Exitronix RMW Series User manual

1. Trace and cut an 8 1/8” x 10 3/4” rectangular hole in the ceiling.
2. Knockout the appropriate mounting holes and wire pass-through hole.
3. Insert back box inside rectangular cutout and secure in place using cables/chains and the appropriate hardware
for the application. (supplied by others) (Fig.1).
4. All electrical connections should be made inside the junction box (supplied by others).
CAUTION! Failure to cap unused wires may result in a shock hazard or unsafe condition as well as equipment
failure.
RMW Series
INSTALLATION INSTRUCTIONS
800.533.3948 • www.barronltg.com
10070210 Rev 2 - 04/19 1
120VAC
White - Common
Black - 120V
Green - Ground
277VAC
White - Common
Orange - 277V
Green - Ground
IMPORTANT SAFEGUARDS
READ AND FOLLOW ALL SAFETY INSTRUCTIONS.
When using electrical equipment, basic safety precautions should always be followed including the following:
• DISCONNECT AC POWER SUPPLY BEFORE SERVICING.
• Installation and servicing of this equipment should be performed by qualified service personnel only.
• Ensure that the electrical wiring conforms to the National Electrical Code NEC® and local regulations if applicable.
• Do not mount near gas or electrical heaters.
• Do not use outdoors.
• Equipment should be mounted in locations and at heights where it will not be readily subjected to tampering by
unauthorized personnel.
• The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
• Any modification or use of non-original components will void the warranty and product liability.
• Do not use this equipment for other than intended use.
• Allow battery to charge for 24 hours before first use.
SAVE THESE INSTRUCTIONS!
Fig. 1
Cable / Chains
Cable/Chains

5. Connect the red (+) positive wire to the (+) positive terminal on the battery. Connect the black (-) negative wire to the
(-) negative terminal on battery only after continuous AC power can be provided to the unit.
6. Replace the cover by inserting the two torsion springs into
the space provided inside the back box. (Fig. 2)
7. To set the lamp heads for best lighting distribution;
loosen the set screw and manually rotate or twist the heads
to the desired position, then retighten the set screw to
lock into place.
8. Energize un-switched AC power to the unit.
9. Verify charge indicator LED is illuminated.
10. Press the test button and verify the lamps turn on.
Note: If lamps do not illuminate, allow the unit to charge for
30 minutes.
11. Leave AC connected for 24 hours prior to performing any full-length test.
12. Refer to the Self-test/Self-diagnostics section for units equipped with G2.
SELF-TEST/SELF-DIAGNOSTICS - Operation
Setup & Standard Operation
1. To Reset/Initiate: disconnect batteries and turn off AC power supply for 10 seconds. Reconnect batteries and turn on
AC power. The system will automatically test unit operation. It will also reset and start all counters for automated
operations.
2. When AC fails, the DC lamps will turn on with a 3-second delay.
3. After AC resumes, the DC lamps will turn off and the CHARGE LED will turn on.
4. A steady green CHARGE indicator indicates a high charge rate. After the battery has reached a full charge, the
indicator LED will turn off. Under normal operation, the charge indicator will turn on and off intermittently while in
standby mode (normal AC present).
5. A flashing green DIAGNOSTIC LED indicates there has been a power failure/loss of AC in the past 48 hours. The
90 minutes Manual Test will not be allowed during this period. The 90 minutes Auto-Test will be initiated after 48
hours and then the indicator will turn back to steady green.
TROUBLESHOOTING - RESET CHARGER BOARD
1. To clear any unit failures or problems from being indicated by the DIAGNOSTIC LED, disconnect batteries and turn
off the AC power supply for 10 seconds to RESET the charger board. Reconnect battery and resume AC.
Torsion Spring
Cover
Set Screws
INSTALLATION INSTRUCTIONS
800.533.3948 • www.barronltg.com
10070210 Rev 2 - 04/19 2
RMW Series
Fig. 2

INSTALLATION INSTRUCTIONS
800.533.3948 • www.barronltg.com
10070210 Rev 2 - 04/19 3
RMW Series
Manual Testing
Multiple durations can be selected as follows:
Instant Test: Press and hold Test Switch for more than 3 seconds
5 Minutes Test: Press Test Switch 2 times within 3 seconds.
90 Minutes Test: Press Test Switch 3 times within 3 seconds.
Momentary Test: Useful during installation, connect battery only (without AC connected), press and
hold Test Switch.
To CANCEL
any Manual Test: Press and hold Test Switch for 5 seconds.
Battery or Charger Diagnostics
Charger:
During normal operation, the onboard microcontroller constantly monitors the charger performance. Should the charger
output vary from design parameter values, the DIAGNOSTIC LED will indicate a flashing red condition.
Transfer:
A failure of the unit to transfer to battery power during a power outage will cause the DIAGNOSTIC LED to flash red.
Battery:
Disconnection of the batteries from the charger will cause the DIAGNOSTIC LED to flash red. If the battery voltage
drops too low or the unit fails to provide battery power for the required duration during a manual/automated test, the
DIAGNOSTIC LED will display steady red.
To prevent battery damage: Do not connect the battery until constant AC power can be supplied to the unit.
Self-test/Self-diagnostics (G2)
Automated Testing:
The Auto-Test scheduling counter will start when both AC and battery are first applied. When automatic testing is in
progress the DIAGNOSTIC LED will flash yellow. A steady green DIAGNOSTIC LED indicates normal operation.
Automated Diagnostic Routine
The Auto-Test automatically initiates a five-minute discharge/diagnostic test every month with two 90-minute discharge/
diagnostic tests every 6 months.
Twenty-four hours following the first 6-month test, the unit will retest again to ensure that the charger has completely
recharged the battery. The lamps will be activated during these tests. The tests exercise the battery to optimize its
capacity and analyze the unit’s emergency operation. Any malfunction of the transfer circuit, batteries or emergency
lamps will cause the multi-color DIAGNOSTIC LED on the unit to indicate the fault. The
DIAGNOSTIC indications will remain latched (stay on) in the system until corrected or reset.
Diagnostics Display
The Auto-test/Self-diagnostics provides a visual indication of unit status via a multi-colored
LED. The LED may indicate just one or any combination of the various conditions as follows:
Steady Green: Normal Operation
Flashing Green: AC Interruption in Last 48 Hours
Steady Yellow: Lamp Circuit Malfunction
Flashing Yellow: Auto-Test or Manual Test in Progress
Steady Red: Battery Failed Testing
Flashing Red: Battery Disconnected or Charger Malfunction
DIAGNOSTIC
CHARGE
TEST
Battery Unit LEDs
and Test Switch
Configuration
Table of contents
Other Exitronix Light Fixture manuals
Popular Light Fixture manuals by other brands

LEGRAND
LEGRAND Finelite E1 installation instructions

Home Accents Holiday
Home Accents Holiday Adorable Dogs LED Husky Assembly instructions

Omron
Omron F3SJ-A P Series user manual

Chauvet
Chauvet BLACKLIGHT F-40 user guide

Renkforce
Renkforce Rubi operating instructions

Lightolier
Lightolier Calculite CS7142 specification