(6)
feet (1.8m) distance will reduce the chance of gas entering the
vent cap.
Locating Wall Opening
Thefurnace istobelocatedon anoutsidewall. Locatewallstuds sothat
wall opening will be located between wall studs. One wall stud can be
used for attachment of inside wall plate. The wall opening required as
shownin Figure1is aminimumdiameter of61/4 (159mm)inches. The
inside wall plate and the outside wall plate are large enough to permit a
wall opening diameter of 8 inches (203mm).
A template is provided in furnace carton for positioning furnace on the
wall. Also, refer to Figure 1 for positioning the furnace on wall and for
locating gas line connection.
Locating Gas Supply
The gas line can enter the unit either through the floor or outside wall.
The gas line opening should be made at this time. Location of the
opening will be determined by the position of floor joists and the valve
and union used for servicing.
Page 4
3" (76mm) DIAMETER FLUE OUTLET TUBE
5" (127mm) DIAMETER AIR INLET TUBE
1/2" (13mm)
2 1/2" (64mm)

1. Attach 5" (127mm) diameter air inlet tube onto the collar of air drop
assembly. Be sure 5" (127mm) diameter air inlet tube is placed as
far as possible onto the collar of the air drop assembly. Mark the 5"
(127mm) diameter air inlet tube 1/2" (13mm) beyond the outside
wall. Remove 5" (127mm) diameter air inlet tube from collar of air
drop assembly.
2. Attach3" (76mm)diameter flueoutlet tubeonto flueoutlet collaron
combustion chamber. Be sure 3" (76mm) diameter flue outlet tube
isplacedasfaraspossibleontothe collar of flue outlet. Mark the 3"
(76mm)diameterflueoutlettube21/2"(64mm)beyondtheoutside
wall. Remove 3" (76mm) diameter flue outlet tube from collar of
flue outlet on combustion chamber.
3. Markorwraptape completely around the tubesatthemarked points
to help in making a true cut. Do not crimp or enlarge tubes.
Installing The Vent Assembly
1. Place provided caulking beneath the edge of the outside wall plate.
Use additional caulking to correct uneven wall surface, such as
clapboard.
2. Attach 5" (127mm) diameter air inlet tube onto the collar of air drop
assembly. Attach caulked, outside wall plate into the 5" (127mm)
diameter air inlet tube. Position the outside wall plate so that 5"
(127mm) diameter air inlet tube has a slight downward slope to the
outside. The downward slope is necessary to prevent the entry
ofrainwater. Attach outsidewall plateto exteriorwall with(4) #10
x 1 1/2" (38mm) screws provided.
3. Apply furnace cement to 3" (76mm) diameter flue outlet collar on
combustionchamberandto3" (76mm) diameter collar on vent cap.
Attach3" (76mm)diameter flueoutlet tubeonto flueoutlet collaron
combustion chamber. Attach vent cap into the 3" (76mm) diameter
flue outlet tube. Attach vent cap to outside wall plate with (3) #10
x 1/2" (13mm) screws provided.
4. Installation is completed.
Reassembly And Resealing Vent-Air Intake System
When vent-air intake system is removed for servicing the furnace, the
followingstepswillassure proper reassembly and resealing ofthevent-
air intake assembly.
1. Remove old furnace cement from flue outlet collar on combustion
chamber and collar of vent cap. Remove old furnace cement from
both ends of 3" (76mm) diameter flue outlet tube.
2. Remove old caulking beneath the edge of the outside wall plate.
Apply new caulking beneath the edge of the outside wall plate. Use
additionalcaulkingtocorrectunevenwallsurface,suchasclapboard.
3. Attach 5" (127mm) diameter air inlet tube onto the collar of air drop
assembly. Attach caulked, outside wall plate into the 5" (127mm)
diameter air inlet tube. Position the outside wall plate so that 5"
(127mm) diameter air inlet tube has a slight downward slope to the
outside. The downward slope is necessary to prevent the entry
ofrainwater. Attach outsidewall plateto exteriorwall with(4) #10
x 1" (25mm) screws provided.
4. Apply furnace cement to 3" (76mm) diameter flue outlet collar on
combustionchamberandto3" (76mm) diameter collar on vent cap.
Attach 3" (76mm) diameter flue outlet tube onto flue outlet collar
on combustion chamber. Attach vent cap into the 3" (76mm)
diameter flue outlet tube. Attach vent cap to outside wall plate with
(3) #10 x 1/2" (13mm) screws provided.
5. Reassembly and resealing vent-air intake system is completed.
Installing a Vent Near a Window Ledge,
Other Type of Projection or on Vinyl Siding
Direct vent furnaces are designed to be installed on a uniform outside
wall. When the wind comes from any angle (up, down or from either
side), it must hit the vent cap equally over both the air inlet and the flue
outlet portions of the vent. Any wall projection, such as a door or
window casing, which disturbs the wind on one side of the air inlet
section will result in back pressure on the flue section smothering the
flame and eventual pilot outage.
When the vent cap is to be installed on vinyl siding or it appears that a
projection within 6" (152mm) of any side of the air inlet section could
shieldtheairinletsection,theentireventshouldbesupportedawayfrom
thewallatleastthedistanceoftheprojection. 2"x 4"(51mm x102mm)
framing whose outside dimensions match the overall dimensions of the
mountingplateisrecommended. The2"x4"(51mmx102mm)framing
protects vinyl siding from possible warpage or discoloration. All joints
can then be sealed and painted. The wall depth plus the additional depth
of the 2" x 4" (51mm x 102mm) framing should not exceed a total depth
of 13" (330mm) for DV-210/DV-215. (See Figure 3)
Figure 3a
Vinyl siding vent kit, DV-822, is available from Empire Comfort
Systems, Inc. The depth is 3" (76mm), which enables the vent cap to be
extendedawayfromvinylsidingorprojections. Thewalldepthplusthe
additional3"(76mm)depthofthevinylsidingventcapextensionshould
not exceed a total depth of 13" (330mm) for DV-210/DV-215. (See
Figure 3a)
Warning: When vinyl siding vent kit, DV-822 or 2" x 4"
(51mm x 102mm) framing is added to an existing installation
(furnace is installed) do not attempt to add sections of pipe to
theflueoutlettubeorairinlettube. Anairtightsealisrequired
for both tubes. Refer to Parts List, page 9 to order tubes.
Installation on Rugs and Tile
If this appliance is to be installed directly on carpeting, tile, or other
combustible material, other than wood flooring, the appliance shall be
installed on a metal or wood panel extending the full width and depth of
the appliance.
The base referred to above does not mean the fire-proof base as used on
woodstoves. The protectionisprimarilyforrugs thatmay beextremely
thick and light-color tile that may discolor.
Gas Supply
Check all local codes for requirements, especially for the size and type
of gas supply line required. On Natural gas lines less than 15' (4.6m)
long, use 1/2" (13mm) pipe; on longer runs, use 3/4" (19mm) iron pipe
or equal. On LP gas lines please consult LP gas supplier.
Installing a New Main Gas Cock
Each appliance should have its own manual gas cock.
A manual main gas cock should be located in the vicinity of the unit.
Where none exists, or where its size or location is not adequate, contact
your local authorized installer for installation or relocation.
R-1917 Page 5
Figure 3
2 x 4 FRAMING
(51mm x 102mm)

purpose of input adjustment to a maximum of 7.0" w.c. (1.743kPa).
Propane gas models will have a manifold pressure approximately 10.0"
w.c.(2.49kPa)atthevalveoutletwiththeinletpressuretothevalvefrom
aminimumof11.0"w.c.(2.739kPa)forthepurposeofinputadjustment
to a maximum of 13.0" w.c. (3.237kPa).
A 1/8" (3mm) N.P.T. plugged tapping, accessible for test gauge
connection, is located on the outlet side of the gas control.
High Altitudes
For altitudes/elevations above 2,000 feet (610m) , input ratings should
be reduced at the rate of 4 percent for each 1,000 feet (305m) above sea
level. Canadian High Altitudes for locations having an elevation
abovemeansealevelbetween2,000feet(610m)and4,500feet(1370m),
themanifoldpressureistobedecreasedfrom4.0"w.c.(.996kPa)to3.2"
w.c. (.797kPa) for Natural Gas and from 10.0" w.c. (2.49kPa) to 8.0"
w.c. (1.99kPa) for Propane Gas.
Piezo Pilot Ignitor Instructions
Depressingtheredbuttoncompletelycausesasparktooccuratthepilot.
This is a substitute for a match which requires opening the pilot hole
cover.
To light the pilot, it is important that the electrode be 1/8" (3mm) from
the thermopile. The spark must occur at the point the burner flame hits
thethermopile. Theendoftheelectrodewillberedhotwiththepiloton.
On a new installation with air in the gas line, it is suggested that a match
be used. The match will light the pilot faster than the piezo under this
condition.
Steps in Removing Main Burner, Orifice and Valve
1. Disconnect the thermopile and pilot supply line at the pilot burner.
2. Remove the burner compartment cover 5/16" (8mm) socket
suggested.
3. Remove screw holding left side of burner and lift out.
4. Main burner orifice is now accessible. Use 1/2" (13mm) box end
wrench to remove and apply non-hardening pipe dope sparingly to
orifice threads when replaced.
5. To remove the entire gas valve the nut holding the orifice fitting to
the chamber must be removed and the gas supply to the valve
disconnected. Afterthis,thevalveandorificeelbowcanberemoved
as a unit.
Cleaning The Pilot Burner
Cleaning of the pilot may be an annual necessity due to spiders. After
removing the supply tubing and orifice, use a pipe cleaner or wire to
clean the entire internal part of the pilot.
Cleaning the Combustion Chamber and Main Burner
Whenthe mainburner andvent capare removed,all internalareas ofthe
combustion chamber are accessible for cleaning with a vacuum hose.
The main burner may be cleaned by forcing water into the ports and the
throatofthe burner. The burnershouldbeblown dry orheatedto dry all
water out before reinstalling.
Proper Pilot Flame (Figure 5)
The pilot flame is blue and goes toward the main burner and thermopile
horizontally. Aslight yellowtip onthe flameis normal. Thepilotflame
must surround and extend approximately 1/4" (6mm) beyond the
thermopile,andmustextendbeyondthefirstrowtowardthesecondrow
of main burner ports.
Page 6 R-1917
Compoundsusedonthreadedjointsofgaspipingshallberesistanttothe
action of liquefied petroleum gases. The gas lines must be checked for
leaksbytheinstaller. Thisshouldbedonewithasoapsolutionwatching
forbubblesonallexposedconnections,andifunexposed,apressuretest
should be made.
Never use an exposed flame to check for leaks. Appliance must be
disconnected from piping at inlet of control valve and pipe capped
or plugged for pressure test. Never pressure test with appliance
connected; control valve will sustain damage!
A gas valve and ground joint union should be installed in the gas line
upstream of the gas control to aid in servicing. It is required by the
National Fuel Gas Code that a drip line be installed near the gas inlet.
Thisshould consistof avertical lengthof pipetee connectedinto thegas
line that is capped on the bottom in which condensation and foreign
particles may collect.
Figure 4
Method of Installing a Tee Fitting Sediment Trap
The use of the following gas connectors is recommended:
— ANS Z21.24 Appliance Connectors of Corrugated Metal Tubing
and Fittings
— ANS Z21.45 Assembled Flexible Appliance Connectors of Other
Than All-Metal Construction
Theabove connectors maybe used ifacceptable by theauthority having
jurisdiction.
Pressure Testing of the Gas Supply System
1. To check the inlet pressure to the gas valve, a 1/8" (3mm) N.P.T.
plugged tapping, accessible for test gauge connection, must be
placed immediately upstream of the gas supply connection to the
appliance.
2. Theapplianceandits individual shutoff valvemustbedisconnected
fromthegassupplypipingsystemduringanypressuretestingofthat
system at test pressures in excess of 1/2 psig (3.5 kPa).
3. Theappliancemustbeisolatedfromthegassupplypipingsystemby
closing its individual manual shutoff valve during any pressure
testing of the gas supply piping system at test pressures equal to or
less than 1/2 psig (3.5 kPa).
Attention! Ifoneoftheaboveproceduresresultsinpressuresinexcess
of 1/2 psig (14" w.c.) (3.5 kPa) on the appliance gas valve, it will result
in a hazardous condition.
Checking Manifold Pressure
Both Propane and Natural gas valves have a built-in pressure regulator
in the gas valve. Natural gas models will have a manifold pressure of
approximately 4.0" w.c. (.996kPa) at the valve outlet with the inlet
pressure to the valve from a minimum of 6.0" w.c. (1.494kPa) for the
3" (76mm) MIN.
1/8" (3mm) NPT
PLUGGED HOLE
FOR TEST GAGE
1/8" (3mm) NPT
PLUGGED HOLE
FOR TEST GAGE

Page 7
Thermostat Location
These heating thermostats are specially designed for use on self-generat-
ing systems. They should never be used on line or low voltage A.C.
circuits.
Exterior Wall — The thermostat may be mounted on an exterior wall
abovetheheaterifitislocatedinthesamestudspaceastheventtubesand
is a minimum of 6" (152mm) above the heater.
Interior Wall — The thermostat should be installed on an inside wall
away from the unit but in the same room.
Note: Use 16 gauge wire to prevent excessive loss of millivolts.
Proper operation depends on a good pilot flame. The flame must cover
thetopofthethermopile. Cleaningof the pilot orifice and burner may be
required due to spiders.
System Check
A millivolt meter is required to check the system. The millivolt readings
should be:
• Across the thermopile terminals, 400-450 millivolts with thermostat
OFF.
• Across the thermopile terminals, 150-250 milllivolts with thermostat
ON.
• Across the thermostat wires at the valve, less than 30 millivolts with
thermostat ON.
• Across the thermostat wires at the thermostat, less than 5 millivolts
with thermostat ON. (Strong winds, dirty pilot and low pressure will
reduce readings.)
Figure 7
R-1917
MAIN BURNER
PILOT
FLAME BURNER
CHANNEL
THERMOPILE
Figure 5
Proper Main Burner Flame (Figure 6)
On the main burner, the burning gas forms a primary flame and a
secondary flame. The primary flame is blue and about 3/16" (5mm)
high. Thesecondaryflameisverypaleblue,3inches(76mm)to5inches
(127mm)high. Dustinthecombustionairwillproduceanorangeflame.
Do not mistake it for an improper yellow flame.
Figure 6

4. Push in gas control knob slightly and turn clock-
wise to "OFF." Do not force.
5. Replace control access panel (front panel).
8. Find pilot - follow metal tube
from gas control. The pilot is
behind the pilot access cover.
9. Turn knob on gas control counterclockwise
to "PILOT."
10. Push in control knob all the way and hold in. Imme-
diately light the pilot with the Piezo Pilot Ignitor or a
match. Continuetoholdthecontrolknobinforabout
one(1)minuteafterthepilotislit. Releaseknob, and
it will pop back up. Pilot should remain lit. If it goes
out, repeat steps 5 through 10.
• Ifknobdoesnotpopupwhenreleased,stop
and immediately call your service techni-
cian or gas supplier.
• Ifthepilotwillnotstaylitafterseveraltries,
turnthegascontrolknobto"OFF"andcall
your service technician or gas supplier.
11. Replace pilot access cover.
12. Turn gas control knob counterclockwise to
"ON."
13. Replace control access panel (front panel).
14. Turn on all electric power to the appliance (if appli-
cable).
15. Set thermostat to desired setting.
16. CAUTION: Pilot access cover must be kept tightly
closed during operation.
1. STOP! Read the safety information above.
2. Set the thermostat to lowest setting.
3. Turn off all electric power to the appliance (if appli-
cable).
4. Remove control access panel (front panel).
5. Push in gas control knob slightly and turn clockwise
to "OFF".
NOTE: Knob cannot be turned from "PILOT" to
"OFF" unless knob is pushed in slightly. Do not force.
6. Waitten(10) minutes toclear outany gas. Then smell
for gas, including near the floor. If you smell gas,
STOP! Follow "B" in the safety information above. If
you don't smell gas, go to the next step.
7. Remove the pilot access cover located on the combus-
tion chamber.
TO TURN OFF GAS TO APPLIANCE
FOR YOUR SAFETY READ BEFORE LIGHTING
WARNING: If you do not follow these instructions exactly, a fire or explosion may result
causing property damage, personal injury or loss of life.
A. This appliance has a pilot which must be lighted by
hand. Whenlighting thepilot,follow theseinstructions
exactly.
B. BEFORE LIGHTING smell all around the appliance
area for gas. Be sure to smell next to the floor because
some gas is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch;
do not use any phone in your building.
• Immediately call your gas supplier from a neigh-
bor'sphone. Followthegassupplier'sinstructions.
• Ifyoucannotreachyourgassupplier,callthefire
department.
C. Useonlyyourhandtopushinorturnthegascontrol
knob. Never use tools. If the knob will not push in
or turn by hand, don't try to repair it; call a
qualified service technician. Force or attempted
repair may result in a fire or explosion.
D. Do not use this appliance if any part has been under
water. Immediately call a qualified service techni-
ciantoinspecttheapplianceandtoreplaceanypart
of the control system and any gas control which has
been under water.
LIGHTING INSTRUCTIONS
R-1917
Page 8
1. Set the thermostat to lowest setting.
2. Turn off all electric power to appliance if service is
to be performed (if applicable).
3. Remove control access panel (front panel).

SERVICE AND MAINTENANCE SUGGESTIONS
CALL SERVICEMAN
SYMPTOMS
R-1917 Page 9
1. Lit match goes out as it enters lighter port.
a. Certain wind conditions will blow out match. Ignite
match, and as it flares, thrust match through opening.
b. Open nearby door or window and relight pilot.
2. Pilot flames but goes out when knob is released.
a. See Lighting Instructions. Relight Pilot.
b. Relight the pilot and hold knob down longer and harder.
Close lighter hole cover just after igniting. Check for a
good pilot flame.
c. Defective thermopile or defective magnet in safety section
of valve. Replace.
3. Yellow pilot flame.
a. Obstruction at pilot orifice.
b. Clean and properly size orifice.
4. Pilot and main burner go out during normal operation.
a. Check millivolts.
b. Check for proper size of pilot flame.
c. Check for defective or weak thermopile.
d. Check input, reduce as needed.
e. Cover on pilot lighter hole must be air tight.
f. Check for tight fit of air and flue tubes at both ends of vent
assembly. No obstruction around vent that would prevent
the wind from hitting all of the vent equally.
5. Thermostat does not turn the main burner on.
a. Check wiring.
b. Check all millivolt readings.
c. Check for spider in main burner orifice.
6. Yellow main burner flame soot on the vent cap.
a. Remove main burner to check for obstructions in throat,
ports and orifices.
b. Install new main burner orifice and pilot orifice. Refer to
Parts List on this page.
1 TH-100 WALL MOUNTING PLATE
2 TH-104 GASKET - FOR WALL MOUNTING
PLATE
3 TH-015 AIR DROP ASSEMBLY - DV-210
3 TH-018 AIR DROP ASSEMBLY - DV-215
4 TH-102 OUTER CASING - DV-210
4 TH-103 OUTER CASING - DV-215
5 TH-142 INNER CASING - DV-210
5 TH-143 INNER CASING - DV-215
6 TH-008 FRONT PANEL - DV-210
6 TH-009 FRONT PANEL - DV-215
7 TH-024 COMBUSTION CHAMBER - DV-210
7 TH-027 COMBUSTION CHAMBER - DV-215
8 712098 GASKET - OBSERVATION HOLE
COVER
9 DV-781 OBSERVATION HOLE COVER
10 DV-064 COVER PLATE - OBSERVATION
HOLE
11 852098 NUT FOR ORIFICE FITTING
12 742134 BURNER ORIFICE - DV-210 NAT
12 742133 BURNER ORIFICE - DV-215 NAT
12 742297 BURNER ORIFICE - DV-210 LPG
12 742282 BURNER ORIFICE - DV-215 LPG
13 742038 ORIFICE FITTING
14 732016 ELECTRODE AND WIRE
15 722049 MANIFOLD
16 R-5598 GAS VALVE 7000 MVRLC - NAT
16 R-5599 GAS VALVE 7000 MVRLC - LPG
17 R-2890 PILOT BURNER W/ORIFICE - LPG
17 R-2893 PILOT BURNER WITH ORIFICE -
NAT
18 TH-335 PILOT SHIELD
19 712051 GASKET - PILOT BURNER
20 TH-133 CHAMBER DOOR WITH GASKET -
DV-210
20 TH-134 CHAMBER DOOR WITH GASKET -
DV-215
21 TH-365 VALVE BRACKET
22 TH-336 PILOT TUBING - 1/4" (6.4mm) WITH
FERRELLS (NAT.)
22 TH-367 PILOT TUBING - 1/4" (6.4mm) WITH
FERRELLS (LP)
23 672064 THERMOPILE - GENERATOR
24 R-2708 PIEZO IGNITOR
25 TH-289 IGNITOR BRACKET
26 TH-275 BURNER - DV-210
26 TH-267 BURNER - DV-215
27 TH-109 3" (76mm) DIA FLUE OUTLET TUBE
28 TH-107 5" (127mm) DIA AIR INLET TUBE
29 TH-331 OUTSIDE MOUNTING PLATE
30 TH-334 VENT CAP
31 TH-123 VENT KIT COMPLETE
32 662021 WALL THERMOSTAT - MILLIVOLT
NOT SHOWN 742158 ORIFICE FOR PILOT - NAT
NOT SHOWN 742266 ORIFICE FOR PILOT - LPG
NOT SHOWN TH-300 GASKET FOR CHAMBER DOOR -
DV-210
NOT SHOWN TH-281 GASKET FOR CHAMBER DOOR -
DV-215
NOT SHOWN TH-351 HARDWARE PACKAGE
NOT SHOWN 652211 REGULATOR - LPG
NOT SHOWN 652121 REGULATOR - NAT
NOT SHOWN 922217 OPERATOR - LPG
NOT SHOWN 922113 OPERATOR - NAT
USE ONLY MANUFACTURER'S REPLACEMENT PARTS. USE OF ANY OTHER PARTS COULD CAUSE INJURY OR DEATH.
PLEASE NOTE: When ordering parts, it is very important that part number and description of part coincide.
INDEX PART
NO. NUMBER DESCRIPTION INDEX PART
NO. NUMBER DESCRIPTION

Page 10 R-1917
Empire Comfort Systems, Inc. Nine Eighteen Freeburg Ave. Belleville, Illinois 62222-0529
PLEASE NOTE: When ordering parts, it is very important that part number and description of part coincide.
How To Order Repair Parts...
Partscanbeorderedonlythroughyour servicepersonordealer. For bestresults, theservicepersonordealershouldorder partsthroughthe distributor.
Parts can be shipped directly to the service person/dealer.
All parts listed in the Parts List have a Part Number. When ordering parts, first obtain the Model Number from the name plate on your equipment. Then
determine the Part Number (not the Index Number) and the Description of each part from the following appropriate illustration and list. Be sure to give
all this information . . .
Furnace Model Number Part Description
Furnace Serial Number Kind of Gas (Propane or Natural)
Part Number
Do not order bolts, screws, washers or nuts. They are standard hardware items and can be purchased at any local hardware store.
Shipments contingent upon strikes, fires and all causes beyond our control.

DVB-1 For Direct Vent Wall Furnaces
DV-210-(7, 9)SG and DV-215-(7, 9)SG
OPTIONAL BLOWER
Page 11R-1917
Cleaning the Blower Wheel
Insomeareas,suchasnearbedroomsandonfloorswithahardsurface,
the blower wheel will be filled with lint very quickly. A visual check
oftheblowerwheelshouldbemadeafter30daysuse. Theblowerwill
run faster with a dirty wheel, but move less air. Remove the entire
blower and clean each blade of the wheel with a tooth brush as often
as necessary.
Figure 1
INSTALLING OPTIONAL BLOWER DVB-1. The blower must be
positioned as shown in Figure 1. Relocate gas line, if necessary, using
elbow fitting at the gas valve, and move Piezo Spark Generator to the
nextscrew. Asloton the bottom of theblowerpackageengagesatabon
the bottom of the inner casing and is secured by one screw in front.
Attaching Switch Box
1. Facing combustion chamber, remove (2) top, left screws on the com-
bustion chamber door.
2. Align (2) clearance holes on the switch box(with fan control) over (2)
clearance holes on the combustion chamber door.
3. Insert and attach (2) screws removed in Step 1 into switch box and
combustion chamber door.
4. Attach switch box cover to switch box with (1) No. 8 x 1/4" screw.
Wiring
The appliance, when installed, must be electrically grounded in accordance
withlocalcodesor,intheabsenceoflocalcodes,withtheNationalElectrical
Code, ANSI/NFPA 70 or Canadian Electrical Code, CSA C22.1, if an
external electrical source is utilized. This appliance is equipped with a
three-prong[grounding]plugforyourprotection against shock hazard
and should be plugged directly into a properly grounded three-prong
receptacle. Do not cut or remove the grounding prong from this plug.
For an ungrounded receptacle, an adapter, which has two prongs and a wire
forgrounding,canbepurchased,pluggedintotheungroundedreceptacleand
its wire connected to the receptacle mounting screw. With this wire
completing the ground, the appliance cord plug can be plugged into the
adapter and be electrically grounded. A 7/8" (22mm) hole is provided in the
junction box for use with a conduit connector if local codes require this type
of protection.
CAUTION: Label all wires prior to disconnection when servicing
controls. Wiring errors can cause improper and dangerous operation.
Verify proper operation after servicing.
Oiling the Motor
Oiling holes are provided on each end of the motor for oiling. The blower
shouldhavefivedropsof#20motoroilevery 6months. Donotusemachine
oil.
Warning:
Unpluggingofbloweraccessory willnotstoptheheaterfrom
cycling. To shut heater off: 1. Turn temperature dial to
lowest setting, then turn thermostat to off. 2. Turn knob on
gas control to off, depressing slightly. Do not force.
Index Part
No. Number Description
1 8720125 Wire Assembly
2 872087 Bushing (Three Required)
3 9120106 Fan Control
4 DV-806 Switch Box
5 DV-807 Switch Box Cover
6 TH-111 Junction Box
7 872056 Bushing (Strain Relief)
8 622019 Motor
9 632016 Motor Cushion
10 TH-080 Blower Cushion
11 TH-356 Motor Support Assembly
12 642029 Blower Wheel
13 TH-135 Blower Housing Assembly
14 872020 Cord Set
This manual suits for next models
1
Table of contents
Other Empire Comfort Systems Wall Furnace manuals