Franklin Electric incon OPTIMIZER3 User manual

incon®OPTIMIZER3 circuit breaker monitor
user guide

The informaon in this publicaon is provided for reference only. While every eort has been made to ensure the reliability and accuracy of
the informaon contained in this manual at the me of prinng, we recommend that you refer to the appropriate website for the most current
version of this manual. All product specicaons, as well as the informaon contained in this publicaon, are subject to change without noce.
Franklin Electric Co., Inc. does not assume responsibility and expressly disclaims liability for loss, damage, or expense arising out of, or in any way
connected with, installaon, operaon, use, or maintenance by using this manual. Franklin Electric Co., Inc. assumes no responsibility for any
infringement of patents or other rights of third pares that may result from use of this manual or the products. We make no warranty of any kind
with regard to this material, including, but not limited to, the implied warranes of merchantability and tness for a parcular purpose.
Copyright © 2020 Franklin Electric Co., Inc., Madison, WI 53718. All world rights reserved. No part of this publicaon may be stored in a retrieval
system, transmied, or reproduced in any way, including, but not limited to, photocopy, photograph, magnec, or other record, without the prior
wrien permission of Franklin Electric Co., Inc.
For technical assistance, please contact:
franklinfueling.com
3760 Marsh Rd. • Madison, WI 53718 • USA
Tel: USA & Canada +1 800 225 9787 • Fax: +1 608 838 6433
Tel: UK +44 (0) 1473 243300 • Tel: Mex 001 800 738 7610
Tel: DE +49 6571 105 380 • Tel: CH +86 10 8565 4566
INCON is a registered trademark of Franklin Electric Grid Soluons.
000-1533 r4
Conventions used in this manual
This manual includes safety precauons and other important informaon presented in the following format:
NOTE: This provides helpful supplementary informaon.
IMPORTANT: This provides instrucons to avoid damaging hardware or a potenal hazard to the environment, for example: fuel leakage from
equipment that could harm the environment.
CAUTION: This indicates a potenally hazardous situaon that could result in minor or moderate injury if not avoided. This may also be used to
alert against unsafe pracces.
WARNING: This indicates a potenally hazardous situaon that could result in severe injury or death if not avoided.
DANGER: This indicates an imminently hazardous situaon that will result in death if not avoided.
Operating precautions
WARNING: IMPORTANT SAFETY INSTRUCTIONS. BEFORE INSTALLING ANY FRANKLIN ELECTRIC GRID SOLUTIONS EQUIPMENT, READ THIS GUIDE
AND FOLLOW SAFETY AND OPERATING INSTRUCTIONS. SAVE THESE INSTRUCTIONS.
WARNING: Do not disassemble any equipment; contact Franklin Electric Grid Soluons when a repair is required. Incorrect reassembly may
result in a risk of electric shock or re.
WARNING: To avoid electric shock, abide by your company’s safety pracces and the following guidelines:
WARNING: Perform service work only for which you have been trained.
WARNING: Refer to NFPA 70E for electrical safety requirements.
WARNING: Use of Personal Protecon Equipment (PPE) and Protecve Clothing per NFPA 70E guidelines is required. Some examples of these,
but not limited to, are: Electrical-insulang Protecve gloves, Protecve footwear; Protecve clothing for voltage levels, Insulated rescue hooks or
other means for pulling personnel from live circuits.
WARNING: Before working with electricity, remove personal metal items such as rings, bracelets, necklaces, watches, etc. A short-circuit
current can be high enough to weld such items, causing a severe burn.
WARNING: Always wear safety glasses with side shields.
WARNING: To avoid a risk of serious injury or death, DO NOT come into contact with any source of live, electric current!
WARNING: Avoid simultaneous contact with live conductors and enclosures, racks, or hardware that may be grounded.

CONTENTS
Introduction.................................................................................................................................................................................................................5
Safety overview......................................................................................................................................................................................................5
Hazzard Assessment..........................................................................................................................................................................................5
Working on energized conductions and equipment......................................................................................................................................5
Optimizer3 Overview .............................................................................................................................................................................................6
Sensor Inputs .....................................................................................................................................................................................................8
CT Inputs.............................................................................................................................................................................................................9
Control Inputs.....................................................................................................................................................................................................9
Control Input Logic Monitoring.......................................................................................................................................................................10
Input Power, Grounding, Isolation.................................................................................................................................................................10
Relay..................................................................................................................................................................................................................11
Programming ...............................................................................................................................................................................................11
Communication Ports...................................................................................................................................................................................... 12
Communications Software..............................................................................................................................................................................14
Self-Diagnostics...............................................................................................................................................................................................14
Specifications................................................................................................................................................................................................... 15
Installation ................................................................................................................................................................................................................16
Mounting...............................................................................................................................................................................................................16
Current Pickup Coils..............................................................................................................................................................................................18
Navigation ............................................................................................................................................................................................................ 18
SF₆ Gas Monitoring....................................................................................................................................................................................................24
SF₆ Parameter Set Up...........................................................................................................................................................................................25
SF₆ Alarm Settings................................................................................................................................................................................................26
SF₆ GIL (Gas Insulated Transmission Line) Application......................................................................................................................................27
Pressure/Density Trend, Forecast Planning Alarms...........................................................................................................................................29
Low Gas Alarm Forecast & Forecast Planning Alarm ....................................................................................................................................29
Other Sensor Monitoring..........................................................................................................................................................................................30
Temperature Monitoring......................................................................................................................................................................................30
Voltage Monitoring ..............................................................................................................................................................................................32
Current Monitoring...............................................................................................................................................................................................33
Motor Run-Time Metrics.......................................................................................................................................................................................34
Voltage Mode...................................................................................................................................................................................................34
Current Mode....................................................................................................................................................................................................34

Heater Monitoring................................................................................................................................................................................................35
Generic Pressure Monitoring...............................................................................................................................................................................36
Dew Point Monitoring..........................................................................................................................................................................................36
Circuit Breaker Monitor Function.............................................................................................................................................................................37
Purpose of Circuit Breaker Monitoring ...............................................................................................................................................................37
Operating Modes..................................................................................................................................................................................................38
Choosing the Desired Operating Mode.............................................................................................................................................................. 40
Mode 1.............................................................................................................................................................................................................. 40
Mode 2 ..............................................................................................................................................................................................................42
Mode 3 ..............................................................................................................................................................................................................43
Mode 4............................................................................................................................................................................................................. 44
Mode 5 ............................................................................................................................................................................................................. 46
Mode 6..............................................................................................................................................................................................................49
Mode 7 ...............................................................................................................................................................................................................51
Velocity & Average Velocity Measurements.......................................................................................................................................................52
Current and Voltage Logging..............................................................................................................................................................................54
Use of AUX Inputs for control circuit status monitoring....................................................................................................................................55
DNP3.0 .......................................................................................................................................................................................................................56
Programming for DNP3........................................................................................................................................................................................56
DNP3 Behavior......................................................................................................................................................................................................58
Flag Behavior ...................................................................................................................................................................................................58
Value Behavior.................................................................................................................................................................................................58
Time Stamps.....................................................................................................................................................................................................58
Units Conversion..............................................................................................................................................................................................59

5
INTRODUCTION
SAFETY OVERVIEW
The Optimizer3 Circuit Breaker Performance and SF₆ Gas Density Monitor is intended to be used on high voltage energized circuit
breakers or equipment. Personnel using equipment on energized equipment must be authorized by the relevant regulatory bodies
to carry out such work and must have appropriate training.
The information given in this document is given as a guide only. It is the user’s responsibility to ensure that correct and safe
procedures are followed at the actual worksite. Franklin Electric Grid Solutions oers no warranty or indemnity for accidents that
may occur when following these instructions.
HAZZARD ASSESSMENT
Prior to installing the equipment, the operator must carry out a worksite, pre-job hazard assessment to identify the safety and
environmental needs. This must be done prior to commencing work and prior to recommencing work after leaving and returning
to the worksite. As a minimum, this hazard assessment should:
• Identify possible hazards and risks.
• Identify the safety needs of the job.
• Identify the correct procedures, practices and equipment.
• Eliminate unsafe conditions and actions from the worksite.
• Identify the need for personal protective equipment.
• Inspect equipment before use.
Prior to working with and installing Optimizer3, you should check the following:
• The sheaths of all cables are secured and undamaged.
• Plugs and connectors are properly connected and serviceable.
• There should also be an ongoing risk assessment during the job.
WORKING ON ENERGIZED CONDUCTIONS AND EQUIPMENT
For the correct and safe use of this equipment, it is essential that all operating personnel follow appropriate safety procedures.
Check with your employer and relevant regulatory body’s rules for working with energized equipment.

6
OPTIMIZER3 OVERVIEW
This guide is written for the Optimizer3 with firmware version 1.9.1 and higher.
The Optimizer3 is an on-line continuous performance monitor for high voltage circuit breakers. It provides information for the
process of Condition-Based Maintenance
Optimizer3 performs four main functions:
1. Mechanism Timing.
2. Estimation of interrupter condition as degraded by internal arcing eects.
3. Measurement of SF₆ gas density, pressure, and dew point temperature.
4. Status Monitoring of Auxiliary systems.
The Optimizer3 is designed to be installed in the circuit breaker control cabinet. Usually this is the most convenient place because
there is easy access to SF₆ plumbing for the density sensors, bushing CT circuits, and control circuits. Often the O&M technicians
have no access to the control building where the protective relays are located. If it is not possible to locate the Optimizer3 in the
control cabinet, then it may be installed in the control building. Most often this decision is based on access to communication links
or SCADA RTU access.
For use as a SF₆-only monitor, such as for monitoring compartments of GIS or SF₆ insulated bus, the Optimizer3 may be located up
to 2000 feet from the digital SF₆ density or pressure sensors if AWG 14 wire is used. This makes it feasible to locate the Optimizer3
in a control building, near communications access points.
If access to circuit breaker control cabinets is restricted, Optimizer3 may also be installed in a separate enclosure, mounted to the
frame of the circuit breaker. This way, Optimizer3 can be accessed without opening the circuit breaker control cabinet, without
restriction of the breaker being taken out of service.
Figure 1 – Breaker Timing Measurements

7
Optimizer3 measures and logs the following information:
• Breaker status OPEN/CLOSE • Heater Current • Open Average Velocity
• SF₆ Density • Optimizer3 Line Voltage • Close Average Velocity
• SF₆ Temperature • Ambient Cabinet Temperature • Open Operation Arcing Time
• SF₆ Dew Point • Days since Last Operation • Clearing Time
• Sensor Malfunction • Restrike Occurrence • Opening Travel Time
• Motor Run Time • Contact Life; cumulative I²T or IT • Closing Travel Time
• Motor Runs per Day • Last Trip Coil Energized (TC1/ TC2) • Total Operation Count
• Motor I²T • Open Latch Time • Non-Fault Operation Count
• Motor Total Run Time • Close Latch Time • Fault Operations Count
• Heater Status On/O
The Optimizer3 continuously monitors the SF₆ attributes according to what sensors are used. Available sensors include:
1. Temperature-Compensated Pressure analog 4-20 mA.
2. Temperature-Compensated Pressure and Temperature (Model PSDP Digital Pressure Sensor).
3. SF₆ Density and Temperature (model DSDP Digital True Density Sensor).
4. SF₆ Density analog 4-20 mA.
5. SF₆ Dew Point Temperature analog 4-20 mA.
The Optimizer3 uses these measured attributes to calculate other user-defined properties in desired units. Optimizer3 calculates
density, pressure, trends, trend rates, changes in mass, etc. Most attributes can be compared to static alarm settings for assertion
when they go out-of-tolerance. Optimizer3 issues alarms via contacts, through DNP3.0 points, and via HTTPS web service, locally or
remotely.
The Optimizer3 Installation has been kept simple, with few connections required to the circuit breaker control circuits. Simple
electrical connections are made to trip and close circuits. Split-core Pickup Coils are attached to bushing CT secondary circuits. SF₆
gas sensors may be installed on the gas plumbing in several ways.
The Optimizer3 can be applied to any type of circuit breaker- vacuum, bulk oil, minimum oil, air blast, SF₆, live tank or dead tank.
Optimizer3 is useful on small sub-transmission circuit breakers to large EHV circuit breakers.
Contact wear models vary slightly by manufacturer and technology used. During set up, the manufacturer’s limits for contact wear
and timing should be used. If this information is not available, then IEEE C37.06-1989 standard should be used as a guide.

8
SENSOR INPUTS
The Optimizer3 includes eight inputs for sensors and five inputs for control signals.
Figure 2 – Sensor Field Wiring
Loop-powered (2-wire) digital or analog sensor inputs.
Supports 4-20 mA sensors or digital sensors with up to
18 VDC compliance voltage. 20 AWG twisted-pair wiring
recommended. Digital good to 700m.
Loop-powered (2-wire) analog-only sensor inputs.
Supports 4-20 mA sensors with up to 24 VDC compliance
voltage. 20 AWG twisted-pair wiring recommended.
Sensor 5
Sensor 4
Sensor 3
Sensor 2
Sensor 1
Sensor 5
Sensor 4
Sensor C
Sensor B
Sensor A
Sensor inputs A, B, and C are dual-function. They accept either 2-wire 4-20 mA analog sensors or 2 wire Sensors with a Proprietary
Digital Protocol. Sensor inputs 1-5 are 4-20 mA analog only and do not accept the digital protocol. For each 4-20 mA analog sensor,
there is a corresponding setup area in the CONFIGURATION web pages where the scaling of the input is done. The digital Sensors
require no scaling. The Optimizer3 scales those signals automatically.
• 18 VDC sensor power is provided for sensors A, B, and C.
• 24 VDC sensor power is provided for Sensors 1-5.

9
CT INPUTS
The Optimizer3 measures the current flowing through the bushing CT secondaries of the circuit breaker. These measurements are
used in the contact wear calculations, arc time, and determination of Fault versus Non-Fault operations. Line current is also logged.
During installation, small split-core Pickup Coils are attached to the relevant bushing CT circuits, noting the bushing CT turns ratio.
Depending on the maximum current expected in the bushing CT circuits, an optimal split-core Pickup Coil is selected. INCON® oers
split-core Pickup Coils with the following full-scale ratings:
Table 1 – Pickup Coil Ratings.
INCON® Part Number CT-20 CT-30 CT-50 CT-100 CT-160 CT-250 CT-400 CT-800
Full Scale Rating (A) 20 30 50 100 160 250 400 800
Range (A) 1.4-20 2.1-30 3.5-50 7-100 11.2-160 17.5-250 28-400 56-800
Each “CT-nn” part number is for a set of three Pickup Coils. The Pickup Coils are compatible with 50 or 60 Hertz power systems.
The split-core Pickup Coils snap on over existing insulated bushing CT secondary circuits without tools and are rated 1.0 % accuracy
and 0.05 VA burden at 5 amps. Removal or disruption of bushing CT circuits is not necessary. Although referred to as a CT, these are
sensors that give 0-5 VAC output for 0 to Full Scale current.
CONTROL INPUTS
The use of each input is determined by the circuit breaker application and Mode of operation. Each control input is multi-function
and is defined in the system CONFIGURATION. The control inputs are continuously interrogated to detect when the control circuit
nodes are in the active or inactive state. Each AUX input is fused on both legs, optically isolated from the monitoring processor
circuits, and has an input impedance of 540 kΩ. The O/On voltage threshold is approximately 35 volts.
Figure 3 – Power, Relay, Aux Input, Field Wiring
Power:
110–264 V AC/DC 50/60 Hz
Twisted pair recommended.
Relay Contact Rating:
NO: @ 250 VAC or 30 VDC
NO: @ 250 VAC or 30 VDC
48–250 VDC
Twisted pair
recommended.
AUX 5
AUX 4
AUX 3
AUX 2
AUX 1
GND
L1
L2
LOAD
LOAD

10
CONTROL INPUT LOGIC MONITORING
The logical state of each Control Input is continuously monitored and compared with the Input Polarity settings, in the context of
the Input Mode setting. Based upon these settings, the Optimizer3 knows the normally expected logic state of each Input, when
the breaker is closed or open. If the voltage state of an Input violates its closed or open state for longer than 3 seconds, the A-B
Logic Alarm will activate. This alarm is self-clearing once the provoking condition returns to the normal state. A record of the alarm
is written in the Event History, along with the dates and times the alarm occurred and was cleared.
This A-B Logic alarm serves as a Trip Coil integrity monitor in Input Modes 2, 4, 5, 6 and 7. The normal voltage state of the Control
Input wired across the Trip Coil is low. The low impedance (approximately 50 ohms) of the Trip Coil, energized through the
high-impedance Red Light, will normally produce a very low voltage to the Optimizer3 Control Input. If the Trip Coil impedance
significantly increases or it becomes open-circuited, the voltage drop across the damaged coil will be high, causing the Optimizer3
to assert the A-B Logic alarm.
INPUT POWER, GROUNDING, ISOLATION
The Optimizer3 operates from station battery DC or AC station service. Nominal current draw is 0.5 amp. The power input
automatically accepts either AC or DC. Both power supply legs are fused. If external fuses are used, 3.15 amp slow-blow are
recommended. Power input leads are isolated from chassis and are floating and not referenced to ground.
Ground connection is internally connected to the metal chassis. It is recommended that the ground be connected to the station
ground or ground bar inside the circuit breaker cabinet. Follow the electrical grounding standard in eect at your utility.
All wiring connections are made to removable Phoenix connectors. The Optimizer3 may be electrically isolated by pulling out
all the connectors from their mating sockets. Follow the electrical isolation standard in eect at your utility. If fused-cutouts are
desired, locate them physically near the Optimizer3 with 3.15 Amp Slow-Blow fuses for all input and control wiring. The Optimizer3
uses a switch-mode power supply with universal input. On power-up, it draws more than nominal current for 1 mS. Slow-Blow
fuses are mandatory if external fuses are used.
IMPORTANT: The Optimizer3 contains flash storage (SD card) for booting the device and saving data. Flash storage has the
potential to be corrupted under rare circumstances due to power loss while the software is writing to the SD card. The Optimizer3
has both hardware and software features to prevent corruption from occurring on boot-up or shut down.
The protection features begin working after 20 seconds of operation. It is important to make sure the power to the Optimizer3 is
solidly connected to terminals without the chance of disconnection and loss of power during the first 20 seconds of operation.

11
RELAY
The Optimizer3 is equipped with one Form C (SPDT) dry contact relay. The relay is asserted by the state of alarms or Digital Inputs.
The relay is fully programmable and must be setup as needed. The relay is un-programmed in the default settings.
PROGRAMMING
The relay is programmed by adding an input for each alarm or Digital Input required to assert the relay. Inputs are added by
clicking the “+” sign. New numbered inputs appear below.
Figure 4 – Create Relay Inputs
The inputs can each be assigned to an “Alarm” or “State”, selected from the “Type” menu.
Figure 5 – Assign Relay Input
Digital Inputs are AUX input channels that are unused, depending upon the Input Mode being used (see page 38). There may be
only one or two to choose from. When the AUX input is energized, the relay will be asserted.
If the Relay Input is an Alarm, it can be left in a generic mode, allowing any alarm to assert the relay. If only specific alarms are
desired to assert the relay, further programming is needed to assign the Event Code, and possibly the Event Key.
Select the Event Code from a menu of all possible alarms and conditions. Some Event Codes allow an Event Key to limit the relay
assertion to a specific CT phase or sensor channel associated with the Event. In most cases, the Event Key can be set to “Any”,
which will allow any alarm event of the same Event Code to assert the relay.

12
Figure 6 – Assign Relay Event Code
The relay’s Polarity can be programmed to “Invert”. This causes the relay to assert when no alarms are active and de-assert when
an alarm occurs. This mode can be used to create a “fail-safe self-diagnostic” alarm of sorts. If the Optimizer3 should lose power
or experience a catastrophic failure, the asserted relay would release. The normally closed contacts would close, notifying the
supervisory system of the failure.
Figure 7 – Program Relay Polarity
If desired, the relay can be programmed to “Latch” in the asserted state. This is useful for bringing attention to alarm conditions
that are occasional or momentary. The relay will remain in the asserted state until manually reset or until the Optimizer3 reboots.
The Relay Latch Reset button is located on the Action page.
Figure 8 – Reset Latched Relay
COMMUNICATION PORTS
Communication ports are used for Configuration of alarms and settings, history data retrieval, resets, data viewing, and data
transfer using DNP3.0 protocol.
RS-485 is half duplex. This port is used for DNP3 communication only. No user interface actions can be done through this port. If the
Optimizer3 is the last device in the network, a wire jumper is needed between terminals marked Term Jump. This jumper places an
internal 120Ω resistor into the circuit for termination. Factory defaults are Data bits: 8, Stop bits: 1, Parity: 1, Baud Rate: 9600 bps,
flow control: none.
USB Port is used for manual data dumping and password resetting. (Contact Technical Service). A USB memory stick with special
script files is necessary to perform specific operations, each operation requires a dierent script. Script files must be located in the
root directory of the USB memory stick. Files in directories on the memory stick will not be seen by the Optimizer3.

13
Mini USB Port default IP address from the factory is https://192.168.171.171 . Drivers may be required. It is recommended that the
PC or laptop be connected to a network with internet access upon first connection to the Optimizer3 using the Mini USB. The PC or
laptop will better be able to find the necessary driver files for the device. If this is not possible or does not work, a Mini USB driver
file is included on the documentation memory stick, which is included with the Optimizer3. It also contains the Optimizer3 User’s
Guide, DNP3 Profile Document and other information. The Mini USB Port can be used for local data dumping, alarm resetting,
downloading, and uploading configuration settings, firmware upgrades and all user interface functions.
Ethernet 1 (Copper) and Ethernet 2 (Fiber Optic) with multiple user’s ports are used with DNP 3.0 and TCP/IP protocols. Optimizer3 is
multi-session so both can be run simultaneously. When connected to a secure local area network, the Optimizer3 can be accessed
remotely with a web browser by using its unique IP address. Firmware upgrades can be performed (locally or remotely) via this
port using the INCON® upgrade tool.
• Ethernet 1 (Copper) Default IP Address is https://192.168.168.168
• Ethernet 2 (Fiber) Default IP Address is https://192.268.169.169 -100 Mbps ST Connection.
• The Ethernet 2 hardware uses multi-mode-capable transceivers.
Ethernet 2 is a hardware option included with the model OM3D-F only. Even when so equipped, it is NOT turned on by default. It
must be enabled and configured before use.
IMPORTANT: Ethernet 1 and Ethernet 2 cannot have the same IP address. If this occurs, the network will be unstable and
unreliable. If these ports get accidentally set the same, connect to the Optimizer3 with the mini-USB port and change the
configuration settings of the Ethernet ports so they are dierent IP addresses.
Customizing the ports is done on the Configuration Page in the Networking Section.
Figure 9 – Network Settings
Clicking on each section reveals the fields where the settings are configured.

14
If using wired Ethernet 1 network connection, use settings as provided by your network administrator.
If using fiber-optic Ethernet 2 network connection, use settings as provided by your network administrator.
The settings for USB networking should be left as shown, so that the local access IP address is always known.
Note: The port addresses are saved in the .XML file during a configuration download. If multiple Optimizer3 monitors are to be
configured using one setup file, the addresses can be edited with a word processor, then uploaded for each monitor.
Dynamic Host Configuration Protocol (DHCP) is a network protocol that enables a server to automatically assign an IP address to a
computer from a defined range of numbers (i.e., a scope) configured for a given network.
Static IP address may be assigned (manually by giving it the XXX.XXX.XXX.XXX number), or they may be automatically assigned by
pointing the Optimizer3 to a DHCP server that manages a range of addresses and “dynamically” assigns these addresses.
COMMUNICATIONS SOFTWARE
The Optimizer3 is a web server. A web browser is required to communicate with it using the TCP/IP protocol via the Mini-USB port
or either of the Ethernet ports. If DNP 3.0 protocol is used, the DNP master device will have software for network communication.
Optimizer3 responds to validated DNP commands.
SELF-DIAGNOSTICS
A blinking green LED “Flashing OK” indicates normal operation of the microprocessor system.
See page 11 regarding programming the relay for use in a “fail-safe, self-diagnostic” mode.

15
SPECIFICATIONS
Table 2 – Specifications.
Specifications
Size: 11.125W X 5.625H X 2.625D, Inches Nominal, Shipping Weight: 6 Lbs.
Input Power: 110-250 VDC or 90-264 VAC (50/60 Hz). Power consumption is 60 VA max.
Recommended External Fuse Rating: 3.15 Amp Slow-Blow
Operating Temperature: -40˚C to +65˚C
Alarm Relay Contact: One form C, 1 amp at 30 VDC, 2 amps at 250 VAC rating.
Analog Sensor Input Accuracy: ±1% max, ±0.5% typical
Pluggable Connector Wire Size: 12 to 24 AWG
Data Storage- Non-volatile memory with capacity of:
10,000 Application Events
10,000 Alarm Events
5000 Circuit Breaker Monitoring Events
5000 SF₆ Gas Parameter data points
750 Daily Summary logs
5000 3 phase Line Current (measured and scaled from bushing CT secondaries)
1000 Line Voltage Measurements (as measured at power input)
5000 Ambient Temperature Measurements (as measured at the monitor)
Test Standards:
IEEE C37.10
CISPR 16-2-1 (Conducted Emissions)
CISPR 16-2-3 (Radiated Emissions)
IEC61000-4-2 (ESD)
IEC61000-4-3 (Radiated RF)
IEC61000-4-4 (EFT)
IEC61000-4-5 (Surge)
IEC61000-4-6 (Conducted RF)
IEC 61000-4-11 (Voltage Dips & Interrupts)
IEC 61000-4-12 (Damped oscillatory wave- Power Ports)
FCC Part 15, Subpart B; ICES-003 (Emissions)

16
INSTALLATION
MOUNTING
Figure 10 – Optimizer3 Mounting Dimensions (Not Actual Size)
OPTIMIZER3 MOUNTING
DIMENSIONS IN INCHES [MILLIMETERS]
(NOT SHOWN ACTUAL SIZE)
11.1
[282,1]
5.63
[142,9]
4.75
[120,7] 2.38
[60,3 ]
.25
[6,4 ]
.31
[8 ]
10.36
[263]
Optimizer3 may be mounted to the circuit breaker cabinet on interior side walls, on swing panels, or any other convenient location
within the control cabinet. It must be mounted horizontally so that the air vent holes on the bottom and top can provide cooling
by convection air flow. If Optimizer3 cannot be mounted horizontally, the ambient temperature measured by the sensor may read
slightly higher than expected.
There are two rows of pluggable connectors on the left side and one row on the right side. Each plug is fastened by two screws,
one on each end of each connector. These must be tightened during installation to assure the plugs stay engaged and do not come
loose from normal shock and vibration of the circuit breaker.
In the event that isolation of the monitor is required, or replacement is necessary, the fasteners are unscrewed at each end and the
connectors unplugged.
CAD files of dimensioned drawings are available from INCON® Technical Service.

17
Figure 11 – Optimizer3 General Dimensions
Sensor 5
Sensor 4
Sensor 3
Sensor 2
Sensor 1
Output 2
Output 1
Sensor C
Sensor B
Sensor A
AUX 5
AUX 4
AUX 3
AUX 2
AUX 1
RS–485 A
A+
B-
GND
Term
Jmp
A+
B-
GND
Term
Jmp
RS–485 B
GND
L1
L2
NO
COM
NC
OPTIMIZER3 MOUNTING
DIMENSIONS IN INCHES [MILLIMETERS]
(NOT SHOWN ACTUAL SIZE)
11.1
[282,1]
5.63
[142,9]
4.75
[120,7]
2.93
[74]
10.36
[263]
.31
[8 ]

18
CURRENT PICKUP COILS
Mounting the Optimizer3 as close as possible to the CT area will minimize Pickup Coil lead length and reduce the possibility of
noise. The 20 AWG twisted pair leads should be cut to length and neatly run in a cable management product or secured with wire
ties. The connections are not polarized even though they are colored black and white. If longer length is needed, do not extend the
leads in the field. Contact Technical Service. The pickup coil output is 0-5 Volts AC.
Figure 12 – Optimizer3 Wiring of Current Transducers/Typical Arrangement
RS–485 A
A+
B-
GND
Term
Jmp
A+
B-
GND
Term
Jmp
RS–485 B
OPTIMIZER3 MOUNTING
DIMENSIONS IN INCHES [MILLIMETERS]
(NOT SHOWN ACTUAL SIZE)
The Optimizer3 should be installed as close to the CT Pickkup
Coils as possible. Cut any excess cable from the Pickup Coils.
It is not recommended to exted the Pickup Coil cables.
Snap-On CT Pickup Coils
(Non-Polarity Sensitive)
Phase B
Secondary
Phase C
Secondary
Phase A
Secondary
NAVIGATION
Optimizer3 functions as a web server. The only required software is a web browser. Using a browser and the mini-USB cable
supplied with the unit, log into the unit. Enter the IP address “https://192.168.171.171” into the address bar to initiate the connection.
The FIRST login attempt will require a new Admin password. The password is blanked from view and needs to be entered two times
to ensure accuracy.
Figure 13 – Initial Entry of the Admin Password. Figure 14 – Normal Login Prompt.
After the Admin password is set, the normal login prompt will appear.
Login with the “admin” username and password just created. The landing page after login is the CBM page which shows the
present status of the circuit breaker.

19
Figure 15 – CBM Status Page
Click on Configuration to begin. Each category can be individually expanded by clicking on the cell or click on “Group >>” to expand
all categories. Click the “Show Errors” button.
Figure 16 – Configuration Page

20
Fill-in the three passwords and Site Name showing as “<not set>” and then click “Save”.
Figure 17 – Setting Passwords and Site Name
It is best to set the Time Zone at this time. If the Time is set first and then the Time Zone is changed, the time will be adjusted
automatically. Therefore, set the Time Zone first, THEN set the time. Click the “Save” button
Figure 18 – Selecting the Time Zone
Set the Time by clicking in the Date/Time tab. Adjust as needed, then click the “Set” button.
Figure 19 – Setting Date and Time
The Optimizer3 system time can be synchronized with an NTP server or from a DNP3 master. The NTP server’s IP address is specified
in the Configuration Page, in the Date/Time group, ‘NTP Servers’ option. Multiple NTP servers can be used by placing a space
between the addresses.
Figure 20 – Setting the NTP Server IP Address
Table of contents