enphase EP200G-NA-02-RSD User manual

Figure 1: Layout of auxiliary contacts in Enpower, Terminals for connecting RSD are indicated in red
Each Enphase Storage system with IQ8 PV requires the presence of a rapid shutdown (RSD) switch. Rapid shut down switch is needed to disconnect
all PV panels, battery and generator systems in the building/home to ensure the safety of maintenance technicians. When the RSD switch is engaged,
the Enphase storage system will be shutdown and the home is connected to the grid.
QUICK INSTALL GUIDE Model number: EP200G-NA-02-RSD
Instructions to use the Rapid shutdown
(RSD) switch connections
The contents of the Rapid shurdown (RSD) switch connections and how to use
them are described below:
Components that are needed for RSD connection
S.No Component Source of Components Qty
1RSD switch RSD kit (SKU: EP200G-NA-
02-RSD)
1
2NEC label 1 RSD kit (SKU: EP200G-NA-
02-RSD)
1
3NEC label 2 RSD kit (SKU: EP200G-NA-
02-RSD)
1
4Cable head assembly Enpower R2 literature kit 4
512 AWG wire (for RSD
connections)
Provided by Installer Length as
required
68-14 AWG wire (for
Ground bar)
Provided by Installer Length as
required
7Screw drivers (PZ2) Provided by Installer 1
Wiring the auxiliary contacts in Enpower R2
A ) The Enpower R2 comes with multiple auxiliary contacts as indicated
in Figure 1.
B ) The contacts NC3 and NC4 are for wiring the RSD (indicated in the
red box in Figure 1).
C ) The Enpower literature kit comes with cable assembly header which
is shown in Figure 2a.
D ) Insert the ferrule of the cable header assembly to the feed through
header which is indicated in Figure 2b.
E ) Tighten the screws on the top (torque 0.22Nm to 0.25Nm) to secure
the wires.
F ) Repeat steps D and E to complete wiring of other 3 terminals of
NC3 and NC4.
© 2021 Enphase Energy. All rights reserved. Enphase, the Enphase logo, Enpower smart switch, Encharge storage system, Envoy, Combiner, Microinverter,
Installer Toolkit, Enlighten and other trademarks or service names are trademarks of Enphase Energy, Inc. Data subject to change. 10-18-2021
2
1
200 ±5
15 ±5
12 3
(SEE NOTE : 6)
COLOR RING
STEP-DOWN END
NOTES:
APPLICABLE STANDARDS:
1.
IPC/WHMA-A-620: CLASS 2 REQUIREMENTS AND ACCEPTANCE
FOR CABLE AND WIRE HARNESS ASSEMBLIES.
WIRE IS TO BE TERMINATED ON AN AUTOMATIC MACHINE. THE APPLICATORS OR CRIMPING APPARATUS TO BE AS
2.
SPECIFIED BY THE TERMINAL MANUFACTURER. TERMINAL CRIMPS MUST WITHSTAND A MINIMUM PULLOUT FORCE
AS PER STANDARD UL 486A.
MUST BE MANUFACTURED UNDER UL RECOGNISED COMPONENT WIRING HARNESS (ZPFW2) PROGRAM.
3.
UL MARKINGS MUST BE ON SMALLEST SHIPPING CARTON.
4.
EACH SHIPMENT SHALL INCLUDE A CERTIFICATE THAT:
- INCLUDES THE UL WIRE STYLE(S)
- THE CONNECTOR MANUFACTURER'S NAME AND PARTNUMBER AND
- REFERENCES THE PURCHASE ORDER AND ENPHASE ENERGY DRAWING NO.
USE OF LOOSE PIECES OR HAND FEED TERMINATION IS NOT ACCEPTABLE.
5.
LABEL WITH CABLE PART NUMBER, REVISION AND MANUFACTURE ID.
6.
REVISIONS
REV
DESCRIPTION
CHECKED
DATE
01
INITIAL RELEASE : ECO-005253
HW
27 APR 21
A3
EPDM VERSION
© COPYRIGHT 2019 ENPHASE ENERGY. ALL RIGHTS RESERVED. ALL THE
TRADEMARKS ARE OWNED BY ENPHASE OR ITS AFFILIATED COMPANIES AND
SHALL NOT BE USED OR REPRODUCED IN ANY FORM OR FOR ANY PURPOSE
WHATSOEVER, WITHOUT THE EXPRESS WRITTEN PERMISSION OF ENPHASE
ENERGY.
FINISHED PART (INCLUDING ALL SUB-COMPONENTS) MUST
BE ROHS COMPLIANT (EU ROHS DIRECTIVE 2015/863/EU).
MANUFACTURER WILL BE REQUIRED TO CERTIFY ROHS
COMPLIANCE. IF THERE IS A CONFLICT BETWEEN THE
SPECIFICATIONS AND ROHS COMPLIANCE, THE VENDOR
MUST CONTACT ENPHASE ENERGY FOR CLARIFICATION.
MASS(g)
FINISH
MATERIAL
ALL DIMENSIONS ARE IN MILLIMETERS.
Cable Assy Header Enpower 200G R2
27 APR 21
PROPRIETARY AND CONFIDENTIAL
THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF
ENPHASE ENERGY. ANY REPRODUCTION IN PART OR AS A WHOLE WITHOUT THE
WRITTEN PERMISSION OF ENPHASE ENERGY IS PROHIBITED.
HENRY W
27 APR 21
DATE
DATE
ENGINEER
2:1
SCALE
TOLERANCES AND DIMENSIONS IN
ACCORDANCE WITH ASME Y14.5 (2009)
HENRY W
DRAWN
840-01451
01
THIRD ANGLE
PROJECTION
SHEET
SIZE
TITLE
SHEET
PART NUMBER
REV
1 of 1
DO NOT SCALE
INDIQUBE GOLFVIEW
BANGALORE, INDIA
WWW.ENPHASE.COM
A A
B B
C C
D D
E E
F F
8
8
7
7
6
6
5
5
4
4
3
3
2
2
1
1
Figure 2a: Cable header assembly
2. Tighten these
screws to hold the
wires in place
1. Insert wires
here
Figure 2b: Feed through header
I/O - 1
(24V, 1A)
I/O - 2
(24V, 1A)
Gen - I/O
(24V, 1A)
NO1 NO2 NC1 NC2 NO3
RSD
NC3 NC4
AC CombinerPV/Storage Generator

Wiring the switch inside the Rapid Shutdown (RSD)
enclosure
A ) Open the front face of the RSD by loosening the two screws on the
front face.
B ) Create wiring conduit in the top/bottom portion of the enclosure. There
are knock outs provided for this.
C ) Screw in 12AWG wires to terminals marked 1,2,3 and 4 of the switch.
Torque values can be found in the below table.
D ) Screw in 8-14 AWG wire to the Ground bar within the enclosure.
Torque values can be found in the below table.
E ) Draw the wires out through the conduit which has been created in the
enclosure.
F ) Secure the switch to the rear plate of the enclosure by torquing the
screws as indicated in gure 3. There are 2 screws to be torqued. The
screws can be found in the RSD kit.
G ) Fit the front face and torque the screws. Torque values can be found in
the below table.
H ) The torque rating of each of these wires/screws are as below:
S.No Point of Torquing Torque (Nm)
1Terminal 1,2,3,4 1.8
2Ground 0.8-1.4
3Front cover 1.5
4Screws to secure Switch 0.6
3
Figure 3: Final RSD wiring
Mounting the RSD
A ) Identify a location which is near the Enpower smart switch to mount
the RSD. Please note that Enpower and RSD cannot be more than 200
ft apart.
B ) There are 2 mounting points on the back plate of the enclosure. They
are marked by red boxes in Figure 4 below.
C ) Installers can use any type of mounting as long as they are not
exceeding the diameter of each xing point.
D ) It is recommended that installers use #8 screw, with a minimum rec-
ommended length of 1.5 inches. The type of screw is to be determined
by installer based on where they wish to mount the RSD.
4
Connect wires from RSD and Enpower
A ) Connect the cables connected from Terminal 1 and 2 of the RSD to the
yellow portion of the cable header assembly (Figure 2) from NC3 and
crimp it.
B ) Connect the cables connected from Terminal 3 and 4 of the RSD to the
yellow portion of the cable header assembly (Figure 2) from NC4 and
crimp it. Refer to Figure 5 and table below.
C ) Connect the cable from the grounding bar to the Ground bar in
Enpower.
D ) Ensure Cables are properly sheathed and are not lose or exposed to
environment.
5
Figure 4: Mounting location in backplate of RSD
Screw for
securing
switch
Terminal 3
Terminal 2
Terminal 4
Terminal 1
Ground bar
Screw for
securing
switch

Functional tests
A ) Use the ITK to check if the RSD is working as desired. When the RSD is
engaged (turned to OFF position) , all the relays except the MID will be
open. Only the MID relay will be closed. Hence effectively isolating the
home from the PV, battery and generator.
B ) In order to check if the RSD is functioning as required, open the ITK
and manoeuvre to the Enpower page.
C ) Turn the RSD rotary handle to OFF position.
D ) In the ITK’s Enpower page, click on “View Live details”.
E ) In the view live details page, the relay status should be as shown in
Figure 6 below. The MID relay should be closed and all other relays
should be in open position.
F ) When RSD handle is shifted to ON position, the Enpower goes back
into functioning normally as it was.
6
Figure 6: ITK checking of Relay status
Instructions for initiating Rapid Shut down and
Enpower System shut down
Rapid shut down of the system can be initiated by turning the handle
of the RSD to the OFF position. With this one step the entire Enphase
system (PV arrays , Encharge battery, Generators connected to
Enpower) is shut down and the regulatory requirement for rapid shut
down are also met.
NOTE: For more details of the RSD switch options and wiring instruc-
tions, please refer to Enpower R2 QIG or the Ensemble R2 design guide
8
Completetheinstallationbyafxingthelabels
A ) In order to identify the Rapid shut down switch the following label (in
Figure 7) needs to be pasted at a distance of not more than 3ft (1m)
from the RSD, as mandated by the NEC code.
7
Figure 7: Label for identifying the RSD
Figure 8: Sticker for showing portions of PV array which will be shut down using RSD
I/O - 1
(24V, 1A)
I/O - 2
(24V, 1A)
Gen - I/O
(24V, 1A)
NO1 NO2 NC1 NC2 NO3
RSD
NC3 NC4
AC CombinerPV/Storage Generator
B ) In order to earmark the parts of the array which will be shut down
by using the RSD the following sticker (Figure 8) needs to be pasted
in the location specied by the Authority having jurisdiction or at a
distance of not more than 3ft (1m) from from the RSD, as mandated
by the NEC code.
Dry Contact Terminals RSD Terminals to
be connected
NC3 Terminal 1 Terminal 1
Terminal 2 Terminal 2
NC4 Terminal 1 Terminal 3
Terminal 2 Terminal 4
Figure 5: Connecting wires from RSD and Enpower
MID EC1 L1 EC1 L2 NFT L1 NFT N
Closed Open Open Open Open
Cable Header
Assembly
(refer Fig 2a)
12 AWG
wires

Enphase Customer Support: enphase.com/en-us/support/contact
Safety and Advisory Symbols
+DANGER: This indicates a hazardous situation, which if not avoided, will
result in death or serious injury.
*WARNING: This indicates a situation where failure to follow instructions
may be a safety hazard or cause equipment malfunction. Use extreme
caution and follow instructions carefully.
✓NOTE: This indicates information particularly important for optimal system
operation. Follow instructions carefully.
Safety Instructions
+DANGER: Risk of electric shock. Risk of re. Only qualied electricians should
install, troubleshoot, or replace the Enpower.
+DANGER: Risk of electric shock. Risk of re. Do not attempt to repair the
Enpower. Tampering with or opening the Enpower will void the warranty.
If the Enpower fails, contact Enphase Customer Support for assistance at
enphase.com/en-us/support/contact.
+DANGER: Risk of electric shock. Do not use Enphase equipment in a manner
not specied by the manufacturer. Doing so may cause death or injury to
persons, or damage to equipment.
+DANGER: Risk of electric shock. Do not install the Enpower without rst
removing AC power from the photovoltaic system and ensuring that the DC
switch on the Enphase Encharge batteries are off. Disconnect the power
coming from the photovoltaics and ensure that the DC switch on the En-
charge batteries are off before servicing or installing.
+DANGER: Risk of electric shock. Risk of re. Do not work alone. Someone
should be in the range of your voice or close enough to come to your aid
when you work with or near electrical equipment.
+DANGER: Risk of re. Do not allow or place ammable, sparking, or explosive
items near the Enpower.
+DANGER: Risk of electric shock. In areas where ooding is possible, install
the Enpower at a height that prevents water ingress.
*WARNING: Risk of equipment damage. Enpower is shipped and stored on its
back. The upright position is only needed when installed.
*WARNING: You must install the Enpower only on a suitable wall using an
Enphase wall-mount bracket.
*WARNING: Before installing or using the Enpower, read all instructions and
cautionary markings in this guide and on the equipment.
*WARNING: Do not install or use the Enpower if it has been damaged in any
way.
*WARNING: Do not sit on, step on, place objects on, or insert objects into the
Enpower.
*WARNING: Do not place beverages or liquid containers on top of the
Enpower. Do not expose the Enpower to ooding.
✓NOTE: Perform installation and wiring, including protection against lightning
and resulting voltage surge, in accordance with all applicable local electrical
codes and standards.
✓NOTE: Because Encharge is grid forming, you must install signage in accord-
ance with NEC articles 705, 706, and 710.
✓NOTE: Using unapproved attachments or accessories could result in dam-
age or injury.
✓NOTE: Install properly rated over current protection as part of the system
installation.
✓NOTE: To ensure optimal reliability and to meet warranty requirements, the
Enpower must be installed and/or stored according to the instructions in this
guide.
✓NOTE: The Enpower is compatible only with the IQ Envoy or Envoy
S-metered communications gateway properly tted with USB hub, USB
radios, and production and Consumption/PCS CTs. The Envoy is required
for operation of the Enpower. Earlier versions of the Enphase Envoy commu-
nications gateway are incompatible.
✓NOTE: The Enphase Enpower is intended to operate with an Internet connec-
tion through the Envoy. Failure to maintain an Internet connection may have
an impact on the warranty. See Limited Warranty for full terms and services
(enphase.com/warranty).
✓NOTE: When replacing an Enphase Enpower, you must replace it with an
Enpower of the same type, with the same AC current rating.
✓NOTE: Properly mount the Enpower. Ensure that the mounting location is
structurally suited to bearing the weight of the Enpower.
✓NOTE: During use, storage, and transport, keep the Enpower:
• Properly ventilated
• Away from water, other liquids, heat, sparks, and direct sunlight
• Away from excessive dust, corrosive and explosive gases, and oil smoke
• Away from direct exposure to gas exhaust, such as from motor vehicles
• Away from falling or moving objects, including motor vehicles. If mounted
in the path of a motor vehicle, we recommend a 91cm (36-inch)
minimum mounting height
• In a location compliant with re safety regulations
• In a location compliant with local building codes and standards
1NOTE: While Enpower provides capability for connection of a generator, it
does not presently support use with generators. Do not attempt to connect a
generator until Enpower is ready to support a generator. This functionality is
reserved for future use and will require an upgrade process to be followed by
a qualied electrician.
2NOTE: Enpower is not suitable for use as service equipment in Canada.
SAFETY
IMPORTANT SAFETY INSTRUCTIONS. SAVE THESE INSTRUCTIONS. This guide contains important instructions that you must follow during installation
and maintenance of the Enphase Enpower. Failing to follow any of these instructions may void the warranty (enphase.com/warranty).
In Case of Fire or Other Emergency
In all cases:
• If safe to do so, switch off the AC breaker for the Enpower circuit, and if an
isolator switch is present, switch off the AC isolator for the Enpower circuit.
• Contact the re department or other required emergency response team.
• Evacuate the area.
In case of re:
• When safe, use a re extinguisher. Suitable types are A, B, and C dry chemical
re extinguishers. Additional extinguishing media include carbon dioxide, or
alcohol-resistant foams.
In case of ooding:
• Stay out of water if any part of the Enpower or wiring is submerged.
• If possible, protect the system by nding and stopping the source of the
water, and pumping it away.
• If water has contacted the UNIT, call your installer to arrange a inspection.
If you are sure that water has never contacted the battery, let the area dry
completely before use.
In case of unusual noise, smell or smoke:
• Ensure nothing is in contact with the Enpower or in the venting area on top of
the Enpower.
• Ventilate the room.
• Contact Enphase Customer Support at enphase.com/en-us/support/contact.
Safety Instructions, continued
Environmental Protection
ELECTRONIC DEVICE: DO NOT THROW AWAY. Waste elec-
trical products should not be disposed of with household
waste. Refer to your local codes for disposal requirements.
Other enphase Switch manuals