Forney AMP RACK User manual

www.forneycorp.com
BURNERS IGNITERS DAMPERS CONTROLS
AMP RACK USER MANUAL
Publication 372000-96 Rev H

This manual contains information for the AMP Rack from Forney Corporation, 16479 Dallas Parkway,
Suite 600, Addison, Texas. www.forneycorp.com
All personnel should become thoroughly familiar with the contents of this manual before attempting to use
the Forney AMP Rack. Because it is virtually impossible to cover every situation that might occur during
operation and maintenance of the equipment described in this publication, personnel are expected to use
good engineering judgment when confronted with situations that are not specically mentioned herein.
PROPRIETARY NOTICE
The contents of this publication are proprietary data of Forney Corporation. Forney reserves all proprietary
rights to this document, including all design, manufacturing, reproduction, use, and sales rights thereto,
except to the extent said rights are expressly granted to others.
AMP Rack User Manual
372000-96 Rev G
i
INTRODUCTION
REVISIONS
REVISIONS DATE COMMENTS
A6/2005 Initial Release
B7/2007
C 11/2009 Update spares part numbers
D 11/2011 Update reference to amplier manuals
E 01/2015 Add RM-IDD9000
F 01/2017 Remove DC power options / update RMA section
G 01/2017 Add Power Consumption
H
General Rewrite

PM IDD9000 Flame Amplier
372001-02 Rev Kv
TABLE
OF
CONTENTS

Section 1 General Information
1.1 Equipment Description
1.2 Power Requirements
1.2.1 Input Power
1.2.2 Output Power
1.2.3 Power Distribution Bezel
1.2.4 Voltage Monitoring Circuit
1.3 Detectors, Ampliers and Bezels
1.4 Retrot and V-Rack Replacement
Section 2 Storage and Handling
2.1 Storage
2.2 Handling
2.2.1 Stacking and Lifting
2.2.2 Unpacking
Section 3 Installation
Section 4 RMA/Warranty
Section 5 Spare Parts
5.1 Recommended Spare Parts
1
2
2
2
2
3
3
4
5
6
6
7
7
7
8
10
11
11
TABLE OF CONTENTS
AMP Rack User Manual
372000-96 Rev G
i

SECTION 1
GENERAL INFORMATION
The Forney AMP Rack has 8 slots that can accommodate the RM-IDD, RM-DR6101E and/or RM-IDD9000
ampliers. The AMP Rack is available with either a single, redundant AC input power supplies, or without
power supplies. See Figure 1 below.
AMP Rack User Manual
372000-96 Rev G
1
Figure 1 Typical AMP Rack Assembly

IDD Flame Detector Heads Manual
372000-05 Rev - K
2
AMP Rack User Manual
372000-96 Rev G
2
EQUIPMENT DESCRIPTION
1.1
POWER REQUIREMENTS
1.2
The AMP Rack will t into any standard 19” EIA rack mounting hardware and is 10 units high.
AMP Rack Component Weight
Empty Rack 18 lbs
Power Supply Module 6 lbs
Power Bezel 1 lb
Assembled rack w/2 PS 31 lbs
The external power source connection is to a dedicated power distribution bezel on the left side of
the AMP rack.
The power module internals are self-regulating and will accept 90 – 250 VAC 50/60 Hz power sources.
Power consumption is 200 VA per power supply. Each power module is supplied with a 5-amp fuse.
Inrush current: 115VAC/ 230 VAC : 75 Amp / 150Amp
Rated load current: 115 / 230 VAC : 4.5 Amp / 2.75 Amp
If only one external AC power source is to be used, the second slot is supplied with a cover. A second
power supply module and a second voltage monitoring board may be added at any time for redundancy.
If the DC power is external and a model without power supplies is used, two covers for the power supplies,
and a cover power bezel will be provided.
Each power supply module provides an output of 8.3 volts @12 amps, +15 volts @ 4.2 amps,
and –15volts @ 3 amps.
Input Power
Output Power
1.2.1
1.2.2

AMP Rack User Manual
372000-96 Rev G
3
The power distribution bezel has one dry contact output per source for monitoring logic level voltage.
If the logic level voltage is above 5.5 VDC, a relay is energized changing the state of its contact.
If the logic level is below the 5.5 VDC threshold, the relay drops out. This form C contact is available
at the power bezel terminals labeled NO, C, and NC. This contact is rated for 240 VAC and 5 amps.
The power distribution bezel includes:
Green LED to indicate Power On
OFF-ON toggle switch
5-amp fuse (replacement part number 71311-00)
L, N, and G power terminals
NC, C, and NO dry contact terminals (used by BMS to monitor AMP Rack logic voltage level)
The terminal block for both the power and dry contact is 6-position rated for 300V and 20 amperes.
It can accept #12-22 AWG wire.
Voltage Monitoring Circuit
1.2.4
Power Distribution Bezel
1.2.3
Figure 2 Bezel with Single and Redundant Power Source

AMP RACK AMPLIFIER SECTION
AMPLIFIER AMP PART NUMBER BEZEL PART
NUMBER DETECTORS
RM-IDD 358317-01 364740-01
IDD-II
IDD-IIU
IDD-IIL
RM-DR 6101E 388056-01 384817-01
IDD-II
IDD-IIU
IDD-IIL
UV-4
DR6.1
RM-IDD9000 408120-01 Bezel included with
Amp
IDD-II
IDD-IIU
IDD-IIL
IDD-Ultra
Each AMP Rack accepts up to (8) ampliers. Any combination of the following may be used.
Details of eld wiring between ame detector and amplier bezel are included in the technical literature
for the amplier.
AMP Rack User Manual
372000-96 Rev G
4
DETECTORS, AMPLIFIERS
AND BEZELS
1.3

V-RACK TO AMP RACK CROSS REFERENCE
OLD V-RACK PART # NEW AMP RACK PART # POWER SOURCE A / POWER SOURCE B
380375-01 404325-01 120 VAC / none
380375-02 404325-02 120 VAC / 120 VAC
380375-04 404325-01 240 VAC / none
380375-05 404325-02 240 VAC / 240 VAC
RETROFIT AND
V-RACK REPLACEMENT1.4
The AMP Rack can replace any AC powered V-rack (380375-xx). See table below.
AMP Rack User Manual
372000-96 Rev G
5
The AMP Rack has only 8 slots compared to 9 in the V-Rack. If the existing V-rack has 9 ampliers
installed, two (2) AMP Racks will be required.
If an AMP Rack is used to replace an existing V-rack, the existing ampliers and bezels may be
re-used. The small power distribution board required on the back of each amplier by the V-rack
is no longer required.
The AMP Rack is smaller (in height only) than the V-rack. If a V-rack is removed, the AMP Rack
will t in its space.
A quantity of 4 AMP Racks will t in one (1) “side” of a 200mm (79”) x 800 mm (31”) x 800 mm
(31”) Rittal style cabinet. The standard TS880B cabinet will hold 8 racks total (4 per side),
if power distribution is installed on the side.

IDD Flame Detector Heads Manual
372000-05 Rev - K
6
CAUTION: Disconnect the cable from the detector by hand, but do NOT twist the
connector barrel. Twisting could cause the wires to become disconnected from solder
connections inside the connector barrel.
SECTION 2
STORAGE AND HANDLING
To preserve the quality of the equipment during storage and handling, follow the below requirements.
STORAGE
2.1
All equipment shall be placed in a storage facility that provides protection from outside weather and
controls the inside environment. Using an inadequate storage facility creates the potential for exposing
the equipment to extremes of temperature, humidity, vibration, and shock. Any of these conditions can
render the equipment unreliable or inoperable under normal operating conditions.
To preserve the reliability of electrical components, store within the following ranges at all times:
Absolute minimum-maximum temperature range: -50º C to +70º C (-58º F to +158º F)
Recommended minimum-maximum temperature range: +10º C to +20º C (+50º F to +68º F)
Relative humidity: 5% to 95% non-condensing
Maximum allowable shock conditions: 25 g for 30 ms.
CAUTION: The storage facility shall be free from rodent or insect infestation.
Rodents will chew through wiring and plastic.
AMP Rack User Manual
372000-96 Rev G
6

When handling equipment, follow the guidelines provided in the following paragraphs.
When unpacking equipment, observe the following guidelines.
HANDLING
2.2
AMP Rack User Manual
372000-96 Rev G
7
When lifting or storing crates, ensure that the crate orientation is as marked. Do not orient the
crates other than as the crates are marked.
Stack only similar size crates. Spacers shall be inserted between crates to allow strapping access.
Crated material may be stacked no more than two high. Non-crated material may not be stacked.
Do not drop any crate or package. Any mishap may void performance warranties.
Do not bump any crates. Damage to the integrity of the crate may damage the equipment or the
protective equipment packaging.
Do not push any crates with a tow motor, fork truck, or any other device. Damage to the integrity
of the crate may damage the equipment or the protective equipment packaging.
Use caution when unpacking crates. Do not dislodge item tagging.
Stacking and Lifting
Unpacking
2.2.1
2.2.2
CAUTION: Lift from all four corners, and maintain a level lift.

Figure 3 Installation Hole Pattern
The AMP Rack is a standard 19” width rack assembly. Attach with 4 bolts per side.
The side anges can be removed and installed in the back of the assembly for panel mount installations.
1. Install the wiring according to the electrical schematics.
2. Refer to the Bill of Material for item descriptions and quantities.
SECTION 3
INSTALLATION
AMP Rack User Manual
372000-96 Rev G
8

Figure 4 Internal Wiring Diagram (reference)
AMP Rack User Manual
372000-96 Rev G
9

AMP Rack User Manual
372000-96 Rev G
10
SECTION 4
RMA / WARRANTY
Forney Corporation warrants this product to be free of defective material and workmanship. Forney will
replace this equipment as long as it is being used for its intended use and is found to be defective upon
receipt up to the expiration of the warranty period.
Prior to returning any material to Forney, please contact your Forney customer service representative and
provide the contract number or the customer purchase order number.

AMP Rack User Manual
372000-96 Rev G
11
SECTION 5
SPARE PARTS
Contract number
Customer purchase order number
For each part ordered, provide the following information:
o Part number
o Part description
o Quantity required
When ordering spare parts, contact Forney’s Spares Department via any one of the following methods
and furnish the following information.
* The power supply is only available as a plug-in assembly; internal parts are NOT available for separate
purchase.
Spare part numbers for the AMP Rack assembly are listed in the following table.
MAIL PHONE FAX
Attn: Spare Parts
Forney Corporation
16479 North Dallas Parkway Suite 600
Addison, TX 75001
(972) 458-6100 or
(972) 458-6142 or
1-800-356-7740
(24-hour direct line)
(972) 458-6600
RECOMMENDED SPARE PARTS
5.1
Part Number Description
404325-01 AMP Rack with Single AC Power Source, 120 – 220 VAC
404325-02 AMP Rack with redundant AC power source, 120 – 220 VAC
404325-03 AMP Rack with NO power supplies
404358-02 Power Supply module*
404345-01 Voltage Monitoring Board
71311-00 Fuse
Table of contents
Popular Rack & Stand manuals by other brands

Multibrackets
Multibrackets M VESA 7 350 073 734 269 installation manual

Sealey
Sealey RE55.V6 quick start guide

Nightlife
Nightlife crowdDJ 10" Kiosk with Desk Stand installation guide

Crimson
Crimson AU42 instruction manual

X-Stand
X-Stand PATRON XSFP456 Assembly and Safe Use Manual

Keysight Technologies
Keysight Technologies E5810B-300 installation guide

Treasure Garden
Treasure Garden AMK-C Assembly and operation guide

Denon
Denon FS500DSD Assembly guide

HUANUO
HUANUO HNLS07S instruction manual

CHIEF
CHIEF STLU installation instructions

CHIEF
CHIEF K1S100 installation instructions

Listen Technologies
Listen Technologies Universal Rack Mounting Kit LA-326 user manual