A
BOUT
…………………………………………………………………………………………………………....
1
S
PECIFICATION
…………………………………………………………………………………………………
2
S
AFETY AND WARNING
……………………………………………………………………………………...
3
C
ONNECTION
……………………………………………………………………………………………………
3
I
NSTALLATION
…………………………………………………………………………………………………..
4
T
ROUBLE SHOOTING
…………………………………………………………………………………………
4
O
RDERING CODE
………………………………………………………………………………………………
4

Doc.Ref No.:m92E/om/101
Issue No.:12
9000C
A
BOUT
I
SOLATED
C
ONVERTER
9000C
S
ERIES
•9000C Series are compact yet rugged 4 wire Signal isolators
designed for conditioning and safe guarding custom-built wide
range of voltage and current field signals. Field Signal is then
isolated and converted to standard instrumentation signals,
acceptable to commercially off the shelf (COTS) automation
products.
•Equipped with Advanced Extended Power Supply Range of 20V to
265V AC or DC.
•9000C model is further enhanced with Switch selectable I/O
configuration for I/O ranges i.e. 0/4-20mA, 0/1-5V and 0-10V. This
feature allows user to have freedom to change 0/4-20mA, 0/1-5V
and 0-10V I/O types only, using switch available on side of device
and with minor tuning using front accessible trim-pots, depending
upon field requirements.
•9000C is equipped with Built in transmitter power supply (TPS)
that can drive filed transmitters in case of 4-20mA DC input signal.
•9000C Series isolators act as signal distributor when used with
more number of outputs.
•9000C Offers excellent accuracy and stability delivering reliable
operation in hostile environments with full 3 port isolation between
input, output and power supply.
•9000C Series are flexible for DIN rail mounting and easily
installable. Its compact design consumes less space and hence
reduces cost of overall installation.
•
9000C with HART Pass through is dedicated Signal Isolator, for 2-
wire HART Programmable devices, with HART Pass capability
and all enhanced features of 9000C Series and can provide an
additional Output of Current for Non HART compatible devices.
F
EATURES
•
Slimmest in its class:12.5mm Single output and 17.5mm Dual
output
•
Extended Universal Power Supply Range: 20V to 265V DC or AC
Capable to provide Safe and Sufficient Power For Field
Transmitter
•
Switch Selectable Input/Output. User can change I/O as per their
requirement.
•
Rugged & accurate 4 wire isolator
•
Up to 2 outputs with Short Circuit Protection
•
Wide zero & span adjustment limits
•
1.5KV AC Isolation between I/P, O/P and Supply
•
High CMRR and NMRR
•
High output Load Driving Capability
SOP & DOP
•Universal AC/ DC Aux. supply
•Front Calibration Facility
•Signal Isolator, dual output
•Three port isolation
•Excellent long term stability
•Built in transmitter’s power
•Slim DIN rail enclosure

Doc.Ref No.:m92E/om/101
Issue No.:12
9000C
Dimensions
9000C
SOP
9000C
DOP
9000C
SOP/DOP
HART
PASS
All dimensions are in mm.
S
PECIFICATION
Input
Input Type Voltage/ Current
Input Range
‘S” Version: 4-20mA (Standard)
‘M” Version: 0/4 to 20mA , 0/1 to 5V , 0 to 10V
(DIP switch selection)
‘H’ Version: 4-20mA, HART Pass
Input Impedance Current I/P ≤10 Ω;
Voltage I/P ≥1 MΩ
Output
Output Type Voltage/Current
Output Range
‘S” Version: 4-20mA (Standard)
‘M” Version: 0/4 to 20mA , 0/1 to 5V , 0 to 10V
(DIP switch selection)
‘H’ Version: 4-20mA, HART Pass on o/p-1,
4-20mA, Standard on o/p-2
Response Time ≤50 ms
Accuracy ± 0.1% of FS
Output Load resistance
mA: Load Voltage ≤15V
(e.g. for 4-20mA: 15V/20mA ≤750Ω)
V: Load Current ≤5 mA
(e.g. for 0-5V: 5V/5mA ≥1 KΩ)
For 4 to 20mA (HART Pass): ≤600Ω
TPS Output Transmitter Power Supply 24VDC
Max current Limit: 26mA Electronic
Power Supply
Power Supply 20 to 265VDC/AC, 45Hz-65Hz
Power Consumption ≤5VA
CMRR >100dB
NMRR >70dB
Isolation
Isolation Power to Input / Output, Input to Output,
Output to Output– 1.5KV AC for 1 minute
Environmental
Operating temperature 0 to 55ºC
Temp. Co-efficient ≤100 PPM
Relative humidity 30 to 95% RH (Non-Condensing)
Protection Conformal Coating on PCB
Physical
Mounting Type DIN RAIL (35 mm) Mounting
Dimensions 12.5(W)x99.7(H)x114.7(D) mm(for SOP)
17.5(W)x99.7(H)x114.7(D) mm(for DOP and
HART Pass)
Weight 100 gms Approx. For SOP model
130 gms Approx. For DOP model
Enclosure Material PA66
Terminal
Terminal type and
cable size Screw type, 2.5mm2

Doc.Ref No.:m92E/om/101
Issue No.:12
9000C
S
AFETY AND WARNING
To ensure that the device can be operated safely and
All function can be used, please read these instructions
Carefully before installing the device.
Caution: Never carry out work when the Power is
turned ON, this is dangerous.
Installation and startup must be carried out by
qualified person only. The relevant country-Specific
regulations (e.g., VDE, DIN) must also be observed.
Before startup it is particularly important to ensure:
•
Terminal wiring:
Check that all cables are connected According to
the connection diagram.
•
The Power supply has been connected correctly
•
Protection is provided against electric shock.
•
The device can be switched off outside the power
Supply according to EN 60950 regulations.
(e.g., by the line protection on the primary side)
•
All supply lines should have sufficient fuse
protection and are of correct size.
•
All output cables are of correct size for the
maximum device output current or have separate
fuse protection.
•
Sufficient convection is ensured.
After installation the terminal area must be covered
to provide sufficient protection against unauthorized
Access to live parts.
This is ensured by installing the device in the
control Cabinet or distributor box.
C
ONNECTION
Connection details:
Block Diagram and connection details of SOP
Note: In case of DC supply connect DC (+) to terminal no.
3 and DC (-) to terminal no. 4.
Block Diagram and connection details of DOP
Block Diagram Connection details SOP HART Pass
Suitable for 2 wire transmitter only
Block Diagram and connection details of DOP HART
Pass Suitable for 2 wire transmitter only
Note: In case of DC supply connect DC (+) to terminal
no. 4 and DC (-) to terminal no. 5.

Doc.Ref No.:m92E/om/101
Issue No.:12
9000C
Switch Selection Table For Different
Input /Output ‘M’ Model SOP/DOP:
I
NSTALLATION
Din Rail Mounting:
The unit can be snapped onto all DIN rails (35 mm)
According to EN60715. The device must be mounted
horizontally (Output terminal blocks facing upper
wards).The housing is mounted on the DIN rail by
swiveling it into place.
Removal:
Release the Snap-On catch using a screwdriver and
then detach the module from the bottom edge of the
DIN Rail.
Installation of SOP & DOP
T
ROUBLE
S
HOOTING
Unit Not Turning ON?
If Red LED at the front side is not turned “ON”,
the device is not getting sufficient supply or the
connections are not as per terminal details.
One must take care while dealing with
Power wirings because it may create
electrical shock
Output not matching with expected
value?
Make sure the load on output of device is as per
specification criteria.
Make sure the output Signal is really incorrect
with respect to input signal before attempting any
re-calibration.
Unstable Reading?
Check for loose connections.
First verify that all conventional instrumentation
norms have been followed for wiring.
Make noise away from signal isolator.
Fluctuation in Reading
The reason can be reverse input connections.
Ordering Code
Model Input Type
No of
O/P O/P Type
9000C S
X
X
X
C 4-20mA 1 One 1 4-20mA
2 Two
Model Input Type
No of
O/P O/P Type-1 O/P Type-2
9000C M
X
X
X
X
C 4-20mA 1 One 1 4-20mA 0 None
D 0-20mA 2 Two 2 0-20mA 1 4-20mA
E 1-5VDC 3 1-5VDC 2 0-20mA
F 0-5VDC 4 0-5VDC 3 1-5VDC
G 0-10VDC 5 0-10VDC 4 0-5VDC
5 0-10VDC
Model Input Type
No of
O/P O/P Type
9000C H
X
X
X
C 4-20mA 1 One 1 4-20mA
2 Two
masibus Automation & Instrumentation Pvt. Ltd.
B/30, GIDC Electronics Estate, Sector- 25,
Gandhinagar-382044, Gujarat, India
Ph: 91-079-23287275 / 76 / 77 / 78 / 79
Fax: 91-079-23287281/ 82
Email: [email protected]
Web: www.masibus.com
This manual suits for next models
3
Table of contents
Other Masibus I/O System manuals