G3 RioExpress User manual

Wireless Cable
Replacement
Analog &
Digital I/O
Analog &
Digital I/O
RioExpress Quick Start Guide
Thank you for purchasing the RioExpress specialty Wireless I/O.
Step 1: Set one unit as the Master. Note that the units are identical, and come with the same
default DIP Switch settings. Pick one unit to be the Master and move the upper left DIP switch (S4-1) to the
“Master” position. See Figure 1 & 2 below for proper settings.
Step 2: Attach whip antenna to each unit.
Step 3: Apply power to both units. They configure themselves, then within a couple of seconds are
communicating with each other.
The RioExpress units are now replicating (mirroring) I/O signals from one unit to the other.
... It’s that simple!
Figures 1 & 2 below show the typical DIP Switch settings for simple Cable Replacement as described above.
Figure 2 shows the factory default settings (Slave), and Figure 1 shows the upper-left DIP Switch S4-1) set for
Master function.
This quick start guide describes the simple
steps 1-2-3 for using a pair of RioExpress modules to replicate (mirror) I/O signals for cable replacement.
Note: See back for information about exercising the RioExpress features, and exploring various setup options.
for Cable Replacement Pair
Model G308
- Vx
MASTERSLAVE POLL RATE
12V 24V
( )
RF NET 0-6
- I/O PWR SAVE
ON
OFF
1
2SEE CHART
SUM OF
VALUES
1
2
4
1
2
4
8
16
32
SLAVE ADDR
SUM OF VALUES
AO -
DO - HOLD ZERO
OFFHOLD
COMM FAIL
( )
1-63
Figure 1: Master Unit Settings
- Vx
MASTERSLAVE POLL RATE
12V 24V
( )
RF NET 0-6
- I/O PWR SAVE
ONOFF
1
2SEE CHART
SUM OF
VALUES
1
2
4
1
2
4
8
16
32
SLAVE ADDR
SUM OF VALUES
AO -
DO - HOLD ZERO
OFFHOLD
COMM FAIL
( )
1-63
Figure 2: Slave Unit Settings (factory default)
O
N
12345678
S4
O
N
12345678
S4
O
N
12345678
S1
O
N
12345678
S1
1
G3 Technologies, Inc.
Ph 913-963-7300
E-Mail: [email protected] Web site: www.g3ti.com
P/N G308-04-E2: Cable Replacement Starter Kit:
Includes: 2 ea. G308-04 RioExpress Wireless I/O, 900MHz
2 ea. Whip Antennas, articulating
2 ea. Wall Cube Power Supplies, 12Vdc
1 ea. RioExpress Quick Start Guide
1 ea. RioExpress User’s Guide
(For 2.4GHz frequency, order P/N G308-08E2)
For Sales and Support contact G3 Technologies
G308 Quick Start Guide CR (2016-03-17)
O
Or
rd
de
er
r
f
fr
ro
om
m:
:
C
C
A
A
B
Br
ri
ig
gg
gs
s
C
Co
om
mp
pa
an
ny
y
622 Mary Street; Suite 101; Warminster, PA 18974
Phone: 267-673-8117 - Fax: 267-673-8118
Sales@cabriggs.com - www.cabriggs.com

I/O Signals
The inputs of one unit are replicated as the outputs of the other. On the MASTER unit connect a jumper wire
from DI1 to GND. The DI1 LED on the MASTER unit will turn on and the DO1 on the SLAVE unit will turn on a
fraction of a second later. The units are shipped with the Analog Inputs set to 0-20mA (4-20mA). Use a 4-20mA
current generator to input an analog signal on AI1 of the MASTER or SLAVE unit. You can measure the
corresponding current output signal on the IO1 of the other unit. The VO1 on the other unit will also output a
corresponding 0-5V (1-5V) signal. If you desire to use a 0-5V (1-5V) input signal, remove the cover and select
the 0-5V input on the Analog Input selection DIP switch. To remove the cover, power off the unit, remove the
four screws on the top of the cover and lift off the cover vertically.
LED Indicators
After applying power on each unit, the CPU LED will be on solid for one second. The TX1 and RX1 LEDs will
then blink as the radio is configured. The CPU LED will then blink once per second. When the Master unit is
powered up, it will transmit a message to the Slave unit and the Slave unit will reply (about four times per
second). This is indicated by the blinking of the TX1 and RX1 LEDs. With the units in the same room, all three
of the Received Signal Strength Indicator (RSSI) green LEDs should be on indicating a strong RF signal.
LED Enable Push Button
Except for the CPU LED, the LEDs will time out after 30 minutes and turn off to conserve energy. If the LEDs
time out, press the LED enable push button next to the CPU LED to enable the LEDs for another 30 minutes.
Repeatedly pressing the LED enable push button will toggle the LEDs on and off.
Communications Failure Action
To demonstrate the Comm Fail Action, power down one of the units and observe the comm fail action on the
other. With the continuous poll rate setting (default) the powered unit will time out after 20 seconds. When the
Comm Fail timeout occurs, the DO5 Comm. Fail output will turn on. With the COMM FAIL AO and DO set to
ZERO and OFF respectively, the analog outputs will go to zero, and the relay outputs will turn off when Comm
Fail occurs. When both units are again powered, communications will be restored and Comm Fail will clear.
Low Power Application Settings
The RioExpress has a variety of settings that allow the user to balance power savings and system performance
in order to minimize cost and still meet system requirements. For ultra-low power usage (<100mW average)
consider the configuration settings depicted in Figures 3 and 4.
In this configuration the POLL RATE is set for once every minute and I/O PWR SAVE is turned on. The
MASTER will poll the SLAVE, then both units will enter Power Save Mode for 58 seconds, then power-up 2
seconds before the MASTER polls the SLAVE again. While in Power Save Mode the radio, sensor excitation
voltage and digital input wetting voltage will be turned off. When using this configuration in a monitoring
application, the RioExpress could use as small as a 1W solar panel and a 2AHr battery.
Note that the Poll Rate settings on the SLAVE define a “hold” time for the Digital Inputs, allowing the capture of
short-duration events even with a slow poll rate.
Refer to the RioExpress User’s Guide for more information, including information needed to use the RioExpress
as a Modbus Slave Wireless I/O device.
- Vx
MASTERSLAVE POLL RATE
12V 24V
( )
RF NET 0-6
- I/O PWR SAVE
ON
OFF
1
2SEE CHART
SUM OF
VALUES
1
2
4
1
2
4
8
16
32
SLAVE ADDR
SUM OF VALUES
AO -
DO - HOLD ZERO
OFFHOLD
COMM FAIL
( )
1-63
Figure 3: Master, Ultra-Low Power
- Vx
MASTERSLAVE POLL RATE
12V 24V
( )
RF NET 0-6
- I/O PWR SAVE
ONOFF
1
2SEE CHART
SUM OF
VALUES
1
2
4
1
2
4
8
16
32
SLAVE ADDR
SUM OF VALUES
AO -
DO - HOLD ZERO
OFFHOLD
COMM FAIL
( )
1-63
Figure 4: Slave, Ultra-Low Power
O
N
123456 7 8
S4
O
N
12345678
S4
O
N
12345678
S1
O
N
12345678
S1
2
G308 Quick Start Guide CR (2016-03-17)
This manual suits for next models
1
Popular I/O System manuals by other brands

Siemens
Siemens SIMATIC ET 200SP manual

Allen-Bradley
Allen-Bradley ControlLogix 1756-IG16 installation instructions

Mini-Circuits
Mini-Circuits USB-I/O-16D8R User & programming guide

Technosoft
Technosoft IO iMOTIONCUBE CAN Technical reference

M-system
M-system R7L-EA16 instruction manual

National Instruments
National Instruments PCIe-6374 SAFETY, ENVIRONMENTAL, AND REGULATORY INFORMATION