8Purevision LPV Freestanding Issue 01 02/21
Where the chimney is believed to have previously served an open fire installation, it is possible that
the higher flue gas temperature from the stove may loosen deposits that were previously firmly
adhered, with the consequent risk of flue blockage. It is therefore recommended that the chimney
be swept a second time within a month of regular use after installation.
If you have any doubts about the suitability of your chimney, consult your local dealer/stockist or
chimney specialist. If there is no existing chimney then either a solid fuel compatible prefabricated
block chimney or a twin-walled insulated stainless steel flue to BS 4543 can be used. These chimneys
must be fitted in accordance with the manufacturer’s instructions and Building Regulations.
5.2. Ventilation
Document J of the Building Regulations states that purpose provided ventilation is not required in
the majority of houses in England and Wales unless the appliance nominal rated output is greater
than 5kW. Over 5kW 5.5 cm2of ventilation (550mm2) is required for every kW output above 5. For
example 6.5 kW requires 8.25 cm2and 8 kW needs 16.5cm2. In any case, if difficulty in starting the
fire or any excessive fuming is experienced, ventilation must be put in place as required to eliminate
these flue problems. If a flue draught stabiliser is fitted then extra ventilation is required. See
Document J of the Building Regulations for detailed guidance especially in new build properties. A
specifically designed direct outside air connection may be used with these stoves to provide 100% of
the required combustion air to appropriate levels of ventilation (significantly in excess of the above
requirements) directly to the stove and chimney as follows. NOTE: in order to register the
installation with HETAS as of early 2016 certain extra evaluation and checking is required if using an
outside air connection. If the direct air kit is used and no ADJ vent is installed then a direct
registration with Building Control may also be possible.
5.3. Direct Outside Air Connection
Purevision stoves are supplied with the facility of using a dedicated 100mm diameter direct
connection duct through a suitable route to the outside air. This will supply 100% of the air required
for combustion and operation of the flue. It can be connected to the rear or underside of the stove
and should be fitted at the time of stove installation. Only the approved kit for Purevision stoves
should be used. This is designed to supply all the necessary air for safe combustion and operation of
the stove –providing there is no depressurisation of the property by mechanical or other types of
ventilation, the flue, chimney and ventilation duct are working correctly, and properly maintained
clear of obstructions or leaks etc. The kit supplies all the primary, secondary and tertiary air to the
stove and also provides room ventilation in excess of the Document J Building Regulations during re-
fuelling via the air connection unit under the stove and so subject to no depressurisation (as above)
may be used where mechanical ventilation and heat recovery (MVHR) units are used. Some
additional instructions for installation are provided with the dedicated kit supplied. NOTE: in order
to register the installation with HETAS as of 2016 certain extra evaluation and checking is required if
using an outside air connection. If the direct air kit is used and no ADJ vent is installed then a direct
registration with Building Control may also be possible.
5.4. Flue Draught
A flue draught at the flue collar of minimum 2.2mm to a maximum 3.5mm water gauge (22 to 35
Pascals) is required for satisfactory appliance performance. This relates to 12-25 Pascals at the
tapping on EN13240/13229 test rigs. The flue draught should be checked under fire at high output
and, if it exceeds the recommended maximum, a draught stabiliser should be fitted so that the rate
of burning can be controlled to prevent over-firing.
5.5. Connection to the Chimney
This appliance is not suitable for use in a shared flue.