manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. ESOair
  6. •
  7. Water Pump
  8. •
  9. ESOair Enviro ET Series Manual

ESOair Enviro ET Series Manual

enviro et series
Oil-free - Linear Diaphragm Pumps
Operating and Maintenance Instructions
ET30, ET40, ET60, ET80, ET100 & ET120
Tel: +44 (0)1932 355277 www.charlesausten.com [email protected]
Royston Road, byfleet, Surrey KT14 7NY, England/UK
Tel: +44 (0) 1932 355277 Fax: +44 (0) 1932 351285
Web: www.charlesausten.com Email: [email protected]
S30 - 176
ESOair
www.kompressoren-drucklufttrockner-filtern.at
[email protected]
Operating and Maintenance Instructions
enviro et series
ET30, ET40, ET60, ET80, ET100 & ET120
These pumps are precision instruments which will give many years of service provided that the
instructions on installation and operation are followed. Whilst the Company may offer advice as
to the model they recommend, it is the sole responsibility of the user to ensure that the pump is
suited to the application for which it is to be used and that the materials offered for the pump and
motor components are suitable for the performance, environmental limitations and chemical
resistance requirements of their application.
Product Features
Two synthetic rubber diaphragms providing continuous air flow at consistent pressure.
Extremely low noise. Low energy consumption and long service life, easy to maintain.
Light-alloy casing, with excellent heat dissipation.
Installation
On receiving the pump, check that it is the model ordered and has not been damaged in transit.
Remove the protective covers from the inlet and outlet pipes where fitted. Ensure that the voltage at
which the pump operates is the same as the rating label.
The pump must is horizontal. Use only to pump air.
One or more aerators can be connected to the pump with piping and T pieces. Choose fittings
and pipe sizes that suit your installation requirements, ensure all pipes are secured with clips. Using
larger bore pipe, and avoiding sharp bends will improve performance.
Use new and sufficiently large aerators with enough discharge capacity, and place them no more
than 3 metres under water. Bends in the air pipe, aerators placed too deep, or old or dirty ones will
all reduce capacity and make the pump work harder and less efficiently. Ensure the pump can
discharge sufficient air at all times, never close off the pump outlet, otherwise the pump will heat
up and may be damaged.
To avoid any backflow of water into the pump, install the pump above water level. If this is not
possible, a non-return, or check valve must be used in the outlet pipe.
To guarantee a long service life, install the pump in dry conditions, free of condensation and dust.
Dust and moisture can seriously shorten the service life of the pump.
Please note that ambient temperatures above 40°C can cause the diaphragms to dry and crack.
Safety Instructions
Never immerse the pump in water.
The electricity supply must be grounded to protect the operator from electric shock.
If the pump falls into the water, unplug from the electricity supply before attempting to retrieve it.
Let qualified technicians check the pump before reconnecting it.
Before installation, and periodically, examine the power cord. If it is damaged it must be replaced
by the supplier or service agent or similarly qualified person in order to avoid a hazard. Never carry
the pump by the power cord. Switch off or disconnect the plug from the power when not in use, and
before installing or removing parts for cleaning.
Periodic maintenance is necessary, as described in these instructions.
Do not place the pump where it might come into contact with liquids, or near flammable or other
dangerous materials or objects.
If the normal pump sound is interrupted, or indicators no longer illuminate or anything abnormal
occurs, immediately disconnect the power and contact the pump supplier.
How it works
When the electromagnetic coils are energized by AC power (AC 100-120 & 200-240V) a magnetic
force is generated. This force then acts to induce poles between the permanent magnets fixed to the
diaphragm rods and the electromagnets. This causes alternate magnetic actions of repulsion and
attraction which move the rod in time with the AC power supply frequency. As the diaphragms move,
air is pumped by the change in volume of the space enclosed by the head and diaphragms and by
the repeated cycles of air intake and compression through the intake and exhaust valves.
Inlet Filter Sponge and Cleaning and Replacement
Any dust or foreign matter entering the air inlet may cause abnormal noise or result in failure of the
pump. Clean or replace the inlet filter sponge regularly, the frequency will depend on the environment.
Disconnect from the power supply before cleaning or replacement work.
With a screwdriver, lever the plastic filter cover off. Remove the filter sponge, clean the air inlet, filter
cover and sponge mounting surface. If the sponge is heavily soiled a new sponge will be needed or
the sponge can be washed in neutral detergent.
Rinse thoroughly, especially if using to aerate fish tanks as fish are extremely sensitive to detergent.
Dry thoroughly out of direct sunlight. Refit sponge and replace cover.
Diaphragm Replacement
Loosen the head screws. Remove the air chamber cover. Loosen the nut. Remove one by one the
diaphragm depressor, electrostatic membrane and diaphragm. Reassemble in reverse order. When
fitting the new diaphragm, ensure that the pip on the diaphragm fits into the notch in the bottom of
the air chamber. If necessary, repeat the repair for the other side of the pump.
Tel: +44 (0)1932 355277 www.charlesausten.com [email protected]
www.kompressoren-drucklufttrockner-filtern.at
[email protected]

This manual suits for next models

6

Popular Water Pump manuals by other brands

POMPE CUCCHI Series WPP Operating and maintenance manual

POMPE CUCCHI

POMPE CUCCHI Series WPP Operating and maintenance manual

Wayne SWS50-8.5FX Operating instructions and parts manual

Wayne

Wayne SWS50-8.5FX Operating instructions and parts manual

GORMAN-RUPP PUMPS 80 Series Installation, operation and maintenance manual

GORMAN-RUPP PUMPS

GORMAN-RUPP PUMPS 80 Series Installation, operation and maintenance manual

Franklin Electric Little Giant BE Series instruction manual

Franklin Electric

Franklin Electric Little Giant BE Series instruction manual

ITT Goulds Pump 2AUW Installation, operation and troubleshooting instructions

ITT

ITT Goulds Pump 2AUW Installation, operation and troubleshooting instructions

Stocker 301 user manual

Stocker

Stocker 301 user manual

SFA SANICUBIC Classic installation instructions

SFA

SFA SANICUBIC Classic installation instructions

Barracuda PUMPS BAAU33 owner's manual

Barracuda PUMPS

Barracuda PUMPS BAAU33 owner's manual

DROPSA 3417000 Series manual

DROPSA

DROPSA 3417000 Series manual

Zoeller 7008 owner's manual

Zoeller

Zoeller 7008 owner's manual

ASC SP010 instructions

ASC

ASC SP010 instructions

Walrus HQ800 Replacing

Walrus

Walrus HQ800 Replacing

Gasboy 61 Special installation instructions

Gasboy

Gasboy 61 Special installation instructions

Neptun ST 800 manual

Neptun

Neptun ST 800 manual

YAMADA DP Series quick guide

YAMADA

YAMADA DP Series quick guide

Bison BPH-125SW2 installation instructions

Bison

Bison BPH-125SW2 installation instructions

Summit 2196 model Installation, operation and maintenance manual

Summit

Summit 2196 model Installation, operation and maintenance manual

Hayward TriStar SP3200 Series owner's guide

Hayward

Hayward TriStar SP3200 Series owner's guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.