Eubank SH Series Installation and operating instructions

REV. 7/7/14 1 3090032.
Installation, Operation and Maintenance
SH SERIES
Ultra Quiet 10+ EER
Wallmount Heat Pumps

REV. 7/7/14 2 3090032.
Your equipment is covered by a LIMITED WARRANTY against
defects in material and workmanship.
This is a vertical, wallmount unit designed for many different
applications in both residential and commercial settings. It is
self-contained and arrives completely assembled, factory-
charged and wired. The unit is 100% run-tested at the factory to
ensure proper operation. Your unit is supplied with high-quality
copper tubing and enhanced aluminum-finned coils for high heat
transfer efficiency and long life. The unit cabinet is constructed
of G-90 galvanized steel. All exterior surfaces are finished with a
baked-on polyester coating. This will provide excellent corrosion
protection in most applications. However, if the unit is installed
in an area with a corrosive atmosphere, such as near an
industrial plant or on the seacoast, additional coating should be
considered to extend the life of the coils and cabinet.
This unit was designed for up to 105ºF of ambient temperature
for the cooling mode; for heating mode, this unit was designed
for up to 78ºF of room temperature and minimum 15ºF ambient
temperature.
INSPECTION AND UNPACKING
A thorough inspection of the shipping container should be made
immediately upon receiving your unit. Look for any punctures or
openings. If it appears as if damage has occurred, it should be
noted on the freight bill before signing. The delivering carrier
should be contacted immediately to inspect damage, and no
installation work should begin until this inspection is completed.
DANGER: BEFORE PERFORMING ANY
WORK ON THIS EQUIPMENT, POWER SUPPLY
MUST BE TURNED OFF AT THE HOUSEHOLD
SERVICE BOX TO AVOID THE POSSIBILITY OF
SHOCK, INJURY, DEATH, OR DAMAGE TO EQUIPMENT.
SAFETY RULES
WARNING: FAILURE TO FOLLOW THESE
RULES AND INSTRUCTIONS COULD CAUSE A
MALFUNCION OR DESTRUCTION OF
EQUIPMENT WHICH COULD RESULT IN
PROPERTY DAMAGE, SERIOUS BODILY INJURY, OR
DEATH.
1. Installation and repair MUST be done by a qualified
person. The equipment should be inspected before use
and at least once annually by a professional service
person.
2. AVOID ELECTRICAL SHOCK! Turn power OFF when
servicing. There may be more than one disconnect
switch to de-energize unit.
3. Close cover(s) before returning breaker(s) to “ON”
position.
4. Please observe good safety practices by wearing
personal protective equipment such as gloves and safety
glasses to avoid injury.
5. Installation MUST conform to local codes. In the absence
of local codes, refer to the National Electrical Code
(NEC), ANS/NFPA No. 70-1993 and recommendations
made by the National Board of Fire Underwriters.
In our continuing effort to improve our product, specifications
may change without notice. If there are any questions, please
see the contact information on the last page of this manual.
In all cases, the equipment MUST be installed in accordance
with the installation instructions described in this manual.
WARNING: IMPROPER INSTALLATION MAY
DAMAGE EQUIPMENT, CAN CREATE A
HAZARD, AND WILL VOID THE WARRANTY
OPERATING INSTRUCTIONS
If heating and cooling functions are controlled by separate
thermostats, turn the furnace thermostat to the “OFF” position
during the cooling season to prevent simultaneous operation of
the heating and cooling systems. Reverse the procedure during
the heating season.
If the same thermostat controls both heating and cooling
functions, set the thermostat to either HEAT or COOL as
desired.
Set the desired temperature on your thermostat and set the fan
switch to “ON” (for continuous air circulation) or to
“AUTOMATIC” (for air circulation only when the heat pump
system is operating).
IMPORTANT: Wait at least three (3) minutes after turning the
air conditioner off before trying to restart. If an attempt is made
to start the compressor before the refrigerant pressures are
equalized, the compressor motor may trip on its overload. An
additional waiting period will be required before restarting.
MAINTENANCE
1. Always install and keep filters clean. Check filters every 2
weeks. Clean or replace if necessary. The factory-installed filter
is located behind the center front access panel.
TO CHANGE SYSTEM FILTER:
A. Turn the power to the unit off at the unit disconnect. The
disconnect is located on the front of the S Series unit
behind a small access door.
B. Remove the front center access door from the unit.
C. Remove and replace the filter with the type and size
indicated in the table below.
D. Replace the access door and turn on the power to the
unit.
NOTE: If your system has a filter grille installed in the return air
opening, the unit filter should have been discarded during
installation.
The filter installed into the return air grille assembly should be
replaced with the same size and type provided with the grille.
If your system is equipped with a fresh air intake, the filter for
the fresh air assembly is accessed through the front center
panel. The filter is a permanent washable type.
UNIT MODEL
QTY.
FILTER SIZE
TYPE
36
1
16 x 30 x 1
(standard) Disposable
36
1
16 x 30 x 2
(optional) Pleated
48, 60
1
20 x 30 x 1
(standard) Disposable
48, 60
1
20 x 30 x 2
(optional) Pleated
WARNING: SERIOUS INJURY MAY RESULT
IF WATER SPRAY IS DIRECTED TOWARD LIVE
ELECTRICAL CONNECTIONS OR POWER
SOURCES.

REV. 7/7/14 3 3090032.
TO CLEAN FRESH AIR INTAKE FILTER:
A. Follow steps A and B at left
“TO CHANGE SYSTEM FILTER”.
B. Gently pull out the filter from the bottom.
C. Wash the filter with water.
D. Reinstall the filter, by sliding it into the
retaining rail.
E. Replace the access door and turn the
power on to the unit.
2. Keep the outdoor coil clean. Wash it down
with a garden hose if necessary.
BE SURE THE UNIT DISCONNECT IS IN THE “OFF”
POSITION AND THAT ALL ELECTRICAL POWER TO THE
UNIT IS TURNED OFF BEFORE CLEANING THE SYSTEM.
Remove any loose grass, leaves, papers, etc., from the area
around the condenser coil. These could reduce the air
supply through the coil and reduce the amount of cooling
capacity.
3. Since the heat pump is located outdoors, it is exposed to all
weather elements. Treat it with a good automobile paste wax
twice a year (in the spring and fall).
Check with your contractor if you have any questions regarding
the maintenance or operation of your unit.
INSTALLATION
A. CODES
The installer SHALL comply with all local, state, and federal
codes and/or regulations pertaining to this type of equipment
and its installation. Such codes and/or regulations should take
precedence over any recommendations contained herein.
Installations SHALL be made in accordance with the National
Electrical Code, local codes, and recommendations made by
the National Board of Fire Underwriters.
B. UNIT SITE SELECTION
1. To eliminate noise from being transmitted into noise
sensitive areas, the unit should NOT be installed on walls
adjoining bedrooms, sleeping quarters, or adjacent to
windows. To further reduce interior space noise levels,
the unit should be installed in a reinforced location.
2. Locating the unit as close as possible to the main duct
system or area to be conditioned, will prevent lengthy
duct runs and unnecessary thermal and air-pressure
losses.
3. The clearance to combustibles is 0" on all sides, and 1/4"
for the first three (3) feet of supply duct.
4. The condenser air inlets (left, right and bottom inlets)
SHALL be located at least 8" away from walls or other
obstructions for unrestricted airflow.
5. The condenser air outlet should be located at least 6’
away from any obstructions to prevent recirculation of
condenser air.
6. Bottom of the unit SHALL be located at least 12" away
from the ground or other obstructions for unrestricted
airflow.
7. Service clearance is 28" from the electrical box access
panel located on the front of the unit and 28" from the
center, upper, and lower front access panels.
8. The wall selected for unit installation MUST be able to or
be made to safely support the weight of the unit.
9. Do NOT locate where heat, lint or exhaust fumes will be
discharged on the unit (as from dryer vents).
C. UNIT PREPARATION
1. The S Series model units have a separate top rain
flashing accompanying the unit. The bottom-mounting
flange for all models is shipped separately and in place.
(Refer to “Section J. Unit Installation” for the
recommended use of the bottom flange.)
2. Electrical entrances are located on the right side and left
side of all S Series units. Refer to “Section H. Electrical
Hook-up” for details.
3. Firmly attach return and supply air collars to the wall and
install foam air gaskets.
4. The supply and return air ducts should be checked to be
sure they:
a. Match the openings on the unit to be installed.
b. Have the same distance between them vertically as
the openings on the unit to be installed.
5. Return and supply grilles must be used when the return
and supply are not ducted.
6. If the factory-installed filter is used on your installation,
access to the filter is made through the center panel on
the front of the unit.
IF A REMOTE FILTER IS USED, SUCH AS A FILTER
GRILLE, THE FACTORY-INSTALLED FILTER MUST BE
REMOVED AND DISCARDED.
D. DUCTWORK
1. Properly-sized duct systems are critical for satisfactory
operation of any air conditioning system. All ductwork
MUST be correctly sized for the design air flow
requirement of the equipment.
2. For increased static pressure operation, connect the
orange and red wires on the Indoor Blower Motor (IBM)
Signal Cable.
3. The recommended operation duct static is to deduct
0.07" W.C. for any size of heater 5 kW to 20 kW on
factory or field-installed heaters.
4. Ductwork routed through wall cavities, as well as any
duct not in conditioned space, MUST be insulated.
Supply ducting routed through exterior walls MUST be
insulated with 1" insulation to the back of the unit.
5. Supply and return air ducts should be flush with the
exterior wall and sized to fit over the unit duct collars in
order to compress the collar air gasket.
6. If supply duct is flashed to the exterior of a building
constructed with combustible material, the flashing
MUST be insulated in order to maintain the required
clearances to combustible materials. Required
clearance is 1/4" for the first three (3) feet of supply
duct.
E. FILTERS
1. Filter grilles with one-inch disposable filters are supplied
standard in each unit. A filter grille with two-inch disposable
filters can also be used and are available as an option.
2. If a filter grille (other than the one accompanying the unit) is
used in the installation, the filter should be properly sized to
allow a maximum velocity of 400 FPM.
WHEN A FILTER GRILLE IS USED, THE FACTORY-
INSTALLED FILTER MUST BE REMOVED.

REV. 7/7/14 4 3090032.
F. ELECTRICAL POWER
The installer MUST check available power to make certain it
matches the unit nameplate rating and that constant voltage can
be maintained to the unit. Unsatisfactory and unsafe
performance could otherwise result. The local power company
should be contacted about questions concerning power supply.
G. BREAKER/DISCONNECT ASSEMBLY
These units are standard equipped from the factory with a unit
disconnect. This is in the form of a circuit breaker (230V
models) or disconnect (460V models). If an optional electric
heat kit is to be installed, follow the instructions included with
the heater assembly.
See Figure 1 for reference.
WARNING: ELECTRICAL EQUIPMENT
SHOULD BE INSTALLED BY A QUALIFIED,
LICENSED ELECTRICIAN. IMPROPER
ELECTRICAL HOOK-UP MAY DAMAGE
EQUIPMENT, CAN CREATE A HAZARD AND WILL VOID
WARRANTY.
H. ELECTRICAL HOOKUP
The line voltage electrical service can be routed through the
right side panel or left side panel. Each area is supplied with two
line voltage knock-outs (1/2" –3/4" and 1" –1 1/4"). Low voltage
wiring can be routed through the right side panel.
NOTE: When routing line voltage through the return air
compartment, conduit MUST be used (even though this is a dry
area) to comply with the NEC code. Refer to the ELECTRICAL
DATA tables for minimum wire size and maximum breaker size.
All wire sizes listed under the dual-feed circuit column are based
on no more than three (3) conductors in the same conduit. If two
circuits or more than three (3) conductors are to be routed in the
same conduit, the ampacity of the wire size listed MUST be
derated. Refer to Article 310 of the NEC code for adjustment
factors. Be sure to install a ground wire of the proper size to the
unit’s equipment ground lug.
I. LOW VOLTAGE WIRING
230 volt, 1- and 3-phase units are equipped with dual-primary
voltage transformers for 208/240 volt operation. These models
are factory wired to the 240 volt tap. For 208 volt operation
connect the factory-installed black wires from the 240 volt tap to
the 208 volt tap. The acceptable voltage range of the tap is as
follows. Tap Voltage Range
240 Volt 253 - 216
208 Volt 220 - 187
Seven (7) conductor thermostat wires should be run from the
thermostat location to the unit. If the unit is equipped with a
powered fresh air option, eight (8) conductor thermostat wires
should be run to the unit. Thermostat wire should be sized as
shown on the table below.
Wire Gauge
Maximum Length
20
45'
18
60'
16
100'
14
160'
12
250'
Refer to wiring diagrams for connection details.
STAGING OF ELECTRIC HEAT
SH series units with electric heat assemblies are wired for two
stage heat in normal operation. The first stage is refrigerant heat
(Y and G terminals are energized and the O terminal is de-
energized). The second stage is auxiliary resistance heat (W is
energized). SH series units are equipped with an emergency
heat lock-out relay. This will disable the compressor when the E
terminal is energized. Do not install a jumper between the W
and E terminals; this would keep the compressor contacts from
being energized and prevent the compressor from operating.
J. UNIT INSTALLATION
S SERIES UNITS ARE FOR USE IN SINGLE-STORY
BUILDINGS ONLY
1. As previously stated, the wall that the unit is to be
installed onto MUST be strong enough to support the unit
under the condition for which it will be used. For example,
a unit to be installed on a building that is intended to be
transported will require more wall strength than a unit
installed at a permanent site. Existing walls may need
additional reinforcement. NEVER RELY ON EXTERIOR
SIDING OR PLYWOOD TO SUPPORT THE UNIT.
Figure 2 on page 5 represents a typical installation of a
single-story stud wall at a permanent site. Since building
materials and techniques vary with regions and intended
use, a building contractor and/or local building code
official MUST be consulted for suitable construction
methods.
2. Locate and attach the lower mounting bracket (J Flange)
and securely fasten to the desired, reinforced location on
the building.
3. Apply a suitable amount of caulk or silicone across the
entire length of the side mounting flanges.
4. Remove the flanges on both ends of the pallet and slide
the S.A.M. approximately 2” off the rear of pallet. Lift
S.A.M. gently into location with fork truck, taking care to
insert the back edge of the unit into the slot on the lower
mounting bracket (J Flange).
5. While allowing a small portion of weight to rest on the
lower bracket (J Flange), push the S.A.M. against the
wall and fasten appropriately.
6. Apply a suitable amount of caulk or silicone across the
entire length of the side mounting flanges.
7. Lift SH unit gently into position with fork truck, taking care
to align the holes on the unit flanges with the holes on the
S.A.M. flanges.
8. Fasten the unit to the S.A.M. using the accompanying
bolts, nuts, and washers. Remove the pallet and attach
top panel to the top of the unit. Apply silicone to the
bottom and back of the rain shield and attach to the wall
at the top of the unit

REV. 7/7/14 5 3090032.
K. CONDENSATE DRAIN
A 3/4” drain hose is located on the bottom side of the unit. The
drain may be extended for condensate removal to comply with
local codes (use fitting size or larger).
L. ELECTRIC HEAT INSTALLATION
Electric heat is an option on S Series units and can be field-
installed on either single- or three-phase models.
Refer to the individual installation instructions for installing heat
kits.
M. OPTIONS
Eubank wallmount air conditioners and heat pumps have the
ability to equip a variety of options:
Electric Heat 5-20kW
Energy Recovery Ventilator
Sound Attenuation Module
Powered Ventilation Damper
Low Ambient Packages
Economizer
Lead Lag Controllers
Option kits must be installed according to the respective
installation manual to ensure safe and reliable operation.
Installation manuals are included with the option kit or can be
found on the Eubank website, www.EubankNCC.com.
N. BASIC SEQUENCE OF OPERATION
COOLING MODE
Low-voltage thermostat terminal R is connected to Y, Y2, O,
and G, at the unit low-voltage terminal board.
The system reversing valve is energized during the cooling
mode. Power is supplied to the reversing valve solenoid
through the low-voltage O terminal. The low-voltage Y
terminal to the control will energize the contactor latch coil
(causing the contactor to energize the compressor). When
Y2 is engaged, the unit switches from the low to high cooling
stage. The low-voltage Y terminal to the control will also
energize the control's timer. During the cooling mode, the
defrost thermostat is open (coil temperature is above 30°F)
and will not allow the time to be accumulated to initiate the
defrost mode. The outdoor fan is wired through the N/C
points of the control’s relay and the N/O points of the
contactor. The fan motor will be energized whenever the
contactor is energized (except during defrost).
REFRIGERANT HEAT MODE
Low-voltage terminal R is connected to Y, Y2, and G, at the
unit low-voltage terminal board.
The system reversing valve is not powered during the
heating mode. With the thermostat system switch turned to
heat. The Y terminal will energize the compressor, outdoor
fan, and the indoor blower. When Y2 is engaged, the unit
switches from the low to high heating stage.

REV. 7/7/14 6 3090032.
DEFROST MODE
To prevent ice build-up on the coil during the heating mode,
as the outdoor coil temperature falls below 30°F ±5°F, an
outdoor defrost thermostat closes. (This thermostat is
located on a coil tube.) When the thermostat closes, the
timer on the defrost control starts accumulating the
compressor run time. After the selected time (30, 60,or 90
minutes) has been accumulated, the controller will start the
defrost cycle regardless of the outside temperature. During
the defrost cycle, the system is switched back into the
cooling mode by the control de-energizing the reversing
valve solenoid. The N/C pole of the control fan relay is
opened, turning off the outdoor fan to allow the outdoor coil
to be warmed (defrosted) faster. The defrost control
energizes the indoor auxiliary heat relays through the E
terminal to temper the indoor supply air. This terminal should
be connected to E (second-stage heat) on the thermostat.
After the defrost thermostat reaches 65°F ±5°F, the defrost
cycle will end. The control will not allow the defrost to
continue longer than 10 minutes.
DEFROST TIME SELECTION
The defrost control has three selectable time intervals: 30,
60 and 90 minutes. The timing is factory set at 60 minutes.
This timing has been determined by testing to provide the
best operating efficiency. In areas where the humidity is
lower than normal, the timer may be set to a higher time (90
minutes). To change the time, move the timer jumper to the
postmarked 30 for 30 minutes, 60 for 60 minutes, or 90 for
90 minutes.
DEFROST TEST POST
The defrost control has test posts to speed up the defrost
time setting by a factor of 256.
If you want to initiate a defrost without waiting for the time to
accumulate, you can jumper the two test pins (marked test).
If the coil temperature is above 30°F you will need to jumper
the DFT (defrost thermostat) terminals to simulate a closed
thermostat. The defrost cycle should occur in 7 seconds for
a 30-minute setting, 14 seconds for a 60-minute setting, and
17 seconds for an 90-minute setting. If the jumper is
removed immediately when the defrost cycle starts, the cycle
will end if the defrost thermostat is opened (coil above 65°F).
If the test pins remain jumped, and the defrost thermostat is
closed, the defrost will end in 2.3 seconds, which is the 10-
minute default.
DURING THE ABOVE TEST, DO NOT CONTACT OR
SHORT ANY OTHER PIN. THIS MAY DAMAGE THE
CONTROL.
O. HIGH-PRESSURE LOCK OUT
SH Series units are equipped with a high-pressure switch.
This switch is wired through a lockout relay to lock out the
system if the high side pressure exceeds 650 psi. The high
side pressure MUST be below 450 psi before the system
can be reset.
FIELD CHARGING
Compared to a cooling-only unit, a heat pump is difficult to
field charge correctly without the use of charging scales. It is
recommended the charge be weighed in with an accurate
charging scale. The correct charge weight can be found on
the unit name plate.

REV. 7/7/14 7 3090032.
EXPLODED PARTS DRAWING - 36/48/60

REV. 7/7/14 8 3090032.
PART NUMBER
DESCRIPTION
TH36S
TH36T
TH36D
TH48S
TH48T
TH48D
TH60S
TH60T
TH60D
1
3020017
COMP ZPS30K5EPFV130
X
1
3020018
COMP ZPS30K5ETF5130
X
1
3020019
COMP ZPS30K5ETFD130
X
1
3020020
COMP ZPS40K5EPFV130
X
1
3020021
COMP ZPS40K5ETF5130
X
1
3020022
COMP ZPS40K5ETFD130
X
1
3020023
COMP ZPS51K5EPFV130
X
1
3020024
COMP ZPS51K5ETF5130
X
1
3020025
COMP ZPS51K5ETFD130
X
2
COND-H436
OUTDOOR COIL
X
X
X
2
3070001
OUTDOOR COIL
X
X
X
X
X
X
3
550505
DISTRIBUTOR 3 CIRCUIT-OD COIL
X
X
X
3
550517
DISTRIBUTOR 6 CIRCUIT-OD COIL
X
X
X
X
X
X
4
T36-EVAP
EVAP COIL
X
X
X
4
3070002
EVAP COIL
X
X
X
X
X
X
5
550517
DISTRIBUTOR 6 CIRCUIT-EVAP
X
X
X
5
550521
DISTIBUTOR 9 CIRCUIT-EVAP
X
X
X
X
X
X
6
TXV410-E3
TXV VALVE
X
X
X
6
TXV410-E5-HP
TXV VALVE
X
X
X
X
X
X
6A
550792
REVERSING VALVE
7
61508
BI-FLOW FILTER DRIER
X
X
X
X
X
X
X
X
X
8
T36-0008
FAN SHROUD HV36
X
X
X
8
T60-0008
FAN SHROUD HV48-60
X
X
X
X
X
X
9
421508
MOTOR MOUNT OD FAN
X
X
X
9
259109
MOTOR MOUNT OD FAN
X
X
X
X
X
X
10
025015/3010014
MOTOR OD 230V 825 RPM
X
X
10
025018
MOTOR OD 460V 1/4 HP 825 RPM
X
10
3010016
MOTOR OD 230V HE755 1/2 HP
X
X
X
X
10
3010017
MOTOR OD 460V HE575 1/2 HP
X
X
11
3020026
OD SWEPT BLADE 22" S*36
X
X
X
11
3020014
OD SWEPT BLADE 22" S*48-60
X
X
X
X
X
X
12
359104
1/3 HP ECM BLOWER MTR 230V/277V
X
X
X
12A
3010020
1/3 HP ECM MODULE
X
X
X
12
359105
1/2 HP ECM BLOWER MTR 230V/277V
X
X
X
12A
3010021
1/2 HP ECM MODULE
X
X
X
12
3010027
3/4 HP EON BLOWER MTR 230V/277V
X
X
X
12A
3010028
3/4 HP ECM Module
X
X
X
12B
T36-0131
ECM MODULE BRACKET
X
X
X
X
X
X
X
X
X
13
050001
R.BLOWER WHEEL 98-7T CW
X
X
X
13A
050000
L.BLOWER WHEEL 98-7T CCW
X
X
X
13
3020002
R.BLOWER WHEEL 100-9T CW
X
X
X
X
X
X
13A
3020003
L.BLOWER WHEEL 100-9T CCW
X
X
X
X
X
X
14
421506
BLWR MTR BRKT
X
X
X
X
X
X
X
X
X
14A
454280
BLWR MTR BRKT GROMMET TUBE
X
X
X
X
X
X
X
X
X
14B
454282
BLWR MTR BRKT WASHER TUBE
X
X
X
X
X
X
X
X
X
14C
454284
BLWR MTR BRKT MOUNTING SLEEVE
X
X
X
X
X
X
X
X
X
14D
454236
BLWR MTR BRKT WASHER
X
X
X
X
X
X
X
X
X
14E
750058
BLWR MTR BRKT BOLT(1/4-20)
X
X
X
X
X
X
X
X
X
15
T36-0000B
ASSEMBLY LEFT SIDE PANEL HV36
X
X
X
15A
T36-0135
OD.GRILL INLET LEFT SIDE HV36
X
X
X
15
T60-0008
ASSEMBLY LEFT SIDE PANEL HV48-60
X
X
X
X
X
X
15A
T60-0091
OD.GRILL INLET LEFT SIDE HV48-60
X
X
X
X
X
X
15B
T36-0126
ERV INTAKE AIR PANEL
X
X
X
X
X
X
X
X
X
16
T36-0001B
ASSEMBLY RIGHT SIDE PANEL HV36
X
X
X
16A
T36-0134
OD.GRILLINLET RIGHT SIDE HV36
X
X
X
16
T60-0001B
ASSEMBLY RIGHT SIDE PANEL HV48-60
X
X
X
X
X
X
16A
T60-0081
OD.GRILL INLET RIGHT SIDE HV48-60
X
X
X
X
X
X
17
T36-0007B
TOP HV36
X
X
X
17
T60-0007B
TOP HV48-60
X
X
X
X
X
X
18
T36-0012
ASSEMBLY REAR PANEL HV-36
X
X
X
18
T60-0012
ASSEMBLY REAR PANEL HV48-60
X
X
X
X
X
X
19
T36-0003
ASSEMBLY DIVIDER DECK HV-36
X
X
X
19
T60-0003
ASSEMBLY DIVIDER DECK HV48-60
X
X
X
X
X
X
20
T36-0005
ASSEMBLY BLOWER DECK HV36
X
X
X
20
T60-0005
ASSEMBLY BLOWER DECK HV48-60
X
X
X
X
X
X
21
2022-0006P
ASSEMBLY DRAIN PAN HV36
X
X
X
21
2023-0006P
ASSEMBLY DRAIN PAN HV48-60
X
X
X
X
X
X
22
T36-0098
BASE PAN ASSEMBLY HV36
X
X
X
22
T60-0098
BASE PAN ASSEMBLY HV48-60
X
X
X
X
X
X
23
T36-0018
BLOWER FLANGE HV36
X
X
X
23
T60-0018
BLOWER FLANGE HV60
X
X
X
X
X
X
24
T36-0010B
UPPER FRONT PANEL HV36
X
X
X
24
T60-0010B
UPPER FRONT PANEL HV48-60
X
X
X
X
X
X
24A
2022-5062
DISCONNECT ACCESS DOOR HV36-60
X
X
X
X
X
X
X
X
X
24B
70518
DISCONNECT ACCESS DOOR LATCH HV36-60
X
X
X
X
X
X
X
X
X
25
T36-0011B
MIDDLE FRONT PANEL (no fresh air) HV36
X
X
X
25
T36-0011EB
MIDDLE FRONT PANEL (economizer f/a) HV36
X
X
X
25
T36-0011FB
MIDDLE FRONT PANEL (barometric f/a) HV36
X
X
X
25
T60-0011B
MIDDLE FRONT PANEL (no fresh air) HV48-60
X
X
X
X
X
X
25
T60-0011EB
MIDDLE FRONT PNL (economizer f/a) HV48-60
X
X
X
X
X
X
25
T60-0011FB
MIDDLE FRONT PNL (barometric f/a) HV48-60
X
X
X
X
X
X
26
T36-0017B
COMPRESSOR ACCESS DOOR HV36
X
X
X

REV. 7/7/14 9 3090032.
PART NUMBER
DESCRIPTION
TH36S
TH36T
TH36D
TH48S
TH48T
TH48D
TH60S
TH60T
TH60D
26
T60-0017B
COMPRESSOR ACCESS DOOR HV48-60
X
X
X
X
X
X
27
2022-5015
LOWER CONDENSER GRILL HV36
X
X
X
27
2023-5015
LOWER CONDENSER GRILL HV48-60
X
X
X
X
X
X
28
659930
AIR FILTER DISPOSABLE 16x30x1 HV36
X
X
X
28
3090005
AIR FILTER PLEATED 16x30x2 HV36
X
X
X
28
659926
AIR FILTER DISPOSABLE 20x30x1 HV48-60
X
X
X
X
X
X
28
659924
AIR FILTER PLEATED 20x30x2 HV48-60
X
X
X
X
X
X
29
T36-0094
EVAP COIL DECK/FILTER RACK HV36
X
X
X
29
T60-0094
EVAP COIL DECK/FILTER RACK HV48-60
X
X
X
X
X
X
29A
T36-0132
2 INCH FILTER BRKT HV36
X
X
X
29A
T60-0132
2 INCH FILTER BRKT HV48-60
X
X
X
X
X
X
29B
T36-0133
1 INCH FILTER BRKT HV36
X
X
X
29B
T60-0131
1 INCH FILTER BRKT HV48-60
X
X
X
X
X
X
ETA1-05-HP
FIELD INSTALL HEAT KIT 5KW 1 PHASE 230V
X
X
X
30
3010002
HEATER 5KW 1PH 230V
X
X
X
ETA1-10-HP
FIELD INSTALL HEAT KIT 10KW 1 PHASE 230V
X
X
X
30
3010003
HEATER 10KW 1PH 230V
X
X
X
ETA3-06
FIELD INSTALL HEAT KIT 6KW 3 PHASE 230V
X
X
X
30
3010006
HEATER 6KW 3PH 230V
X
X
X
ETA3-09
FIELD INSTALL HEAT KIT 09 KW 3 PHASE 230V
X
X
X
30
3010007
HEATER 09 KW 3PH 230V
X
X
X
ETA4-06
FIELD INSTALL HEAT KIT 6KW 3 PHASE 460V
X
X
X
30
3010010
HEATER 6KW 3P 460V
X
X
X
ETA4-09
FIELD INSTALL HEAT KIT 09KW 3 PHASE 460V
X
X
X
30
3010011
HEATER 09KW 3P 460V
X
X
X
454332
SWITCH LIMIT 245F ONE SHOT
X
X
X
X
X
X
X
X
X
454323
SWITCH LIMIT 160-30F 240
X
X
X
X
X
X
X
X
X
31
T36-0009
CONTROL PANEL HV36
X
X
X
31A
T36-0093
TERMINAL BOARD PANEL HV36
X
X
X
31
T60-0009
CONTROL PANEL HV48-60
X
X
X
X
X
X
31A
T60-0093
TERMINAL BOARD PANEL HV48-60
X
X
X
X
X
32
T36-0036
CONTROL PANEL COVER HV36
X
X
X
32
T60-0036
CONTROL PANEL COVER HV48-60
X
X
X
X
X
X
33
T36-0015
HEAT SHIELD HV36
X
X
X
33
T60-0015
HEAT SHIELD HV48-60
X
X
X
X
X
X
453150
COMP CONTACTOR 1 POLE 1P 25 AMP
X
X
453770
COMP CONTACTOR 2 POLE 1P 40 AMP
X
453772
COMP CONTACTOR 3 POLE 3P 25 AMP
X
X
X
X
X
X
452842
PHASE MONITOR
X
X
X
X
X
X
450502
COMP CAPACITOR 7.5/80X370V
X
450370
COMP CAPACITOR 7.5/45X370V
X
450378/450377
COMP CAPACITOR 10/70X370V -/.-7.5/10X370V
X
450205
COND. MTR CAPACITOR 7.5X370V
X
X
X
X
X
X
451000
TERMINAL BLOCK
X
X
X
X
X
X
X
X
X
452752
TRANSFORMER 208/240V 50VA 24V
X
X
X
X
X
X
452756
TRANSFORMER 480V 50VA 24V
X
X
X
452200
FAN RELAY
X
X
X
X
X
X
0821N-0084A
FAN RELAY
X
X
X
42004
CIRCUIT BREAKER 2 POLE 1P 60 AMP 240V
X
X
X
453807
CIRCUIT BREAKER 3 POLE 3P 60 AMP
X
X
X
451955
DISCONNECT KIT 460V
X
X
X
451956
DISCONNECT KNOB 460V
X
X
X
0415-0028
LOW VOLTAGE TERMINAL BOARD
X
X
X
X
X
X
X
X
X
454388
LOW PRESSURE SWITCH
X
X
X
X
X
X
X
X
X
451988
HIGH PRESSURE SWITCH
X
X
X
X
X
X
X
X
X
452195
LOCKOUT RELAY
X
X
X
X
X
X
X
X
X
451995
DEFROST BOARD
X
X
X
X
X
X
X
X
X
0445-0007
DEFROST TERMINATION SENSOR
X
X
X
X
X
X
X
X
X
451049
JUMPER BAR ASSEMBLY
OPTIONAL
OPTIONAL
OPTIONAL
OPTIONAL
OPTIONAL
OPTIONAL
451840
OPTION BOARD
OPTIONAL
OPTIONAL
OPTIONAL
OPTIONAL
OPTIONAL
OPTIONAL
OPTIONAL
OPTIONAL
OPTIONAL
451992
FAN CYCLE SWITCH
OPTIONAL
OPTIONAL
OPTIONAL
OPTIONAL
OPTIONAL
OPTIONAL
OPTIONAL
OPTIONAL
OPTIONAL
1082628
CRANKCASE HEATER
OPTIONAL
OPTIONAL
OPTIONAL
1064905
CRANKCASE HEATER
OPTIONAL
OPTIONAL
OPTIONAL
OPTIONAL
OPTIONAL
OPTIONAL
C-OPT-SH2-410
LOW AMBIENT KIT
OPTIONAL
OPTIONAL
OPTIONAL
C-OPT-SH-410
LOW AMBIENT KIT
OPTIONAL
OPTIONAL
OPTIONAL
OPTIONAL
OPTIONAL
OPTIONAL
3080002
LOW SOUND SUPPLY GRILL
X
X
X
3080004
LOW SOUND SUPPLY GRILL
X
X
X
X
X
X
3080001
LOW SOUND RETURN FILTER GRILL
X
X
X
3080003
LOW SOUND RETURN FILTER GRILL
X
X
X
X
X
X
T60-0140
LARGE SUPPLY GRILLE FRAME
X
X
X
X
X
X
T36-0140
SMALL SUPPLY GRILLE FRAME
X
X
X

REV. 7/7/14 10 3090032.
SINGLE FIELD CIRCUIT
DUAL FIELD CIRCUIT
Model No. &
Electric
Heater Kw [1]
Volt /
Phase
No. of
Field
Power
Ckts
MINIMUM
CIRCUIT
AMPACICY
MAX OVER
CURRENT
PROTECTION [2]
FIELD POWER
WIRE SIZE
[3],[4],[5]
GROUND
WIRE SIZE
MIM WIRE
AMPACITY
MAX OVER
CURRENT
PROTECTION [2]
FIELD POWER
WIRE SIZE
[3],[4],[5]
GROUND
WIRE SIZE
CKT1
CKT2
CKT1
CKT2
CKT1
CKT2
CKT1
CKT2
SH36S00
208-
230/1
1
22
30
12
12
5
1
48
60
8
10
10
1 OR 2
74
90
4
8
22
52
30
60
12
6
12
10
SH36T00
208-
230/3
1
17
30
14
14
6
1
35
60
8
10
9
1
44
60
8
10
SH36D00
460/3
1
9
15
14
14
6
1
18
30
14
14
9
1
23
30
12
12
SH48S00
208-
230/1
1
33
60
10
10
5
1
59
60
6
10
10
1 OR 2
85
90
4
8
33
52
60
60
10
6
10
10
SH48T00
208-
230/3
1
24
30
12
12
6
1
42
60
8
10
9
1
51
60
6
10
SH48D00
460/3
1
12
15
14
14
6
1
21
30
12
12
9
1
26
30
10
10
SH60S00
208-
230/1
1
40
60
8
10
5
1 OR 2
66
90
4
8
40
26
60
30
8
10
10
10
10
1 OR 2
92
100
3
8
40
52
60
60
8
6
10
10
SH60T00
208-
230/3
1
27
30
10
10
6
1
45
60
8
10
9
1
54
60
6
10
SH60D00
460/3
1
13
15
14
14
6
1
22
30
12
12
9
1
27
30
10
10
[1] Heater data were based on 240V or 480V AC respectively.
[2] Maximum recommended size for "Time Delay" fuse or HACR circuit breaker.
[3] Power supply wire size and ground wire sizez were based on AWG 75C rise, NEC Article 310 and Table 310.15(B)(16).
[4] For single power conductor, sized per NEC Table 310.15(B)(17).
[5] Power supply wire 75C rated COPPER CONDUCTOR ONLY.
SH SERIES HEAT PUMP ELECTRICAL DATA

REV. 7/7/14 11 3090032.

REV. 7/7/14 12 3090032.

REV. 7/7/14 13 3090032.

REV. 7/7/14 14 3090032.
The information in this manual supersedes and replaces the previous instruction/operation manual 3090015 with regards to S Series
wallmount products. Illustrations, part numbers and others cover the general appearance of the units at the time of publication and the
manufacturer reserves the right to make changes in design and construction at any time without notice.
For replacement parts contact:
National Coil Company
1998 FM 2011
Longview, TX 75603
Phone: 903-643-2261
Fax: 903-643-2222
TV 36 S 10 - F B 00
MODEL SERIES OPTION CODE
TV = AIR CONDITIONER 10 EER SERIES (UP TO 5 CHARACTERS)
TH = HEAT PUMP 10 EER SERIES
TR = REFRIGERATION SERIES CABINET COLOR
SV = AIR CONDITIONER LOW SOUND SERIES B = MESA TAN (Std)
SH = HEAT PUMP LOW SOUND SERIES W = WHITE
NOMINAL COOLING CAPACI TY FRESH AIR
36 = 36,000 BTU/H NOMINAL F = BAROMETRIC DAMPER (Std)
M = MOTORIZED DAMPER
ELECTRI CAL SERVICE E = ECONOMIZER
S = 208-230/1/60 B = SOLID DOOR
T = 208-230/3/60 P = PRV
D = 460/3/60 V = ERV
ELECTRI C STRIP HEATER
10 = 10 kW
UNIT NOMENCLATURE
Table of contents
Other Eubank Heat Pump manuals
Popular Heat Pump manuals by other brands

WATERKOTTE
WATERKOTTE EcoTouch DS 5050T Planning and installation

Robur
Robur GAHP-AR Installation, use and maintenance manual

Gree
Gree GRS-CQ6.0Pd/Na-K Service manual

FHP
FHP HR000 installation manual

Airxcel
Airxcel Marvair Classic HVPA24HP Maintenance service manual

Heatcraft Refrigeration Products
Heatcraft Refrigeration Products Condensing Units H-IM-CU Installating and operation manual