CAPACITIES OF EXPANSION VESSELS
Safety Valve Setting @ 3 3 3
Vessel charge and
Initial System Pressure 0.5 1 1.5
(BAR GAUGE)
LITRES LITRES LITRES LITRES
52.1 2.7 3.9
50 4.2 5.4 7.8
75 6.3 8.2 11.7
100 8.3 10.9 15.6
125 10.4 13.6 19.5
150 12.5 16.3 23.4
175 14.6 19.1 27.3
200 16.7 21.8 31.2
225 18.7 24.5 35.1
250 20.8 27.2 39.0
275 22.9 30.0 42.9
300 25.0 32.7 46.8
325 27.0 35.7 50.7
350 29.1 38.1 54.6
375 31.2 40.9 58.5
400 33.3 43.6 62.4
425 35.4 46.3 66.3
450 37.5 49.0 70.2
500 41.6 54.5 78.0
Multiplying
Factors for
other system
Volumes 0.0833 0.109 0.156
11
EXPANSION VESSEL SIZING
Bs7074:Part1:1989 gives full details of accurate
method of calculating the required expansion
vessel capacity, assuming that full and accurate
design information is available, particularly total
system water content.
However, in practice, it is often not possible to
calculate the system water contents with any
certainty, and therefore estimates must be made.
The following volume approximations can be used
to give a reasonable estimate of total system
volume.
50/70 SYSTEM 20 Litres
KW RATING 14.65-20.5
SMALL BORE PIPEWORK 1 Litre Per Kw of
System Output
STEEL PANEL RADIATORS 8 Litres Per Kw of
System Output
LOW WATER CAPACITY 2 Litres Pre Kw of
RADIATORS MODERN TYPE System Output
HOT WATER CYLINDER 2 Litres
Note: As an approximation, BS7074: Part 1
suggests that figure of 12 litres/kw of boiler output
could be used to estimate total system water
content-this would be generous for most systems.
EXPANSION VESSEL SIZING
Having determined the total system water
content, expansion vessel sizing can be
considered. Taking into account the other system
design factors.
Full details of expansion vessel sizing and Altecnic models available are given in the expansion
vessel data sheet.
However, Altecnic expansion vessels are supplied pre-charged at 1bar (suitable for system static
heads up to 15 metres) and the safety valve normally pre-set at 3 bar (British Specification).
For standard conditions therefore, the following table can be used to select the required
expansion vessel volume.
NB: Please note the above information (EXPANSION VESSEL SIZING) is only a guide therefore we do
not accept responsibility for sizing of systems and this does not over rule British Standards always
refer back to BS7074: Part 1 if in doubt.
WARNING SEALED SYSTEM
This boiler operates on a sealed system up to a maximum pressure of 3 bar. It is the responsibility
of the installer to ensure all pipework and fittings are suitable for use under these circumstances.
This boiler is supplied with a 12 litre expansion vessel. It is the installers responsibility to ensure
adequate provision is made for expansion within the system and to install extra capacity if
required.
Damage to components caused by over expansion may not be covered by warranty. Unsuitable
pipework and fittings and factors such as sediment or residue left in the system, may cause
damage to your boiler and its components this will not be covered by warranty.
FILLING THE SYSTEM
Prior to filling, the system must be thoroughly flushed using a cleaning agent. The system must then
be vented of all air and recharged to maximum of 1.5 bar.