Remote controller set up first time Remote controller set up first time
When you first power up the unit the remote controller will ask you a few
questions please follow as directed below:
1. Select language, English, press OK
2. Date and Time, use left and right to select 12 or 24-hour format, press
down,
3. Year will highlight, use up and down to change, press right, set month
using up and down,
4. Press right, set day using up and down,
5. Press right, set hours and minutes. Then press ok.
6. Configuration assistant, press ok
7. Is this device attached to unit? Select yes using right, press ok
8. Is this device used as a room thermostat? Select no, press ok
9. How many circuits do you have? Select 1, press ok
10. What are the heat emitters on the circuit? Select to suit (Radiators or
UFH), press ok
11. If you have rads AND UFH select rads.
12. Do you have a domestic hot water tank installed? If you have a
cylinder select yes, press ok.
13. Do you have a swimming pool? No, press ok.
14. Do you have a boiler installed? No, press ok. (If you have a hybrid
system or Backup boiler, select yes, it will then ask what the bi-valent
point is, set to 3 degrees or you’re your design temp)
15. Do you have electric backup heater? Select no on Monobloc and HT
units, select yes in Split and Combi units, press ok.
16. How many thermostats are installed? Select 0 (This is asking how
many HITACHI thermostats are installed on the system, so we select 0,
even though your system will be controlled by an external run signal),
press ok.
17. Completed shows, press ok.
On all units Activate Anti Legionella
1. Scroll up to DHW – OK
2. Scroll down to Anti Legionella – OK
3. Status press right to change to enabled
4. Press down, to operation day, press left to Tuesday
5. Down to start time to right to 3 am
6. Press down setting temperature 60°C
7. Press return x 2
On all units Stop Pumps running when there is no demand.
1. DSW 4, Pin 5 needs to set- pushed up (already done)
2. Scroll to Heat Pump – OK
3. Water Pump Configuration – OK
4. Minimum off time – Change to 0 mins
5. Minimum on time – change to 0 mins
6. Overrun time – change to 0 mins
7. Press return x2
On all units Adjust the weather comp
8. In system configuration, ok
9. Space heating, ok
10. Circuit 1, ok
11. Water calculation mode, ok
12. OTC gradient shows go left to points.
13. In points graph, pressing down highlights the water temp at low
ambient, set this using left or right arrows to 45°C for UFH or 50°C for
radiators. On HT units set this to 70°C
14. Pressing down highlights water temp at low ambient temperatures,
set this using right or left to 37°C. On HT units set this to 50°C
15. Press down to set the low ambient temp set this to -2 with the right
button,
16. Press down to set the high ambient temperature, use the left arrow
button to set this to 15°C.
17. Press return 3 times until you get back to the menu.
IMPORTANT do this: Air Purge Procedure
18. Scroll down to Commissioning – OK
19. Air Purge Procedure – OK
20. Set duration – 30 mins use left or right, Down Select start air purge –
OK
21. Do you want to continue Select Yes – OK
22. Let the unit cycle the pumps and get the air out the system, it will
take it up to 30 mins. Press down Select Cancel – OK to stop Air Purge
procedure.
23. Once finished press return 3 times to menu screen, scroll down to
return to user mode, press ok. Do you want to continue right ok.
Accessing the Installer Menu
To get into the installer menu to start the commissioning process, hold the Back/Return and the OK button together for three seconds.
It was ask for a passcode, the passcode is: Right, Down, Left, Right. “Passcode Correct” shows, press ok. You will now see a picture of a
Spanner in the bottom, right hand corner. Press the Menu button and you will see more options in the menu than when in user mode.
On a Combi unit, only If you are using a buffer, plate heat exchanger or a
low loss header with pump 3.
1. Press Menu
2. System Configuration – OK
3. Optional Functions – OK
4. System – OK
5. Hydraulic Separator Status – press right change to enabled
6. Press return x 2
This setting activates the pump on the heating side of the header.