manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. FULTON
  6. •
  7. Relay
  8. •
  9. FULTON RM7895A User manual

FULTON RM7895A User manual

Popular Relay manuals by other brands

Woodward BU1-DC2 manual

Woodward

Woodward BU1-DC2 manual

ABB SSR32 product manual

ABB

ABB SSR32 product manual

Siemens SIRIUS 3UG4633 operating instructions

Siemens

Siemens SIRIUS 3UG4633 operating instructions

Siemens SIRIUS 3TK2824 A.20 Series Original operating instructions

Siemens

Siemens SIRIUS 3TK2824 A.20 Series Original operating instructions

Shelly Pro Series user manual

Shelly

Shelly Pro Series user manual

GE MVAX 11 Technical manual

GE

GE MVAX 11 Technical manual

ABB RELION REF615R manual

ABB

ABB RELION REF615R manual

Kemo Electronic B197 quick guide

Kemo Electronic

Kemo Electronic B197 quick guide

Seg MRM3 manual

Seg

Seg MRM3 manual

Basler BE1-700C manual

Basler

Basler BE1-700C manual

CD Automation REVEX 2PH 280A user manual

CD Automation

CD Automation REVEX 2PH 280A user manual

ABB SPAJ 142 C User manual and technical description

ABB

ABB SPAJ 142 C User manual and technical description

Ruelco 1S04 Operation manual

Ruelco

Ruelco 1S04 Operation manual

Basler V3E Z1P B2C1F instruction manual

Basler

Basler V3E Z1P B2C1F instruction manual

GE DGP instruction manual

GE

GE DGP instruction manual

Kyongbo Electronics GDR-D01 user manual

Kyongbo Electronics

Kyongbo Electronics GDR-D01 user manual

Eaton easyE4 series Application note

Eaton

Eaton easyE4 series Application note

Siemens BD2-AK03X/FS Series installation instructions

Siemens

Siemens BD2-AK03X/FS Series installation instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

PRODUCT DATA
32-00122-01
SIL3
Capable
RM7895A
Relay Module
APPLICATION
The RM7895A Relay Module is a microprocessor based
integrated burner control for automatically fired gas, oil or
combination fuel single burner applications. The
RM7895A consists of the Relay Module. Subbase,
Amplifier and Purge Card are required to complete the
system. Options include Keyboard Display Module (KDM),
Personal Computer Interface, Data ControlBus™* Module,
Remote Display Module, First-Out Expanded Annunciator
and Combustion System Manager™* Software.
The RM7895A is programmed to provide a level of safety,
functional capability and features beyond the capacity of
conventional controls.
Functions provided by the RM7895A include automatic
burner sequencing, flame supervision, system status
indication, system or self-diagnostics and
troubleshooting.
FEATURES
• Safety Features
— Closed loop logic test.
— Dynamic input check.
— Dynamic safety relay test.
— Dynamic self-check logic.
— Internal hardware status monitoring.
— Tamper resistant timing and logic.
• Access for external electrical voltage checks.
• Application Flexibility.
• Communication interface capability.
• Dependable, long-term operation provided by
microcomputer technology.
• First-out annunciation and system diagnostics
provided by an optional Keyboard Display Module.
• First-out expanded annunciation with 26 Light
Emitting Diodes (LEDs) for limit and interlocks
(optional).
• Five LEDs for sequence information.
• Interchangeable plug-in flame amplifiers.
• Local or remote annunciation of RM7895 operation
and fault information.
• Nonvolatile memory; RM7895 retains history files
and sequencing status after loss of power.
• Remote reset (optional).
• Report generation (optional).
• Selectable recycle or lockout on loss of airflow.
• Selectable recycle or lockout on loss of flame.
• Shutter drive output.
Contents
Application ............................................................................................ 1
Features .................................................................................................. 1
Specifications ...................................................................................... 2
Principal Technical Features ........................................................ 5
Safety Provisions ................................................................................ 5
Wiring ....................................................................................................... 8
Assembly ................................................................................................ 10
Operation ............................................................................................... 12
Checkout ................................................................................................ 16
Troubleshooting ................................................................................. 21
RM7895A RELAY MODULE
32-00122-01 2
• Burner controller data (optional):
— Expanded annunciator status.
— Flame signal strength.
— Hold status.
— Lockout/alarm status.
— Sequence status.
— Sequence time.
— Total cycles of operation.
— Total hours of operation.
— Fault history providing for the six most recent
faults:
• Cycles of operation at the time of the fault.
• Expanded annunciator data at the time of the
fault.
• Fault message and code.
• Hours of operation at the time of the fault.
• Sequence status at the time of the fault.
• Sequence time at the time of the fault.
— Diagnostic information:
• Device type.
• Flame amplifier type.
• Flame failure response time.
• Manufacturing code.
• On/Off status of all digital inputs and outputs.
• Selected prepurge time.
• Software revision and version of RM7895 and
optional Keyboard Display Module.
• Status of configuration jumpers.
SPECIFICATIONS
Model:
RM7895A Relay Module. Provides primary control.
Provides automatic burner sequencing, flame
supervision, system status indication, system or self-
diagnostics and troubleshooting. Intermittent pilot
valve operation.
Electrical Ratings (see Table 1):
Voltage and Frequency:
120 Vac (+10/-15%), 60 Hz (±10%).
Power Dissipation: 10W maximum.
Maximum Total Connected Load: 2000 VA.
Fusing: Total Connected Load: 15A maximum, Type SC or
equivalent, fast blow.
Table 1. Terminal Ratings.
aThe RM7895 must have an earth ground providing a connection between the subbase and the control panel or
equipment. The earth ground wire must be capable of conducting the current to blow the 15A fuse (or breaker) in event
of an internal short circuit. The RM7895 needs a low impedance ground connection to the equipment frame, which, in
turn, needs a low impedance connection to earth ground. For a ground path to be low impedance at rf frequencies, the
connection must be made with minimum length conductors that have maximum surface areas. Wide straps or brackets,
rather than leadwires, are preferred. Be careful to verify that mechanically tightened joints along the ground path, such
as pipe or conduit threads or surfaces held together with fasteners, are free of nonconductive coatings and are
protected against mating surface corrosion.
b2000 VA maximum connected load to RM7895 Assembly.
cCan also be 120 Vac, 1A pilot duty.
dCan also be 65 VA pilot duty with motorized valve, 1150 VA inrush, 460 VA open, 250 VA hold.
Environmental Ratings:
Ambient Temperature:
Operating: -40°F to +140°F (-40°C to +60°C).
Storage: -40°F to +150°F (-40°C to +66°C).
Humidity: 85% rh continuous, noncondensing.
Vibration: 0.5G environment.
Dimensions: See Fig. 1.
Weight: RM7895 with dust cover: 1 pound, 15 ounces
(0.87 kg).
Terminal Number Description Ratings
G Flame Sensor Ground —
Earth G Earth Grounda—
L2(N) Line Voltage Common —
3 Alarm 120 Vac, 1A pilot duty.
4 Burner Motor 120 Vac, 9.8 AFL, 58.8 ALR (inrush).
5 Line Voltage Supply (L1) 120 Vac (+10/-15%), 50 or 60 Hz (±10%)b,c.
6 Burner Control and Limits 120 Vac, 1mA.
7 Airflow Interlock 120 Vac, 9A.
8 Pilot Valve/Ignition 120 Vac, 4.5A ignition and 50 VA pilot dutyc.
9MainFuelValve
120 Vac, 2A pilot dutyd.
10 Ignition 120 Vac, 4.5A ignitionc.
(F)11 Flame Sensor 60 to 220 Vac, current limited.
12 to 21 Unused —
22 Shutter 120 Vac, 0.5A.
RM7895A RELAY MODULE
332-00122-01
IMPORTANT:
Flame Detection System available for use with
RM7895. To select your Plug-In Flame Signal
Amplifier and applicable Flame Detector, see Table
2 and Fig. 3 and 4.
Table 2. Flame Detection Systems (Fig. 3 and 4).
aOrder flame rod separately; see holder instructions.
bThe C7012A,C, C7027, C7035 and C7044 Flame Detectors should be used only on burners that cycle on-off at least
once every twenty-four hours. Appliances with burners that remain on continuously for twenty-four hours or longer
should use the C7012E,F Flame Detector with the R7847C Amplifier or the C7076A,D Flame Detector with the R7886A
Amplifier as the ultraviolet flame detection system.
Table 3. Sequence Timing for Normal Operation.
* STANDBY and RUN can be an infinite time period.
** PURGE will be determined by which ST7800A Purge Card is selected.
Approvals:
Underwriters Laboratories Inc. listed, File No. MP268,
guide No. MCCZ.
Factory Mutual approved, Report No. J.I.1V9A0.AF.
IRI acceptable.
Federal Communications Commission, Part 15,
Class B—Emissions.
SIL 3 Capable:
SIL 3 Capable in a properly designed Safety Instrumented
System. See form number 65-0312 for Certificate
Agreement.
Mounting: Q7800A for panel mount.
Required Components:
Plug-in Flame Signal Amplifier, see Table 2.
Plug-in Purge Timer Cards: selectable ST7800A: two sec-
onds to 30 minutes.
Q7800A Wiring Subbase.
Accessories:
203541 5-wire connector, required when Keyboard Dis-
play Module is used for remote reset; remote annuncia-
tion or report generation.
Optional:
Q7700A1014 Communication Interface Base Unit.
QS7800A1001 Communication Interface ControlBus
Module.
ZM7850A1001 Combustion System Manager™*.
203541 ControlBus 5-wire Electrical Connector.
S7810A1009 Data ControlBus™* Module.
221729A Dust Cover.
S7830A1015 Expanded Annunciator.
S7810M1003 ModBus Card.
Flame Simulators:
—203659 UV Flame Simulator.
—123514A Rectification Simulator.
S7800A1019 Keyboard Display Module.
203765 Remote Display Mounting Bracket.
203968A Remote Display Power Supply Plug-In.
S7820A1007 Remote Reset Module.
221818A Sixty-inch (1.52 meters) Extension Cable
Assembly.
221818C 120 inch (3.05 meters) Extension Cable
Assembly.
A7800A1002 Tester.
Plug-In Flame Signal Amplifiers Applicable Flame Detectors
Type Color
Self-
Checking Model
Flame
Failure
Response
Time Fuel Type Models
Rectificatio
n
Green No R7847A1041 3 sec. Gas Rectifying Flame
Rod Holdersa
C7004, C7007, C7011.
Complete Assemblies:
C7008, C7009, Q179.
Gas, oil,
coal
Ultraviolet (Purple
Peeper) C7012A,Cb.
Ultraviolet Purple R7849A1031 Gas, oil Ultraviolet
(Minipeeper) C7027, C7035, C7044b.
Device Initiate Standby Purge
Flame Establishing Period
Pilot Main
RM7895A 10 seconds * ** 4 or 10 seconds No
RM7895A RELAY MODULE
32-00122-01 4
*Registered Trademark of Honeywell International.
Fig. 1. Mounting dimensions of RM7895A Relay Module
and Q7800A Wiring Subbase in in. (mm).
Fig. 2. Rectification detectors.
POWER
BLOWER
FLAME
MAIN
ALARM
RESET
5
(127)
5 (127)]
M3529
5-1/4 (133)
REMOVE ONLY FOR TERMINAL TEST ACCESS.
1
1
BURNER CONTROL
R
MOUNTING FLANGE
1/2- 14 NPSM
LEADWIRES FACEPLATE
3/4-14 NPT
M1962B
3-3/4
(95)
7-7/32
(183)
5-1/8 (130)
3-7/16
(87)
5-1/4 (133)
C7012A,C,E,F
THREADED
MOUNTING
HOLES (2)
(10-32 UNF)
1 (25)
FLAME ROD
TARGET
CERAMIC
INSULATORS
IGNITION
ELECTRODE
(Q179C ONLY)
BRACKET
M1983A
3-1/8
(79)
1-21/32
(42)
1-13/32
(36)
3/8 (10)
1/2 (13)
1-1/16
(27)
25/32
(20)
25/32
(20)
2-25/32
(62)
3/32 (2) 11/16
(18)
17/32
(14)
RM7895A RELAY MODULE
532-00122-01
Fig. 3. Ultraviolet detectors.
PRINCIPAL TECHNICAL
FEATURES
The RM7895 provides all customary flame safeguard
functions while providing significant advancements in the
areas of safety, annunciation and system diagnostics.
Safety Shutdown (Lockout) Occurs
If:
1. INITIATE PERIOD
a. Purge card is not installed or is removed.
b. Purge card is bad.
c. Configuration jumpers have been changed after
200 hours of operation.
d. Ac line power errors occurred, see Operation.
e. Four minute INITIATE period has been exceeded.
2. STANDBY PERIOD
a. Flame signal is present after 40 seconds.
b. Ignition/pilot valve/intermittent pilot valve ter-
minal is energized.
c. Main valve terminal is energized.
d. Internal system fault occurred.
e. Purge card is not installed or is removed.
f. Purge card is bad.
3. PREPURGE PERIOD
a. Airflow lockout feature is enabled and the airflow
switch does not close after ten seconds or within
the specified purge card timing.
b. Flame signal is detected after 30 seconds.
c. Ignition/pilot valve/intermittent pilot valve ter-
minal is energized.
d. Main valve terminal is energized.
e. Internal system fault occurred.
f. Purge card is removed.\
g. Purge card is bad.
4. PILOT FLAME ESTABLISHING PERIOD (PFEP)
a. Airflow lockout feature is enabled and the airflow
switch opens.
b. Ignition/pilot valve terminal is not energized.
c. No flame present at end of PFEP.
d. Main valve terminal is energized.
e. Internal system fault occurred.
f. Purge card is removed.
g. Purge card is bad.
5. RUN PERIOD
a. No flame present.
b. Airflow lockout feature is enabled and the airflow
switch opens.
c. Main valve terminal is not energized.
d. Internal system fault occurred.
e. Purge card is remove.
f. Purge card is bad.
SAFETY PROVISIONS
Internal Hardware Status
Monitoring
The RM7895 checks the purge card for correct parity to
prevent purge timing shifts and circuitry failures. It also
analyzes the integrity of the configuration jumpers and
internal hardware. The POWER LED will blink every four
seconds, signifying an internal hardware check.
COLLAR WITH 1/2-14 NPSM
INTERNAL THREADS
4 (102) 8 FOOT (2.44 METER)
LEADWIRES (2)
M1943F
C7027A1064 HAS 24 FOOT (7.32 METER) LEADWIRES.
C7027A1114 HAS 44 IN. (1.118 M) LEADWIRES WITH
22 IN. (558 MM) FLEXIBLE CONDUIT.
1
2
2
3-1/2 (89)
1-1/16
(27)
1
MODELS AVAILABLE WITH SPUD CONNECTOR (1/2-14 NPSM INTERNAL
THREADS) INSTEAD OF CLAMP TYPE CONNECTOR.
1/2-14 NPSM
INTERNAL THREADS
2
2 (51)
COLLAR WITH
1 - 1-1/2 NPSM
INTERNAL
THREADS 1
1DIN APPROVED C7035A1064 HAS 1-11 BSP.P1 INTERNAL MOUNTING THREADS.
DIN APPROVED C7035A1064 HAS 1/2-14 BSP-F INTERNAL MOUNTING THREADS.
C7035A1056 HAS 12 FOOT (3.66 METER) LEADWIRES.
2
3
INSERTION DEPTH
6 FOOT
[1.83 METER]
LEADWIRES (2) 3
M1945D
2-5/8 (67)
1-1/2
(38)
31/32
(25)
4-1/8 (105)
1-3/16
(30)
6 FOOT [1.83 METER]
LEADWIRES (2) MOUNTING BRACKET
3-5/8 (92)
1/2
(13) 1-27/64
(36)
3/8
(10)
7/8
(22)
9/16
(14)
M1944B
RM7895A RELAY MODULE
32-00122-01 6
Closed Loop Logic Test
The test verifies the integrity of all safety critical loads,
terminals 8, 9, 10 and 21. If the loads are not energized
properly; i.e., the main valve terminal is powered during
PREPURGE, the RM7895 will lock out on safety shutdown.
The RM7895 must react to input changes but avoid the
occurrence of nuisance shutdown events. Signal
conditioning is applied to line voltage inputs to verify
proper operation in the presence of normal electrical line
noise such as transient high voltage spikes or short
periods of line drop out. Signal conditioning is tolerant of
synchronous noise (line noise events that occur at the
same time during each line cycle).
Dynamic Input Check
All system input circuits are examined to assure that the
RM7895 is capable of recognizing the true status of
external controls, limits and interlocks. If any input fails
this test, a safety shutdown occurs and the fault will be
annunciated.
Dynamic Safety Relay Test
Checks the ability of the dynamic safety relay contact to
open and close. Verifies that the safety critical loads,
terminals 8, 9, 10 and 21, can be de-energized, as
required, by the Dynamic Self-Check logic.
Dynamic Self-Check Safety Circuit
The microcomputer tests itself and related hardware, and
at the same time, the safety relay system tests the
microcomputer operation. If a microcomputer or safety
relay failure occurs and does not allow proper execution of
the
self-check routine, safety shutdown occurs and all safety
critical loads will be de-energized.
Expanded Safe-Start Check
The conventional safe-start check, which prevents burner
startup of flame is indicated at startup, is expanded to
include a flame signal check during STANDBY, an airflow
switch check and a safety critical load check.
Off Cycle (Standby or Prepurge)
Flame Signal Check
The flame detection subsystem (flame detector and
amplifier) is monitored during STANDBY. If a flame
simulating condition or an actual flame exists, a system
hold occurs and startup is prevented. If the flame signal
exists at any time after the first 40 seconds of STANDBY, a
safety shutdown occurs and is annunciated. A shutter-
check amplifier and self-checking detector are energized
for the first 40 seconds during STANDBY and the last two
seconds before exiting STANDBY. If a flame exists, a safety
shutdown occurs. A standard amplifier is energized
continually through STANDBY and PREPURGE; if a flame
exists, a safety shutdown occurs.
Tamper Resistant Timing and Logic
Safety and logic timings are inaccessible and cannot be
altered or defeated.
Verified Spark Termination
The ignition terminal is monitored to assure early spark
termination (ten seconds ignition and pilot and ten
seconds pilot and main only).
First-Out Annunciation and Self-
Diagnostics
Sequence Status Lights (LEDs) provide positive visual
indication of the program sequence: POWER, PILOT,
FLAME, MAIN and ALARM. The green POWER LED blinks
every four seconds, signifying that the RM7895 hardware
is running correctly.
Optional multi-function Keyboard Display Module shows
elapsed time during PREPURGE, PILOT IGN and MAIN
IGN. As an additional troubleshooting aid, it provides
sequence timing, diagnostic information, historical
information and expanded annunciator information when
a safety shutdown or hold or normal operation occurs.
First-Out Annunciation reports the cause of a safety
shutdown or identifies the cause of a failure to start or
continue the burner control sequence with an English text
and numbered code via the optional Keyboard Display
Module. It monitors all field input circuits, including the
flame signal amplifier. The system distinguishes 43
modes of failure and detects and annunciates difficult-to-
find intermittent failures.
Self-Diagnostics add to the First-Out Annunciation by
allowing the RM7895 to distinguish between field
(external device) and internal (system related) problems.
Faults associated within the flame detection subsystem,
RM7895 or Plug-in Purge Card are isolated and reported
by the optional Keyboard Display Module. See the 7800
SERIES System Annunciation Diagnostics and
Troubleshooting, Form 65-0233.
Interlock Requirements
The following interlock input is provided:
Airflow Switch Interlock
This interlock is typically connected to an airflow switch.
The Airflow Interlock (ILK) input must close ten seconds
into PREPURGE or within the specified purge card timing;
otherwise, a recycle to the beginning of PREPURGE or
lockout will occur, depending on how the airflow switch
selectable jumper is configured (see Table 6).
RM7895A RELAY MODULE
732-00122-01
INSTALLATION
WARNING
Fire or Explosion Hazard.
Can cause severe injury, death or property
damage.
To prevent possible hazardous burner operation,
verification of safety requirements must be
performed each time a control is installed on a
burner.
When Installing This Product…
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a
hazardous condition.
2. Check the ratings given in the instructions and
marked on the product to make sure the product is
suitable for your application.
3. Installer must be a trained, experienced, flame
safeguard service technician.
4. After installation is complete, check out the product
operation as provided in these instructions.
WARNING
Electrical Shock Hazard.
Can cause severe injury, death or property
damage.
Disconnect the power supply before beginning
installation to prevent electrical shock and
equipment damage. More than one power supply
disconnect may be involved.
1. Wiring connections for the RM7895 are unique;
therefore, refer to Fig. 5 or the correct Specifications
for proper subbase wiring.
2. Wiring must comply with all applicable codes,
ordinances and regulations.
3. Wiring, where required, must comply with NEC Class
1 (Line Voltage) wiring.
4. Loads connected to the RM7895 must not exceed
those listed on the RM7895 label or the Specifica-
tions, see Table 1.
5. Limits and interlocks must be rated to carry and
break current simultaneously to the ignition trans-
former, pilot valve, and main fuel valve(s).
6. All external timers must be listed or component
recognized by authorities who have jurisdiction for
the specific purpose for which they are used.
IMPORTANT
1. For on-off gas-fired systems, some authorities
who have jurisdiction prohibit the wiring of any
limit or operating contacts in series between the
flame safeguard control and the main fuel valve(s).
2. Two flame detectors can be connected in parallel.
3. This equipment generates, uses and can radiate
radio frequency energy and, if not installed and
used in accordance with the instructions, may
cause interference to radio communications. It
has been tested and found to comply with the
limits for a Class B computing device of part 15 of
FCC rules, which are designed to provide
reasonable protection against such interference
when operated in a commercial environment.
Operation of this equipment in a residential area
may cause interference; in which case, the user, at
their own expense, may be required to take
whatever measures are required to correct this
interference.
4. This digital apparatus does not exceed the Class B
limits for radio noise of digital apparatus set out in
the Radio Interference Regulations of the Cana-
dian Department of Communications.
Humidity
Install the RM7895 where the relative humidity (RH) never
reaches the saturation point. The RM7895 is designed to
operate in a maximum 85 percent RH continuous,
noncondensing, moisture environment. Condensing
moisture may cause a safety shutdown.
Vibration
Do not install the RM7895 where it could be subjected to
vibration in excess of 0.5G continuous maximum
vibration.
Weather
The RM7895 is not designed to be weather tight. If
installed outdoors, the RM7895 must be protected by an
approved, weather-tight, enclosure.
Mounting Wiring Subbase
NOTE: For installation dimensions, see Fig. 1.
1. Mount the subbase in any position except
horizontally with the bifurcated contacts pointing
down. The standard vertical position is
recommended. Any other position decreases the
maximum ambient temperature rating.
2. Select a location on a wall, burner or electrical panel.
The Q7800 can be mounted directly in the control
cabinet. Be sure to allow adequate clearance for
servicing, installation, access and removal of the
RM7895, Dust Cover, flame amplifier, flame
amplifier signal voltage probes, electrical signal
voltage probes and electrical field connections.
RM7895A RELAY MODULE
32-00122-01 8
3. For surface mounting, use the back of the subbase
as a template to mark the four screw locations. Drill
the pilot holes.
4. Securely mount the subbase using four no. 6 screws.
Fig. 4. Internal block diagram of the RM7895 (see Fig. 6 for detailed wiring instructions).
WIRING
IMPORTANT
For proper subbase wiring, refer to Fig. 5.
For proper remote wiring of the Keyboard Display
Module, refer to the Specifications for the Key-
board Display Module (form 65-0144), Communi-
cations Interface Base Unit (63-2278), Data
ControlBus™ Module (65-0091) or Extension
Cable Assembly
(65-0131).
NOTE: Part number 203541 5-Wire Connector (order
separately) is required except when using the
extension cable assembly.
WARNING
Electrical Shock Hazard.
Can cause severe injury, death or property
damage.
Disconnect the power supply before beginning
installation to prevent electrical shock or
equipment and control damage. More than one
power supply disconnect may be required.
1. For proper remote wiring of the Keyboard Display
Module, refer to the Specifications for the Keyboard
Display Module (65-0144), Communication Inter-
face Base Unit (63-2278), Data ControlBus™ Module
(65-0091) or Extension Cable Assembly (65-0131).
2. Disconnect the power supply from the main discon-
nect before beginning installation to prevent electri-
cal shock and equipment damage. More than one
disconnect may be involved.
3. All wiring must comply with applicable electrical
codes, ordinances and regulations. Wiring, where
required, must comply with NEC Class 1 (Line Volt-
age) wiring.
4. Recommended wire size and type: see Table 4.
5. Recommended grounding practices: see Table 5.
6. The Keyboard Display Module, Data ControlBus™
Module (for remote mounting or communications)
or Communication Interface ControlBus Module
must be wired in a daisy chain configuration, (1(a)-
1(a),
2(b)-2(b), 3(c)-3(c)). The order of interconnection of
all the devices listed above is not important. Be
aware that modules on the closes and farthest end
of the daisy chain configuration string require a
120-ohm, 1/4 watt minimum, resistor termination
across terminals 1 and 2 of the electrical connectors,
for connections over 100 feet. Recommended wire
routing of leadwires:
CONFIGURATION
JUMPERS
MICROCOMPUTER
RESET
PUSHBUTTON
RUN/TEST
SWITCH
STATUS LEDs
PLUG-IN PURGE
TIMER CARD
SAFETY RELAY
CIRCUIT
POWER SUPPLY
OPTIONAL KEYBOARD
DISPLAY MODULE
PLUG-IN
FLAME
AMPLIFIER
RELAY
DRIVE
CIRCUIT
CONTROL
POWER
TEST
JACK
REMOTE
RESET
DDL
DDL
COMMUNICATIONS
INDICATES FEEDBACK SENSING
TO RELAY STATUS FEEDBACK
AND LINE VOLT INPUTS
FIELD WIRING
INTERNAL WIRING
IGNITION
PILOT
MAIN VALVE
1K
RELAY
STATUS
FEEDBACK
AND LINE
VOLTAGE
INPUTS
LIMITS CONTROLLER LOCKOUT
INTERLOCK
(INCLUDING
AIRFLOW SWITCH)
1K1 2K1 5K1
FLAME SIGNAL
TEST
PROVIDE DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQUIRED.
RS485
1
2
3
L1
(HOT)
L2
5
67
4K1
2K2
10
8
9
7K
6K
5K
4K
3K
2K
F
G
22
1
BLOWER
6K1
4
ALARM
3K1
3
L2
M5110G
1
RM7895, RM7896: 120 VAC, 50/60 HZ.
EC7895A,C: 220-240 VAC, 50/60 HZ.
RM7895A RELAY MODULE
932-00122-01
a. Do not run high voltage ignition transformer
wires in the same conduit with the flame
detector, Data ControlBus™ Module, or Remote
Reset Module wiring.
b. Do not route flame detector, Data ControlBus™
Module, or Remote Reset Module leadwires in
conduit with line voltage circuits.
c. Enclose flame detector leadwires without armor
cable in metal cable or conduit.
d. Follow directions in flame detector, Data
ControlBus™ Module, or Remote Reset Module
Instructions.
7. Keyboard Display Module (KDM): Because the KDM
is powered from a low voltage, energy limited,
source, it can be mounted outside of a control panel
if it is protected from mechanical damage.
NOTE: A 13 Vdc power supply must be used any time
more than one KDM is used.
8. Maximum wire lengths follow:
a. RM7895—The maximum length of leadwire is
300 feet to terminal inputs (Control, Preignition
Interlock, Running/Lockout Interlock, High Fire
Switch and Low Fire Switch).
b. Flame Detector leadwires—The maximum flame
sensor leadwire length is limited by the flame
signal strength.
c. Remote Reset leadwires—The maximum length
of wire is 1000 feet to a Remote Reset push but-
ton.
d. Data ControlBus™ Module—The maximum Data
ControlBus™ Module cable length depends on
the number of system modules connected, the
noise conditions and the cable used. The maxi-
mum length of all Data ControlBus™ Module
interconnecting wire is 4000 feet.
9. Make sure loads do not exceed the terminal ratings.
Refer to the label on the RM7895 or to the ratings in
Table 1.
Final Wiring Check
1. Check the power supply circuit. The voltage and
frequency tolerance must match those of the
RM7895. A separate power supply circuit may be
required for the RM7895. Add the required
disconnect means and overload protection.
2. Check all wiring circuits and complete the Static
Checkout, see Table 7, before installing the RM7895
on the subbase.
3. Install all electrical connectors.
4. Restore power to the panel.
Table 4. Recommended Wire Sizes and Part Numbers.
Table 5. Recommended Grounding Practices.
Application Recommended Wire Size Recommended Part Number(s)
Line voltage terminals 14, 16 or 18 AWG copper conductor,
600 volt insulation, moisture-resistant
wire.
TTW60C, THW75C, THHN90C.
Keyboard Display Module (KDM) 22 AWG two-wire twisted pair with
ground, or five wire.
Belden 8723 shielded cable or
equivalent.
Data ControlBus™ Module
Remote Reset Module 22 AWG two-wire twisted pair,
insulated for low voltage.
—
Communications Interface
ControlBus™ Module
22 AWG two-wire twisted pair with
ground.
Belden 8723 shielded cable or
equivalent.
13 Vdc full-wave rectified transformer
power input
18 AWG wire insulated for voltages and
temperatures for given application.
TTW60C, THW75C, THHN90C.
Ground Type Recommended Practice
Earth Ground (subbase and relay module). 1. Use to provide a connection between the subbase and
the control panel of the equipment. Earth ground
must be capable of conducting enough current to
blow the 15A fuse (or breaker) in the event of an inter-
nal short circuit.
2. Use wide straps or brackets to provide minimum
length, maximum surface area ground conductors. If
a leadwire must be used, use 14 AWG copper wire.
3. Make sure that mechanically tightened joints along
the ground path are free of nonconductive coatings
and protected against corrosion on mating surfaces.
Signal ground (KDM, Data ControlBus™ Module,
Communications Interface ControlBus™ Module).
Use the shield of the signal wire to ground the device to the
signal ground terminal [3(c)] of each device. Connect the
shield at both ends of the chain to earth ground.
RM7895A RELAY MODULE
32-00122-01 10
Fig. 5. Wiring the RM7895A Relay Module.
ASSEMBLY
Mounting RM7895
NOTE: For installation dimensions, see Fig. 1.
Relay Module Mounting
1. Mount the RM7895 vertically (see Fig. 7) or mount
horizontally with the knife blade terminals pointing
downward. When mounted on the Q7800A, the
RM7895 must be in an electrical enclosure. See Fig.
6.
2. Select the location in an electrical enclosure. Be sure
to allow adequate clearance for servicing, installa-
tion and removal of the RM7895, Dust Cover, flame
amplifier, flame amplifier signal probes, electrical
signal voltage probes and electrical connections.
M3536B
G
L2
3
4
5
6
7
8
9
10
F
(L1)
13
14
15
16
17
18
19
20
21
22
12
AIR FLOW INTERLOCK
MASTER
SWITCH
IGNITION
MAIN FUEL VALVE(S)
BURNER
CONTROLLER/LIMITS
BURNER MOTOR
(BLOWER)
120V ALARM
INTERRUPTED
PILOT/IGNITION
RECTIFYING FLAME
ROD
FLAME DETECTOR
C7027A, C7035A, OR
C7044A ULTRAVIOLET
FLAME DETECTOR
C7012A,C, ULTRAVIOLET
FLAME DETECTOR
120V, 50/60 Hz POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
DO NOT WIRE TO ANY UNUSED TERMINALS.
FOR DIRECT SPARK IGNITION
(OIL OR GAS)
IGNITION
TRANSFORMER
MAIN VALVE
L1
(HOT)
L2 1
OR
OR
BLUE
BLUE
WHITE
YELLOW
L2
WHITE
WHITE
BLACK
BLACK
L1
L2
8
10
L2
Q7800
2
1
2