COZY DVCF407B-R and User manual

24 VOLT SYSTEM WITH LOW-BTU PILOT
MODEL NUMBERS
NAT. GAS DVCF403B-R DVCF653B-R
L.P. GAS DVCF404B-R DVCF654B-R
DIRECT VENT
COUNTERFLOW
WALL FURNACE
INSTALLATION AND
OPERATING INSTRUCTIONS
P/N 72900 REV. 12/03
24 VOLT SYSTEM W/INTERMITTENT IGNITION (IID)
MODEL NUMBERS
NAT. GAS DVCF407B-R DVCF557B-R
L.R GAS DVCF408B-R DVCF558B-R
The coating selected to provide longer life to
the heat exchanger may smoke slightly upon
initial firing. Please provide adequate
ventilation if this ocurs.
INSTALLER MUST LEAVE THESE
INSTRUCTIONS WITH THE CONSUMER
HAVE THEM COMPLETE,AND RETURN
THE WARRANTY CARD.
WARNING: If the information in this manual is not followed
exactly, a fire or explosion may result causing property damage,
personal injury or loss of life.
-Do not store or use gasoline or other flammable vapors and
liquids in the vicinity of this or any other appliance.
- WHAT TO DO IF YOU SMELL GAS:
•Do not try to light any appliance.
•Do not touch any electrical switch; do not use any phone in your
building.
•Immediately call your gas supplier from a neighbor's phone.
Follow the gas supplier's instructions.
•If you cannot reach your gas supplier, call the fire department.
- INSTALLATION AND SERVICE MUST BE PERFORMED
BY A QUALIFIED INSTALLER, SERVICE AGENCY OR
THE GAS SUPPLIER.
WARNING: Operation of this furnace without the properly installed, furnished vent system and vent cap I
could result in Carbon Monoxide (CO) poisoning and possible death. For your safet)_ this furnace and the I
vent system should be inspected at least annually by a qualified service person.
This unit is not approved for installation in greenhouses, or environments involving dusty, wet, I
corrosive, or explosive conditions. Such conditions will invalidate the warranty and may create I
unsafe conditions.

The appliance may be installed in an aftermarket permanently located, manufactured (mobile)
home, where not prohibited by local codes. This appliance is only for use with the type of gas
indicated on the rating plate. This appliance is not convertible for use with other gases, unless a
certified kit is used.
CONTENTS
Introduction ..................................... 2
Specifications and Dimensions ............... 2
Safety Rules ..................................... 3
Clearances ....................................... 4, 5
Location .......................................... 6
Installation ....................................... 6
Operation ........................................ 7
Lighting Instructions ........................... 8, 9
Pilot Adjustment ................................ 10
Removing Burner ............................ 10
Proper Burner Flame ........................ 10
Optional Side Discharge Kit ............... 14
Terminal Block Wiring ..................... 13
Manual Reset ................................. 13
Maintenance Instructions ................... 13
Trouble Shooting ............................. 16,17
Pans Drawing ................................. 18
Parts List ....................................... 19,20
Warranty ....................................... 22
INTRODUCTION
Read these installation and operating instructions carefully before you install or attempt to use this Direct
Vent Counterflow Wall Furnace. If you do not understand any part of the instructions, consult local authorities,
a qualified installer, service agency or the gas supplier. FAILURE TO READ OR UNDERSTAND THESE
INSTRUCTIONS CAN RESULT IN MALFUNCTION, INEFFICIENT OPERATION, PROPERTY
DAMAGE, SERIOUS INJURY OR DEATH.
SPECIFICATIONS AND DIMENSIONS
Your Direct Vent Counterflow Wall Furnace is shipped in two cartons. One carton contains the furnace,
thermostat, thermostat wire and insulated staples. The second carton will have the vent tube, air intake tube
and vent cap assembly. After the furnace has been removed from the carton check the rating plate to verify
that the model number is correct and that the wall furnace is equipped with the type gas you intend to use.
Model Type Type Btu/Hr. Gas Blower Approx.
Number Control Gas Input Inlet Finished Dimensions Speed Amps CFM Ship. Wt
24 VOLT SYSTEM WITH LOW-BTU STANDING PILOT
DVCF403B-R 24¼)1t Nat. 40,000 ½"
DVCF404B-R 24Volt L.P 40,000 ½"
DVCF653B-R 24¼_1t Nat. 62,500 ½"
DVCF654B-R 24¼_1t L.P 62,500 ½"
14-5/16"Wx78-5/8"Hxl 1-3/4"D 1 1.95 320 128Lbs.
14-5/16"Wx78-5/8"Hxl 1-3/4"D 1 1.95 320 128Lbs.
14-5/16"Wx87-5/16"tLxl 1-3/4"D 2 3.05 440 142Lbs.
14-5/16"Wx87-5/16"tLxl 1-3/4"D 2 3.05 440 142Lbs.
24 VOLT SYSTEM WITH INTERMITTENT IGNITION (I.I.D.)
DVCF407B-R 24¼_1t Nat. 40,000 ½" 14-5/16"Wx78-5/8"Hxll-3/4"D 1 2.2 320 130Lbs.
DVCF408B-R 24¼_1t L.P 40,000 ½" 14-5/16"Wx78-5/8"Hxll-3/4"D 1 2.25 320 130Lbs.
DVCF557B-R 24¼_1t Nat. 55,000 ½" 14-5/16"Wx87-5/16"ILxll-3/4"D 2 3.3 440 144Lbs.
DVCF558B-R 24¼)1t L.P 55,000 ½" 14-5/16"Wx87-5/16"Hxll-3/4"D 2 3.35 440 144Lbs.
Page 2

SAFETY RULES
1. Follow all applicable local codes and ordinances. If there are none, follow the latest edition of the
National Fuel Gas Code, ANSI.Z223.1. A copy may be obtained from American Gas Association,
1515 Wilson Blvd., Arlington, Virginia 22209, or the National Fire Protection Association,
Batterymarch Park, Quincy, MA. 02269. In Canada, see the current CAN1-B 149 installation code,
available from International Approval Services, 55 Scarsdale Road, Don Mills, Ontario, Canada
M3B-2R3.
2. The appliance, when installed, must be electrically grounded in accordance with local codes or, in
the absence of local codes, with the latest edition of National Electrical Code, ANSI/NFPAT0. In
Canada, see the current CSA C22.2 Canadian Electrical Code, available from International Approval
Services, 178 Rexdale Boulevard, Etobicoke, Ontario, Canada M9W 1R3.
3. Do not install this furnace in a recreational vehicle or trailer.
4. Do not operate this furnace unless it is connected to the supplied vent system with vent cap in place.
Do not attempt to extend vent pipes. 12 inches is maximum length.
5. Never use a match, candle, flame or other source of ignition to check for gas leaks. Use only soapy
water or liquid detergent.
6. Before cleaning or servicing, turn offthe gas and allow furnace to cool.
7. Do not operate furnace without grilles and front panel in place.
8. Due to high temperatures, locate furnace out of traffic and away from furniture and drapes.
9. Children and adults should be alerted to the hazard of high surface temperature and should be kept
away to avoid burns or clothing ignition.
10. Young children should be carefully supervised when they are in the same room with the furnace.
11. Do not place clothing or other flammable material on or near the furnace.
12. Installation and repair should be done by a qualified service person. The furnace should be inspected
before use and at least annually by a professional service person. More frequent cleaning may be
required due to excessive lint from caLt_eting, bedding material, etc. It is imperative that control
compartments, burners, and circulating air passageways of the furnace be kept clean.
13. Do not put anything around the furnace or vent cap that will obstruct the flow of combustion and
ventilation air.
14. When installing the furnace allow adequate accessibility clearances for servicing and proper operation.
(See Figure 1- Page 5).
15. When the furnace is installed directly on carpeting, tile or other combustible material other than
wood flooring, the furnace shall be installed on a metal or wood panel extending the full width and
depth of the furnace.
16. Do not use this heater if any part has been under water, hnmediately call a qualified service technician
to inspect the heater and to replace any part of the control system which has been under water.
17. For your safety, this furnace is equipped with a manual reset auxiliary limit switch. In case of failure
by the primary limit switch, this switch will shut the valve down completely before unsafe temperatures
are reached. After a cool down period, switch must be manually reset. If outages persist, call a
qualified service person.
18. Side discharge kit boots must not exceed 10 inches.
19. Locate the auxiliary limit switch and push in the red reset button. This will reset the switch in case
it accidentally opened during shipping.
Page 3

REFERENCE LETTERTO
DRAWING
A: Clearance above grade, veranda,
)orch, deck, or balcony
B : Clearance to window or door that
may be opened
Vent Terminal _._ Air Supply Inlet [] Area where terminal is not permitted
VENT TERMINAL CLEARANCES
CANADIAN INSTALLAI
12 Inches (30 cm)
12 Inches (30 cm)
C=Clearance to permanently closed 12 Inches (30 cm)
window
18 Inches (46 cm)
D=Vertical clearance to ventilated
soffit located above the terminal within
a horizontal distance of 2 Feet (61 cm)
from the center line of the terminal
E: Clearance to unventilated soffit
F: Clearance to outside corner
G: Clearance to inside corner
H : Clearance to each side of center
line extended above meter/regulator
assembly
I : Clearance to service regulator vent
outlet
24 Inches (61 cm)
12 Inches (30 cm)
12 Inches (30 cm)
3 Feet (91 cm) within a height
15 Feet (4,5m) above the meter,
assembly
3 Feet (91 cm)
J= Clearance to nonmechanical air 12 Inches (30 cm)
supply inlet to building or the
combustion air inlet to any other
appliance
K: Clearance to a mechanical air 6 Feet (1,83 m)
supply inlet
I. = Clearance above paved sidewalk or
paved driveway located on public
property
M = Clearance under veranda, porch,
deck, or balcony
In accordance with the current CSA-B149,1 Natural Gas and Prep(
7 Feet (2,13m) A vent shall not l-
directly above a sidewalk or pa_
driveway that is located betwe_
single family dwellings and serve
dwellings,
12 Inches (30 cm) permiffed onl!
veranda, porch, deck, or balcon
open on a minimum of two side_
Page 4

CLEARANCES
1. The minimum clearance to a side wall is 4". (See Fig. 1). NOTE:
The unit may be recessed and rest directly against side studs and
the inside surface of the rear wall.
2. The minimum clearance to the ceiling is 4". (See Figure 1).
3. The minimum clearance to the floor is 0". (See Figure 1).
4. The minimum clearance from the side of the vent cap to any
protruding obstructions, or corners is 12". (See Figure 2b).
5. The minimum clearance from any window to the side of the vent
cap is 9" for DVCF403, 404, 407 and 408 (See Figure 2), and
12" for DVCF557, 558, 653, and 654 (See Figure 2b).
6. The minimum clearance from any overhanging projection is 24"
to top of vent cap (See Figure 2).
7. RESIDENTIAL GARAGE INSTALLATION: Gas utilization
equipment in residential garages shall be installed so that all
burners and burner ignition devices are located not less than 18
inches (46 cm) above the floor. Such equipment shall be located,
or protected so it is not subject to damage by a moving vehicle.
Use care in selecting a good location within the garage. DO
NOT locate the appliance where heated air will be directed onto
anearby parked vehicle. Paint may discolor or rubber may harden
and crack. DO NOT allow heated discharge air to blow directly
onto open or closed containers of paint, gasoline or other liquids
having flammable vapors.
FIGURE 1
24"]/iin. [--][--]
, ff]D
-12" _ _,,)
)
FIGURE 2 /DVCF403B, 404B, 407B, AND 408B
24'{Mln. DD
DD
FIGURE 2B /DVCF557B, 558B, 653B, AND 654B
Page 5

LOCATIONS
1. This furnace must be installed on an outside wall and vented
to the outside. If possible, this wall should be on the side of
the house that receives the least amount of wind since strong
gusting winds could cause pilot outage.
2. For most efficient performance, locate furnace as centrally
as possible in the area to be heated.
3. The furnace can be installed flush against a wall or recessed
up to 10" maximum. For proper combustion, make sure
unit is level front to back and side-to-side.
4. Do not install the furnace in acloset, alcove or small hallway
where the furnace could be isolated from the space to be
heated by closing a door.
5. Be sure the vent cap will have the proper clearances (See
Figure 2).
6. Check inside the wall to make sure there are no obstacles
such as water pipes, electric wiring, etc. which could
interfere with the installation of the furnace or vent tubes.
7. Be sure to maintain adequate accessibility clearances for
servicing and proper operation.
8. If the furnace is installed in a basement, a 12" clearance
must be maintained between ground level and the bottom
of the vent cap. Do not install furnace where vent cap will
terminate in a window well or any other opening below
ground level.
INSTALLATION
ELECTRICAL ROUGH-IN
For convenience, this furnace is equipped with a three-prong
power cord located on the top left of heater. The 115V wiring
should be brought in on the left side terminating in a receptacle
box (not provided). Consult local codes or ordinances. (For
Alnps, see Page 2/Specifications and Dimensions).
ROUGH-IN GAS SUPPLY
Install a 1/2 inch diameter gas supply line. The gas line can
enter the cabinet through the right side or bottom (See Figure
3). The gas line must have an individual manual shut offvalve.
Also, you must install a drip leg and provide a 1/8" N.RT.
plugged tapping, accessible for test gauge connection,
immediately upstream of the gas supply connection to the
furnace (See Figure 4).
The furnace and its individual shut off valve must be
disconnected from the gas supply piping system during any
pressure testing of that system at test pressures in excess of */2
psig (3.5kPa). The furnace must be isolated from the gas supply
piping system by closing its individual manual shut off valve
during any pressure testing of the gas supply piping system at
test pressures equal to or less than 1/2psig (3.5kPa).
--_l _---3-1/2"
_v--_-l- 1/20A
FIGURE 3
Gas
-- ; Supply
II Line
Drip_ _-
Leg -* Cut off- 1/8 N.P.T.
Valve Pressure Tap
FIGURE 4
II I
II I
II I
1
9-1/4 I
DIA. I
I
I
' DVC_I40 -59"
WALL _ DVCF,55/65- 68-1/T
sTuDs}i II
II
II
II
II
FINISHED II
,, FLOOR ,I,I ,,
FIGURE 5
Page 6

LOCATE VENT OPENING
After the location of the heater has been determined, the
opening for the vent pipe should be cut. If the heater is to be
recessed, cut out opening tbr heater between studs on the
interior wall and cut out the floor plate bepvveenthe studs, so
heater will set flat on floor as all dimensions are given from
a finished floor. The height of the cut out for a 40,000 BTU
model is 78-5/8", for the 55,000 and 62,500 models the cut
out height is 87-5/16". NOTE: This dimension may be
increased to allow more room t\)r installation and making
the wiring connection, then refinished.
Next, cut out a 9-1/4" opening in exterior wall t\)r the vent
tubes to pass through. The center of opening for the 40,000
BTU furnace is 59", the center for opening tbr 55,000 and
62,500 BTU furnaces is 68-1/2". See Figure 5, on Page 6.
If the heater is to be surfaced mounted, cut out 9-1/4" opening
through the interior and exterior wall. The center of cut out
will be 59" for 40,000 BTU and 68-1/2" for 55,000 and
62,500 BTU models. Be sure both cutouts are level with
each other.
INSTALLING THE FURNACE
The vent system supplied with this furnace will accommodate
walls 3/4"(when recessed) up to 12" thick. Use only the
exhaust tube. air intake tube and vent cap supplied with
heater. Do not attempt to lengthen the exhaust or air intake
robes, this could cause an imbalance in the heater resulting
in poor perforlnance and pilot outage (See Figure 6).
Measure exact distance "X" between surface on which back
of cabinet will rest (inside of recessed cavity or face of wall
when freestanding) and the outside wall surfiace (see Figure
6).
Inlet Air Tube "A" Measuring from gasketed surface,
mark and cut pipe same as dimension "X". Remove any
burrs.
Vent Exhaust Tube "B" Measuring from gasketed
surface, mark and cut pipe 1-3/4" _eater than dimension
"X". Remove any burrs.
Fasten vent exhaust robe "B" to heat exchanger collar and
Inlet Air Tube "A" to flange on back of furnace using 16 #
3/8 screws ("C") provided. Be sure gaskets are in place and
not damaged. Anytime the vent pipes are removed check
and replace gaskets (if necessary). Failure to replace missing
or damaged gaskets may expose homeowner to life
threatening conditions.
Secure furnace in place using 2 holes provided in bottom of
casing. NOTE: Make sure both robes are centered in cut
out. Slide the vent cap onto the pipes extending from the
back of the furnace. A rotating or twisting motion will ease
this installation. Secure vent cap and vent cap spacer plate
to wall causing the vent tubes to have a slight downward
pitch. This will prevent water from entering. Anchors (not
provided) may be required. Caulk around vent cap spacer
plate with caulking provided. NOTE: Some framing may
be necessary to provide a flat surface against the vent cap
spacer plate and to prevent rain from entering the wall
opening.
I
VentJ
Cap Vent Cap
Spacer
Plate
get
Collar
FIGURE 6
GAS CONNECTION
Make the gas connection between the manual shut offvalve
and the furnace gas control valve with approved _/2"
connectors. Compounds used on threaded joints of gas
piping shall be approved for use with L.P. gas. The gas
lines must be checked for leaks by the installer with soapy
water or liquid detergent, never use an open flame. If
connections are not exposed, a pressure test must be run.
Be sure to disconnect the gas supply line from the appliance
valve bet\_re pressure testing. The manifold pressure is
prc-set at the factory and should be 3.5" w.c. tbr Natural
Gas and 10" w.c. t\)r L.R Gas. The minimum inlet pressure
for Natural Gas is 4.5" w.c. and 11" w.c. for L.P. Gas, "for
purpose of input adjustment". The maximum inlet pressure
should never exceed 7.0" w.c. on Natural Gas or 14" w.c.
on L.P. Gas.
THERMOSTAT INSTALLATION
Follow the instructions included with the therlnostat. Select
a location for the therlnostat on an inside wall approximately
5 feet above the floor where it won't be affected by heat or
cold sources such as direct sunlight, televisions, fireplaces,
hidden hot or cold water pipes, drafts, etc., and a minimum
of 4' tiom the heater. The thermostat must never be placed
in an adjacent room. Connect thermostat wires to
thermostat and mount to wall. Run wire to furnace and
make connections to thermostat wires coming out of top of
furnace. Use insulated staples (provided) to secure wire to
wall.
OPERATION
This unit uses a "step action" valve. When the heater comes
on initially, it operates at a lower pressure to insure proper,
quiet, iguition. After 20 seconds or less, it automatically
steps up to the proper manit\_ld pressure with a discernabte
increase in flame height.
After the heat exchanger has wanned sufficiently, the tan
will automatically come on to efficiently transfer the heat
into the room. NOTE: All but the 40,000 BTU unit (which
is one-speed) have an automatic two-speed Pan.
Page 7

LIGHTING INSTRUCTIONS: DVCF403B, DVCF404B, DVCF653B, DVCF654B
FOR YOUR SAFETY READ BEFORE LIGHTING
WARNING: If you do not follow these instructions exactly, a fire or explosion may result I
causing property damage, personal injury or loss of life. I
A. This appliance has a pilot which must be lighted by • If you cannot reach your gas supplier, call the fire
hand. When lighting the pilot, tStlow these instmc- department.
tions exactly.
BEFORE LIGHTING, smell all around the appliance C.
area for gas. Be sure to smell next to the floor because
some gas is heavier than air and will settle on the
floor.
WHAT TO DO IF YOU SMELL GAS:
Do not try to light any appliance.
Do not touch any electric switch, do not use any
phone in your building.
hmnediately call yore gas supplier tiom a neighbor's
phone. Follow the gas supplier's instructions.
D.
Use only yore hand to push in or slide the gas control
lever. Never use tools. If the lever will not push in or
slide by hand, don't try to repair it, call a qualified sel_Tice
technician. Force or attempted repair may result in a fire
or explosion.
Do not use this appliance if any part has been under water.
hmnediately call a qualified selwice technician to inspect
the appliance and to replace any part of the control system
and any gas control which has been under water.
LIGHTING INSTRUCTIONS
2.
3.
4.
5.
STOP! Read the information on the safety label.
Set thermostat to lowest setting.
Turn off all electric power to the appliance.
Remove cabinet door.
Push in gas control lever slightly and slide right
to "OFF".
Max. (High) Gas Control
Pressure Regulator Lever
NOTE: Knob
can not be
moved to
"OFF" unless it
is pushed in
slightly. Do
not tSrce.
Step Pre_;ure Regulator
6. Wait five (5) minutes to clear out any gas. Then smell
for gas, including near the floor. If you smell gas, STOP!
Follow "B" in the information on the safety label. If you
don't smell gas, go to the next step.
7. Open sight glass cover.
8. Locate red piezo iguitor button on side of gas control.
Locate pilot behind sight glass. (Follow metal pilot tube
9. Slide gas control lever left _ to "Set" and hold
hmnediately begin a series of pushing and releasing the
red piezo ignitor button, while obsel_ing the pilot througl_
the sight glass. Continue to spark until pilot is lit
Continue to hold the gas control lever to "Set" for aboul
one (1) minute after the pilot is tit. Release the gas control
lever and it will return to "Pilot". Pilot should remai_
lit. If pilot goes out, repeat steps 5 thin 9.
,, If gas control lever does not return to "Pilot" whe_
released, STOP and immediately call your service
technician or gas supplier.
• If the pilot will not stay lit after several tries, slide the
gas control lever to "OFF" and call your sela_icetechnicia[
or gas supplier.
10. Close sight glass cover.
11. Slide gas control lever right - to "ON".
12. Replace cabinet.
13. Turn on all electric to the appliance.
from gas control). 14. Set thermostat to desired
TO TURN OFF GAS TO APPLIANCE
Turn thermostat to it's lowest setting.
2. Turn off all electric power to the appliance if sela_iceis to be performed.
3. Remove cabinet door.
4. Push in gas control lever slightly and slide right - to "OFF". Do not tSrce.
5. Replace cabinet door.
Page 8

LIGHTING INSTRUCTIONS: DVCF407B_ DVCF408B_ DVCF557B_ DVCF558B
FOR YOUR SAFETY READ BEFORE LIGHTING
WARNING: If you do not follow these instructions exactly, a fire or explosion may result causing
property damage, personal injury or loss of life.
A. This appliance is equipped with an ignition device which
automatically lights the pilot. Do not try to light the
pilot by hand.
B. BEFORE LIGHTING, smell all around the appliance area
for gas. Be sure to smell next to the floor because some
gas is heavier than air and will setting on the floor.
• If you cannot reach your gas supplier, call the fire
department.
WHAT TO DO IF YOU SMELL GAS:
Do not try to light any appliance.
Do not touch any electric switch: do not use any phone
in your building.
hmnediately call your gas supplier from a neighbor's
phone. Follow the gas supplier's instructions.
C. Use only your hand to push in or slide the gas control
lever. Never use tools. If the lever will not push in or
slide by hand, don't try to repair it, call a qualified
service technician. Force or attempted repair may result
in a fire or explosion.
D. Do not use this appliance if any part has been
water. Ilnmediately call a qualified service
under water.
LIGHTING INSTRUCTIONS
1. STOP! Read the int\_rlnation on the safety label.
2. Set the therlnostat to it's lowest setting.
3. Turn off all electric power to the appliance.
a. This appliance is equipped with an iNlition device which
automatically lights the pilot. Do not try to light the
pilot by hand.
5. Remove cabinet door.
5. Push in gas control lever slightly and slide right _ to
"OFF".
Maxhnum (High)
Pressure Regulator
i i-" __oJ II
Gas Control
• o_ __ NOTE: Lever
lcan not be
ovedto
'OFFunless
iN I v ] it is pushed
d _ in slightly. Do
not force.
[
Step Pressure Regulator
Wait five (5) minutes to clear out any gas. Then small
t\_rgas, including near the floor. If you smell gas, STOP!
Follow "B" in the inforlnation on the safety label. If you
don't smell gas, go to the next step.
8. Slide gas control lever left _ to "ON".
Maximuln (High)
Pressure Regulator Gas Control
Lever
Step Pressure Regulator
9. Replace cabinet door.
10. Turn on all electric power to the appliance.
11. Set thermostat to desired setting.
12. If the appliance will not operate, t\_llow the
instructions "TO TURN OFF GAS TO
APPLIANCE" and call your service technician or
gas supplier.
TO TURN OFF GAS TO APPLIANCE
1. Turn therlnostat to it's lowest setting.
2. Turn off all electric power to the appliance if service is to be pert\tuned.
3. Remove cabinet door.
4. Push in gas control lever slightly and slide _ to "OFF". Do not force.
5. Replace cabinet door.
Page 9

PILOT ADJUSTMENT
Locate the pilot adjustment screw on the valve. The
pilot flame should surround at least the top 3/8" of the
powerpile (pilot generator) or flame sensor (see Figure
7). The pilot is unregulated so it will be operating at
inlet line pressure (Max. 7" w.c. for Natural Gas and
11" w.c. tbr Propane). To decrease the pilot flame,
turn the screw clockwise _ (approximately six full
turns to bottom ofpitot light channel) until you produce
sufficient flame at the minilnum noise level.
PILOT FLAME ADJUSTMENT: Pilottlame
should envelop 3/8 to 1/2 inch of the tip of sensor.
._3/8" to 1/2"
FIGURE 7A
STANDING PILOT
"---'4-to
I i[ 1/2"
FIGURE-7B
I.I.D. PILOT
Pilot Adj. Screw
-
ROBERTSItAW
7200ER-SO4
FIGURE 7C
STANDING PILOT
Pilot Adj. Screw
IN -
ROBERTSItAW
7200IPER-SO4
FIGURE 7D
I.I.D. PILOT
[-1/ 01
3/4
FIGURE 8
TO REMOVE MAIN BURNER FOR
INSPECTION AND CLEANING
1. Turn thermostat to lowest setting and allow furnace to cool.
2. Turn off all electric power to furnace.
3. Remove lower mille.
4. Disconnect gas supply to valve.
5. Disconnect wires from gas vane.
6. Remove 15 screws holding burner door to burner box. Pull
door tbrward to remove complete burner, gas valve assembly.
7. After inspecting and cleaning, place burner assembly back
into burner box and tighten 15 screws. NOTE: Be sure door
gasket is not damaged and will effect a proper seal or pilot
outage will occur.
8. Connect wires back to valve.
9. Connect gas supply back to valve.
10. Turn on electric to furnace.
11. Follow lighting instructions, and replace lower _ille.
It is recommended that the furnace and all components be inspected
at least annually by a qualified service person. This should include
the burner, pilot, heat exchanger, and vent system. Be sure that
the flow of combustion and ventilation air is not obstructed.
IMPORTANT: Keep burner and control compartment clean.
Vacuum control compartment at the start of the heating season
and as often as needed.
PROPER BURNER FLAME
The burner flame may be observed by raising the sight glass cover.
A proper flame will have a dark blue inner mantle that sits right
on top of the burners with a lighter blue outer mantle rising above
the burner (See Figure 8). There may be some yellow where the
pilot flame and burner flame meet. There is no primary air
adjustment on the burner, and proper flame is assured since the
correct manifold pressure and orificing has been done at the factory.
NOTE: It is advised that the burner flames be checked at least
twice during the heating season t\_r any changes in burner flame
characteristics. The appliance area must be kept clear and tree
from combustible materials, gasoline, and other flammable vapors
and liquids. This heater comes fioln the factory with the proper
burner orifice for elevations up to 2,000 feet. Heaters installed
above 2,000 feet must be derated 4% for every 1,000 feet. For the
proper orifice size, find the Model Nmnber and elevation on the
orifice chart. Replace burner orifice.
NATURAL GAS
MODEL 0 to 2000 - 4000 - 6000 - 8.000
NI_4BER 2 000' 4 000' 6 000' 8 000' I0 000'
DVCF403B 32 34 35 36 40
DVCF407B 32 34 35 36 40
DVCF557B 3.6m 29 30 30 31
DVCF653B 25 27 28 29 30
ORDERKIT#498402287-1HIGHALTITUDEKIT
L.P. GAS
MODEL 0to 2.000- 4.000- 6.000- 8.000
iXXEVIBER 2.000' 4000' 6000' 8000' 10.000'
DVCF404B 49 50 51 52 52
DVCF408B 49 50 51 52 52
DVCF558B 44 45 47 48 49
DVCF654B 2.3n_n 44 45 47 48
[ORDER KIT #49840 2287-1 HIGH ALTITUDE KIT
Page 10

DVCF403B, DVCF404B STANDING PILOT DVCF653B, DVCF654B
THERMOSTAT POWER
_1 @ POOV_ER THERMOSTAT
POWER _ CORD
_" _< / _,_ 0 0
I II gli_l _c_,,_I ,It MOTOR)
,
PRANSFO 4JLl
1 , L
_'_'_ [ SWIT(H SWITCH I.../t'_..] _ SWITCH _ SWITCH
<["_L_IT DVCF403, DVCF404 <1 _/Lai_ir _ DVCF653, DVCF654
,_ _wm'_ _11 IL...-_II_"_ PICTORIAL SCHEMATIC
I _ . PICTORIALSCHEMATIC
,_lo_ MOD_L_O_MP_ I°_ MODEL NO. AMPS
_ DVCF403 1.95 I L__._._ DVCF653 3.05
II-- _ DVCF404 1.95 [ DVCF654 3.05
FAN SWITCH
AUXILIARY
LIMIT
DVCF403
DVCF404
LADDER
SCHEMATIC
FAN SWITCH
--5.o
LIMIT SWITCH
[
DVCF654
LADDER
SCHEMATIC
AUXILIARY
LIMIT
-o7
Page 11

DVCF407B, DVCF408B I.I.D. DVCF557B, DVCF558B
m 7/2
BRO'_ _W
PICTORIAL
SCHEMATIC
TRANSFORMER
LIMIT SWITCH FAN
_ SWITCH
ALLXILIARY
LINFIT
fITCH
TH
PV
SP715-NAT.SENSE
OR MV
SP735-L.R
IGN
IHERMOSTAT POWER
I CORD
SPT15-NAT.
OR _fv
SP735-L.R
IGN
DVCF557, DVCF558
PICTORIAL
SCHEMATIC
JMODEL NO. AMPS
DVCF407 2.2
DVCF408 2.25
FAN SWITCH
TCH TRANSFORMER
THERMOSTAT
II
AUXILIARY LIMIT i
DVCF407
DVCF408
LADDER
SCHEMATIC
1
SP715-NAT.[
1
OR
SP735-L.P.
k_ MODEL NO. AMPS
DVCF557 3.3
DVCF558 3.35
FAN SWITCH
SELECTOR
SWIT(H
LIMIT SWITCH
41
AUXILIARY LIMIT
TRANSFORMER
DVCFS57
DVCF558
LADDER
SCHEMATIC
SP:1oRNAT]
[sP:35-L.P.t
Page 12

CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can
cause improper and dangerous operation. Verify proper operation after servicing.
TERMINAL BLOCK WIRING DIAGRAM
_Fml/Limit Switch (Brown)
Selector Switch -1 / r- Power Cord (Black)
(Red) [/ [F Transf°nner (Black)
Lh_t
Motor___JL[]JL .__-Switch
(Red) (Blue)
O MOTOR (Wlfite) O
Power(Green)COrd__..+_.,
Terminal t;oard
Ground (Gree_}otor -
(Green)
_' Selector
'm'_=:_ r"_---_"_---- Switch
--//-- (Black)
Power Cord (White)
P/N91123
DVCF557B, 558B, 653B, 654B
F Fan/Limit Switch (Brown)
|FP°wer Cord (Black)
/ IF Transt`onner (Black)
/11 LhNt
_-_ 1_-_1 [_-]],,---- - Swit ch
u u (Blue)
0MOTOR (White) O
_' Fan
Power Cord_ ____j=_ If===ll r--31 ____Switch
(Green) _-_l F[L-]I1F u (Black)
Tenninat Board _1 | | l L Motor (Black)
Ground (Gree_/totor_l [LTransi`onner(Black )
(Green) L___Power Cord (White)
P/N91122
DVCF403B, 404B, 407B, 408B
MANUAL RESET SWITCH
For your safety this furnace is equipped with a manual reset limit switch. In case of failure by the primary limit switch, this
switch wilt shut the valve do,am completely before unsafe temperatures are reached. After a cool down period, switch must be
manually reset. If outages persist, call a qualified service person.
MAINTENANCE INSTRUCTION
For proper and sate operation, keep furnace and furnace area clean.
At regmlar intervals turn control valve oft; let cool and clean inside
control compartment. To clean cabinet, use only a damp cloth.
Do not use any kind of sotvent or cleaning fluid that could leave a
residue or invisible coating that would burn or give off fumes
when furnace is turned on.
Have the furnace checked, cleaned, and repaired by a qualified
service person for vent system, pilot and burner operation prior
to use each year.
The beatings of the fan motor should be oiled every twelve (12)
months with S.A.E. 20 oil. (See Figure 10).
Follow a regular service and maintenance schedule for sate and
efficient operation.
Examine the venting system as a routine part of the safety
performance check on an annual basis.
OILTUBE /
.¢
FIGURE 10
WARNING: This is a gas-fired appliance. Keep the area clear of gasoline and other flamlnaabte vapors and
liquids. All combustible material must be kept clear of this area to avoid fire or explosion. I
Page l3

OPTIONAL SIDE DISCHARGE KITS
SIDE DISCHARGE ON CASING
1. Use Optional Kit No. 306SR-A.
2. Cut out and remove embossed area on casing side.
3. Remove talockout from inner liner.
4. Place 1-1/2" boot from kit through opening,
matching flanges of boot to knockout on inner liner.
5. Mark screw holes and remove boot.
6. Drill holes with a 1/8" drill.
7. Attach inner boot with screws provided.
8. Place grille into position, drill holes into casing,
and attach with screws provided.
KIT NO. 306SR
SIDE REGISTER - FLUSH
SIDE DISCHARGE (With Extension Boot)
NOTE: Maximum boot length is 10 inches.
1. Use Optional Kit No. 30SRB-A.
2. Cut opening in drywall as shown in Fig. 9.
3. Position plaster ground as shown in Figure 9.
(Optional).
4. Cut out and remove embossed section on casing side.
5. Remove kalockout on inner liner.
6. Put heater into position.
7. Place inner boot into position, mark and cut boot
flush with watt. Place outer boot into position, mark
and cut boot flush with wall.
8. Place boot trim into position, slide inner boot through
wall fiom adjacent room and attach to inner liner.
Slide outer boot through wall from adjacent room
and attach to casing side.
9. Place grill in position and secure to wall.
ROUGH-INS FOR SIDE DISCHARGE
Install plaster mounds as shown in Figure 9. NOTE: When
side discharge Kit No. 30SRB is being used, furnace should be
set exactly 4" fiom side wall.
14-3/8"
SIDE
FIGURE 9
KIT NO. 30SRB
SIDE REGISTER W/BOOT
Page 14

14-PEK KIT INSTRUCTIONS
(14' PLUG EXTENSION KIT)
FOR NON-RECESSED INSTALLATIONS ONLY
90 De_ee
Outside --'+
Corner
©
3FT.
SECTION©
3FT.
SECTION
®
MODEL NO.
DVCF40
DVCF55
DVCF65
LENGTH OFBOTTOM
SECTION (REF. 4)
PLASTIC RACEWAY
5-5/16 Inches
14 Inches
14 Inches
NOTE: Above lengths terminate approximately
2 inches above floor.
UNITS WITH TERMINAL BOARD
STEP #
1. Turn heater off following Section 3 in "Lighting
Instructions" and allow to cool.
2. Turn offall electricity to heater.
3. Remove top louver assembly, tan shroud and fan
blade.
4. Loosen two screws on romex connector.
5. Remove junction box cover plate.
6. Disconnect three power cord terminals and pull
power cord out of top of heater.
7. Insert power cord provided in kit through romex
connector and plug onto terminal board following
wiring diagram found in lighting and operating
instructions.
8. Tighten two screws on romex connector.
9. Replace junction box cover plate.
10. Replace fan blade, fan shroud and top louver
assembly.
11. Snap 90 degree outside corner (Ref. 1) onto 3
foot section (Ref. 2) plastic raceway. Insert power
cord and remove blue backing from adhesive strip
on raceway and apply to side of heater.
12. Insert power cord into second 3-foot section of
raceway (Ref. 3) and remove blue backing and
apply to side of heater, butting up against bottom
of other section.
13. Cut 14-inch long bottom section to required length
(see chart), insert power cord, remove backing
and apply to side of heater.
14. Plug power cord into wall receptacle.
15. Light the heater following lighting instructions.
Page 15

SYMPTOM
Flame too large
Yellow burner flame
Gas Odor
Delayed Ignition
Failure to ignite
Burner won't turn off
Incorrect gas input
Not enough heat
TROUBLE SHOOTING CHART
i.
2.
3.
i.
1.
2.
3.
4.
2.
3.
4.
POSSIBLE CAUSES
Defective operator section of valve, i.
Burner orifice too large. 2.
If installed above 2,000 feet. 3.
Clogged burner ports. 1.
Obstructions around vent cap. 2.
Gas leak. i.
Pilot flame too small. I.
Burner ports clogged at pilot. 2.
Low gas pressure. 3.
Pilot decreases in size when main 4.
burners come on.
Main gas off. i.
Thermostat not set high enough to call 2.
for heat.
Clogged burner orifice. 3.
Thermostat wired wrong or defective. 4.
Defective or damaged thermostat wire, 1.
or themmstat.
Thermostat location. 2.
Defective or sticking valve. 3.
Excessive gas pressure. 4.
I. Gas input not checked.
2. Clogged orifice.
i. Furnace undersized.
2. Thermostat set too low.
3. Incorrect supply pressure.
CORRECTIVE ACTION
Replace valve.
Check with local gas company for proper orifice
size and replace.
See orifice chart, page 10.
Remove main burner and check for obstructions in
throat, ports, and orifices. Clean - but do not enlarge
ports or orifices.
Make sure area around vent cap is clear, be sure
vent system is sealed.
See Page 1.
Adjust pilot flame.
Clean burner ports (do not enlarge).
Check gas supply pressure.
Supply piping is too small. Consult local gas
company or competent installer.
Open all manual gas valves.
Set thermostat to higher temperature.
Clean burner orifice (do not enlarge).
Check wiring, jump across thermostat terminals at
valve, if valve open, re-check wires, replace thermostat.
Can be checked by removing wire from valve temlinal.
If valve goes of'f, replace wire or thermostat.
Follow instructions, check location.
Replace valve.
Contact utility supplying gas.
i. Re-check gas input.
2. Clean orifice with a smooth wood toothpick,
do not enlarge.
I. This is especially true when a dwelling or room is
enlarged. Have the heat loss calculated and
compare to furnace output. Your gas company can
supply you with this information. If furnace is
undersized, replace with correct size unit.
2. Raise temperature setting.
3. Check supply pressure.
Too nmch heat i. Thermostat set too high. I. Lower temperature setting.
2. Combination control valve stuck open. 2. Replace combination control valve.
1. Weak thennocouple.
2. Input too high.
3. Cover around pilot lighter hole not
air tight.
4. Vent robes not properly installed or
sealed.
Pilot and main burner
go out during normal
operation
1. Check millivoltage and replace if low.
2. Check input rate.
3. Tighten wing nuts securing cover and sight glass.
Check and replace gasket if needed.
4. Follow instructions. Check both exhaust and air
intake robes, and vent cap. Be sure all gaskets are
in place and properly sealed. Use only tubes and
vent cap supplied. Do not alter vent tubes or cap.
Page 16

SYMPTOM
Burner won't tuna on
(STANDING PILOT)
Pilot won't light, or
stay lit
(Ll.D. PILOT)
Pilot won't light
TROUBLE SHOOTING CHART -Continued
POSSIBLE CAUSES
1. Gas valve not turned on.
2. No voltage to valve.
3. Defective thermostat.
4. No 115 W. Line voltage.
5. Gas valve defective.
6. Manual reset switch not engaged.
i. Air in line.
2. Defective thermoeouple
3. Pilot flame too low.
4. Manual reset switch not engaged.
i. Sparker won't work.
2. Sparker won't light pilot.
3. Manual reset switch not engaged.
CORRECTIVE ACTION
i. Turn gas valve to "on" position.
2. Check for 24 Volts to valve from transformer.
3. Check wall thermostat.
4. Provide line voltage.
5. Replace gas valve.
6. Depress red button on switch.
1. Bleed line.
2. Replace thermocouple.
3. Adjust pilot flame.
4. Depress red button on switch.
1. Check wire connections, provide adequate
ground.
2. {a} Pilot flame too small.
{b} Turn valve to "on" position.
{c} Check for pilot restriction.
3. Depress red button on switch.
SERVICE RECORD SERVICE RECORD
Page 17

DIRECT VENT COUNTERFLOW WALL FURNACE
MODELS:
DVCF403B-R, DVCF404B-R
DVCF407B-R, DVCF408B-R
DVCF557B-R, DVCF558B-R
DVCF653B-R, DVCF654B-R
SPARK IGNITER -
I.I.D.
THERMOSTAT T
VENT ASSEMLBY
BURNER ASSEMBLY
DVCF40B-R, DVCF55B-R, DVCF65B-R SERIES
Prices and specifications subject
to change without notice.
All prices are F.O.B. factory.
Mr. Contractor, we only sell parts through our
wholesalers, but the prices listed are for your
convenience. Forprolnpt parts service, contact the
wholesaler from which you purchased your Cozy
heater. NOTE: Parts & schematic drawings on
current models are shown at
,_-vvw.cozyheaters.com.
Page 18

HOW TO PROPERLY ORDER PARTS
In addition to part description and part nmnber, please give model nmnber, serial nmnber, and type of gas used.
NAT, DVCF403B-R DVCF407B-R DVCFS57B-R DVCF653B-R
MODEL NUMBER L,P. DVCF404B-R DVCF408B-R DVCFS58B-R DVCF654B-R
REE PART LIST PART LIST PART LIST PART LIST
PARTDESCRIPTION NO. NO. PRICE NO. PRICE NO. PRICE NO. PRICE
Casing Side, Right la 34065 $56.10 34065 $56.10 34560 $61.30 34560 $61.30
Casing Side, Left lb 34055 $56.!0 34055 $56.!0 34550 $61.30 34550 $61.30
Center Front Panel Assembly 1c 34104 $27.80 34104 $27.80 30534 $28.80 30534 $28.80
Top Assembly ld 34050 $10.60 34050 $10.60 34050 $10.60 34050 $!0.60
Upper Back Assembly le 34080 $42.80 34080 $42.80 34080 $42.80 34080 $42.80
Lower Back Assembly If 34090 $36.60 34090 $36.60 34575 $40.40 34575 $40.40
Bottom Assembly lg 34070 $!6.10 34070 $16.10 34070 $16.10 34070 $16.10
Casing Mounting Brackets NIA *30260 $!.20 *30260 $1.20 *30260 $1.20 *30260 $1.20
Liner Assembly 2 34115 $81.30 34115 $81.30 34600 $87.60 34600 $87.60
Fan Shroud Assembly 3 34140 $23.80 34140 $23.80 34140 $23.80 34140 $23.80
Top Louver 4 34100 $16.30 34100 $16.30 34590 $17.70 34590 $17.70
Bottom Louver Assembly 6 30100 $31.60 30100 $3! .60 30100 $31.60 30100 $31.60
Upper Front Shield 7 30250 $3.50 30250 $3.50 30250 $3.50 30250 $3.50
Switch Box 8 30252 $7.10 30252 $7.10 30450 $7.20 30450 $7.20
Switch Box Cover 9 30253 $2.80 30253 $2.80 30253 $2.80 30253 $2.80
Lower Front Shield !0 30256 $5.10 30256 $5.10 30256 $5.10 30256 $5.10
Motor Mounting Bracket 11 *34088 $3.60 *34088 $3.60 *34579 $2.10 *34579 $2.10
Burner 12 72107 $38.20 72107 $38.20 72107 $38.20 72107 $38.20
Pilot Bracket 53 34440 $4.00 34440 $4.00 34440 $4.00 34440 $4.00
Valve, 7200ER, Natural Gas 13 72090 $137.90 N/A N/A NIA N/A 72090 $137.90
Valve, 7200ER, L.P. Gas 13 72091 $!37.90 N/A N/A N/A N/A 72091 $137.90
Valve, 72001PER, Natural Gas 13b N/A N/A 72092 $129.00 72092 $129.00 N/A N/A
Valve, 72001PER, L.P. Gas 13b N/A N/A 72093 $129.00 72093 $129.00 NIA N/A
Manifold 14 72103 $19.10 72103 $!9.10 72103 $19.10 72103 $19.10
Burner Orifice, Natural Gas 15 72147 $3.40 72147 $3.40 72140 $3.40 72142 $3.40
Burner Orifice, L.P. Gas 15 72149 $3.40 72149 $3.40 72141 $3.40 72143 $3.40
Fan Motor !6 72108 $73.90 72108 $73.90 72110 $83.90 72110 $83.90
Fan Blade 17 78101 $24.20 78101 $24.20 78101 $24.20 78101 $24.20
Rubber Grommet 18 78010 $3.00 78010 $3.00 78010 $3.00 78010 $3.00
Limit Switch 60T11-L220F 19 N/A N/A NIA NIA 72160 $5.90 72160 $5.90
Limit Switch 60T11-L180F 19 78065 $5.90 78065 $5.90 N/A N/A N/A N/A
Fan Switch 60T12-120-15 Deg. F 20 78067 $6.10 78067 $6.10 78067 $6.10 78067 $6.10
Speed Switch 60T13-F160-30 21 NIA NIA N/A N/A 78066 $8.90 78066 $8.90
Aux. Limit Switch 60T15-L350 22 78086 $9.30 78086 $9.30 78086 $9.30 78086 $9.30
Thermostat 24 Volt 23 78355 $20.00 78355 $20.00 78355 $20.00 78355 $20.00
Transformer 24 78069 $23.50 78069 $23.50 78069 $23.50 78069 $23.50
Transformer Plate N/A 34089 $3.80 34089 $3.80 34089 $3.80 34089 $3.80
Terminal Board 35 78300 $5.00 78300 $5.00 78300 $5.00 78300 $5.00
Pilot 0.140.512, Natural Gas 25 72020 $22.70 NtA N/A N/A N/A 72020 $22.70
Pilot 0.140.502, L.P. Gas 25 72021 $22.70 N/A N/A NiA N/A 72021 $22.70
Cozy Handle 26 84003 $2.30 84003 $2.30 84003 $2.30 84003 $2.30
Thermostat Wire 27 74518 $1.30 74516 $1.30 74518 $1.30 74518 $1.30
Thermocouple Q309A1954 28 78095 $11.40 N/A NiA N/A N/A 78095 $11.40
Insulated Staples 29 74209 $1.20 74209 $1.20 74209 $1.20 74209 $1.20
Pilot 3S-24F_ Natural Gas 25b N/A N/A 72098 $37.30 72098 $37.30 N/A N/A
Pilot 3S-24F, L.P. Gas 25b N/A N/A 72097 $33.70 72097 $33.70 N/A N/A
Wiring Harness 30 72251 $18.80 72251 $18.80 72250 $21.10 72250 $21.10
Flame Sensor S-1 28b N/A N/A 72025 $14.10 72025 $14.10 N/A N/A
-CONTINUED -
Mr. Contractor, we only sell parts through our wholesalers, but the prices listed above are for your conve-
nience. For prompt parts service, contact the wholesaler from which you purchased your Cozy heater. NOTE:
Parts &schematic drawings on current models are shown at www.cozyheaters.com.
Page 19
MARCH 2005

HOW TO PROPERLY ORDER PARTS
In addition to part description and part nmnber, please give model nulnber, serial nmnber, and type of gas used.
NAT. DVCF403B-R DVCF407B-R DVCFS57B-R DVCF653B-R
MODEL NUMBER L.P, DVCF404B-R DVCF408B-R DVCFSS8B-R DVCF654B-R
REF. PART LIST PART LIST PART LIST PART LIST
PART DESCRIPTION NO. NO. PRICE NO. PRICE NO. PRICE NO. PRICE
Power Cord N/A 78213 $4.70 78213 $4.70 78213 $4.70 78213 $4.70
Sight Glass Assembly 31 43252 $6.50 43252 $6.50 43252 $6.50 43252 $6.50
Sight Glass Cover 32 43258 $1.50 43258 $1.50 43258 $1.50 43258 $1.50
Si,qht Glass Gasket 33 72067 $1.50 72067 $1.50 72067 $1.50 72067 $1.50
Burner Box Gasket 34 72059 $5.90 72059 $5.90 72059 $5.90 72059 $5.90
Slip Joint Assembly w/Gaskets 50 34220 $27.20 34220 $27.20 34220 $27.20 34220 $27.20
Slip Joint Gasket N/A 72057 $4.70 72057 $4.70 72057 $4.70 72057 $4.70
Slip Joint Ring Gasket 61 72056 $2.30 72056 $2.30 72056 $2.30 72056 $2.30
Slip Jt. Ring Gsk. (2 pc. Graphite) N/A 72058 $4.70 72058 $4.70 72058 $4.70 72058 $4.70
Flue Outlet Pipe Gasket 36 72055 $1.90 72055 $1.90 72055 $1.90 72055 $1.90
Air Intake Pipe Gasket 37 72054 $3.80 72054 $3.80 72054 $3.80 72054 $3.80
Heat Exchan,qer Cover Plate 52 34195 $3.60 34195 $3.60 34195 $3.60 34195 $3.60
Heat Exchanger Cover Plate Gasket 38 72053 $1.60 72053 $1.60 72053 $1.60 72053 $1.60
Burner Box Inlet Gasket 39 72052 $7.00 72052 $7.00 72052 $7.00 72052 $7.00
Exhaust Pipe Gasket 40 72051 $2.30 72051 $2.30 72051 $2.30 72051 $2.30
Manifold Gasket 55 72068 $1.50 72068 $1.50 72068 $1.50 72068 $1.50
Piezo Igniter 41 70050 $5.60 N/A N/A NIA N/A 70050 $5.60
Igniter Wire 0.028.508 42 72022 $4.70 N/A NIA N/A N/A 72022 $4.70
Spark Igniter SP715, Natural Gas 43 N/A NIA 78070 $104.50 78070 $104.50 N/A NIA
Spark Igniter SP845, L.P. Gas 43 N/A NIA 78088 $143.30 78088 $143.30 N/A NIA
Heat Exchanger Kit 44 34805 $272.40 34805 $272.40 34810 $274.60 34825 $285.60
Vent Cap Assembly Complete 45 34250 $127.90 34250 $127.90 34250 $127.90 34250 $127.90
Vent Cap Spacer Plate Assembly 46 34273 $14.50 34273 $14.50 34273 $14.50 34273 $14.50
Vent Cap Mounting Kit 47 34330 $10.70 34330 $10.70 34330 $10.70 34330 $10.70
Air Intake Pipe Assembly 48 34280 $28.40 34280 $28.40 34280 $28.40 34280 $28.40
Vent Exhaust Pipe Assembly 49 34290 $22.20 34290 $22.20 34290 $22.20 34290 $22.20
Elbow 3/8x90 Degree NtA 84501 $2.10 84501 $2.10 84501 $2.10 84501 $2.10
Air Drop Assembly 51 34201 $124.60 34201 $124.60 34630 $140.16 34630 $140.10
Burner Box Bottom Assembly 58 34400 $50.90 34400 $50.90 34400 $50.90 34400 $50.90
Burner Access Door 56 34425 $11.00 34425 $11.00 34425 $11.00 34425 $11.00
Burner Access Gasket 57 72065 $8.20 72065 $8.20 72065 $8.20 72065 $8.20
90 De_. Pilot Fitti% N/A N/A N/A 70352 $10.70 70352 $!0.70 N/A N/A
Pilot Tube Bracket 60 34475 $2.00 34475 $2.00 34475 $2.00 34475 $2.00
Vent Terminal Shield N/A 34950 $60.80 34950 $60.80 34950 $60.80 34950 $60.80
Pilot Tubing w/Fittings NIA 78452 $5.40 78452 $5.40 78452 $5.40 78452 $5.40
Pilot Tube Gasket 59 72063 $1.20 72063 $1.20 72063 $1.20 72063 $1.20
Mr. Contractor, we only sell parts through our wholesalers, but the prices listed above are for your
convenience. For prompt parts service, contact the wholesaler from which you purchased your Cozy
heater. NOTE: Parts & schematic drawings on current models are shown at www.cozyheaters.com.
Page 20
MARCH 2005
This manual suits for next models
7
Table of contents
Other COZY Wall Furnace manuals
Popular Wall Furnace manuals by other brands

Empire Heating Systems
Empire Heating Systems GWT-50-2 Installation instructions and owner's manual

Braemar
Braemar WF2000 Owner operating instructions

HouseWarmer
HouseWarmer HWDV080DV(N Installation instructions and owner's manual

Empire Heating Systems
Empire Heating Systems FAN TYPE VENTED WALL FURNACE FAW-55IP Installation instructions and owner's manual