SCE-SS and RCE-SS CS-2466 09/01/06 Page 1 of 4
SCE-SS and RCE-SS
Addressable Control and Relay Modules
SCE-SS Module
(See wiring diagram Fig. 5 for RCE-SS)
Description
SCE-SS Control Module — The SCE-SS
Addressable SmartScan™ Control Module
provides Gamewell intelligent control pan-
els a circuit for Notification Appliances
(horns, strobes, speakers, etc.) or to moni-
toratelephonecircuit.Addressabilityallows
the SCE-SS to be activated, either manu-
ally or through panel programming, on a
select (zone or area of coverage) basis.
RCE-SS Relay Module — The RCE-SS
Addressable Relay Module provides the
system with a dry-contact output for acti-
vating a variety of auxiliary devices, such
asfans, dampers,control equipment,etc.
Addressability allows the dry contact to
be activated, either manually or through
panel programming, on a select basis.
Applications
The SCE-SS is used to switch 24 VDC audible/visual power, high-level audio (speak-
ers), or control telephone devices. The RCE-SS may be programmed to operate dry
contacts for door holders, Air Handling Unit shutdown, etc., and to reset four-wire
smoke detector power.
Construction
• The face plate is made of off-white Noryl®.
• Controls include two rotary switches for direct-dial entry of address (01-99).
• The SCE-SS is configured for a single Class B (Style Y) or Class A (Style Z)
Notification Appliance Circuit.
• The RCE-SS provides two Form-C dry contacts that switch together.
Operation
Each SCE-SS or RCE-SS uses one of 99 possible module addresses on a SLC loop.
It responds to regular polls from the control panel and reports its type and status,
including the open/normal/short status of its NotificationAppliance Circuit (NAC). The
LED blinks with each poll received. On command, it activates its internal relay. The
SCE-SS supervises Class B (Style Y) or Class A (Style Z) notification or control cir-
cuits.
Upon code command from the panel, the SCE-SS will disconnect the supervision and
connect the external power supply in the proper polarity across the load device. The
disconnection of the supervision provides a positive indication to the panel that the
control relay actually turned ON. The external power supply is always relay isolated
from the communication loop so that a trouble condition on the external power supply
will never interfere with the rest of the system.
Rotary switches set a unique address for each module. The address may be set be-
fore or after mounting. The built-in TYPE CODE (not settable) will identify the module
to the control panel, so as to differentiate between a module and a sensor address.
• Built-in type identification
automatically identifies these
devices to the control panel.
• Internal circuitry and relay
powered directly by two-wire
SLC loop. The SCE-SS module
requires power (for horns,
strobes, etc.), audio (for speak-
ers), or a telephone riser (for
handsets). Internal relay feature
available on SmartScan™
systems only.
• Use with IF602, 610, 632, 654
and 658.
• Integral LED “blinks” green each
time a communication is
received from the control panel
and turns on in steady red when
activated.
• LED blink may be deselected
globally (affects all devices).
• High noise immunity (EMF/RFI).
• The SCE-SS may be used to
switch 24-volt NAC power, audio
(up to 70.7 VRMS) or telephone.
• Wide viewing angle of LED.
• SEMS screws with clamping
plates for wiring ease.
• Direct-dial entry of address 01–
99 for SmartScan™.
• Speaker, audible/visual, and
telephone applications may be
wired for Class B or A (Style Y or
Z).
Listings
Listings and approvals below
apply to the SCE-SS & RCE-SS
Series Addressable Control and
Relay Modules. In some cases,
certain modules may not be
listed by certain approval
agencies, or listing may be in
process. Consult factory for
latest listing status.
• UL Listed: file S521.
• CSFM approved:
file 7300-1288:171.
Features
TENS
ONES
SmartScan™ is a trademark of Gamewell.
6724mod2.tif
SCE-SS and RCE-SS CS-2466 09/01/06Page 2 of 4
Specifications for SCE-SS
Normal operating voltage: 15 to 32
VDC.
Maximum current draw:6.5mA(LED
on).
Average operating current: 375 µA
group poll (SmartScan™ mode) with
LED flashing.
External supply voltage (between
Terminals T3 and T4): maximum 80
volts (RMS or DC).
Drain on external supply: 2mA maxi-
mum (using internal EOL relay).
EOL resistance: 47K ohms.
Temperature range: 32°F to 120°F
(0°C to 49°C).
Humidity range: 10% to 93% non-
condensing.
Dimensions: 4.5" (11.43 cm) high x
4" (10.16 cm) wide x 1.25" (3.175 cm)
deep. Mounts to a 4" (10.16 cm)
square x 2.125" (5.398 cm) deep box.
Specifications for RCE-SS
Normal operating voltage: 15 to 32
VDC.
Maximum current draw:6.5mA(LED
on).
Average operating current: 255 µA
group poll (SmartScan™ mode) with
LED flashing.
EOL resistance: not used.
Temperature range: 32°F to 120°F
(0°C to 49°C).
Humidity range: 10% to 93% non-
condensing.
Dimensions: 4.5" (11.43 cm) high x
4" (10.16 cm) wide x 1.25" (3.175 cm)
deep. Mounts to a 4" (10.16 cm)
square x 2.125" (5.398 cm) deep box.
Normal operating voltage: 15 to 32
VDC.
Maximum current draw:6.5mA(LED
on).
Average operating current: 255 µA
group poll (SmartScan™ mode) with
LED flashing.
EOL resistance: not used.
Temperature range: 32°F to 120°F
(0°C to 49°C).
Humidity range: 10% to 93% non-
condensing.
Dimensions: 4.5" (11.43 cm) high x
4" (10.16 cm) wide x 1.25" (3.175 cm)
deep. Mounts to a 4" (10.16 cm)
square x 2.125" (5.398 cm) deep box.
Product Line Information
SCE-SS Intelligent Addressable Control Module.
RCE-SS Intelligent Addressable Relay Module.
A2143-20 Capacitor, required for Class A (Style Z) operation of speakers.
SMB500 Optional Surface-Mount Backbox.
CB500 Control Module Barrier — required by UL for separating power-limited
and non-power-limited wiring in the same junction box as SCE-SS-1.
Relay Contact Ratings for both SCE-SS and RCE-SS models
Mounting Diagrams
Note CB500 Module Barrier,
which creates isolated quadrant.
Load Description Application Maximum
Voltage Current
Rating
Resistive Non-coded 30VDC 3.0A
Resistive Coded 30VDC 2.0A
Resistive Non-coded 110 VDC 0.9 A
Resistive Non-coded 125 VAC 0.9 A
Inductive (L/R= 5 ms) Coded 30 VDC 0.5 A
Inductive (L/R= 2 ms) Coded 30 VDC 1.0 A
Inductive (PF = 0.35) Non-coded 125 VAC 0.5 A
6724mt2.wmf
6724mt1.wmf
SCE-SS and RCE-SS CS-2466 09/01/06 Page 3 of 4
Wiring Diagrams
The following wiring diagrams are provided:
1) SCE-SS: Typical notification appliance circuit configuration, NFPA Style Y.
2) SCE-SS: Typical fault-tolerant notification appliance circuit configuration, NFPA Style Z.
3) SCE-SS: Typical wiring for speaker supervision and switching, NFPA Style Y.
4) SCE-SS: Typical fault-tolerant wiring for speaker supervision and switching, NFPA Style Z.
5) RCE-SS: Relay module wiring diagram.
Fig. 1 SCE-SS: Typical notification appliance circuit configuration, NFPA Style Y.
Fig. 2 SCE-SS: Typical fault-tolerant notification appliance circuit configuration, NFPA Style Z.
• Connect modules to Listed compatible Gamewell control panels only.
• All wiring shown is supervised and power limited.
• Module polarities are shown in alarm.
• Connect modules to Listed compatible Gamewell control panels only.
• All wiring shown is supervised and power limited.
• Module polarities are shown in alarm.
6827wir1.wmf
6827wir2.wmf
SCE-SS and RCE-SS CS-2466 09/01/06
Page 4 of 4
Gamewell-FCI
12 Clintonville Road
Northford, CT 06472-1610
Phone:203-484-7161
Fax: 203-484-7118
www.gamewell-fci.com
AHoneywell Company
© 2006 Gamewell-FCI
Specifications and wiring information are provided for information only and are believed
to be accurate. Gamewell-FCI assumes no responsibility for their use.
Dataanddesignare subjectto change without notice.Installationand wiring instructions
shipped with the product shall always be used for actual installation. For more
information, contact Gamewell-FCI.
Fig. 3 SCE-SS: Typical wiring for speaker supervision and switching, NFPA Style Y.
• Connect modules to Listed compatible
Gamewell control panels only.
• All wiring shown is supervised.
• Wires must be supervised per NFPA.
• Module polarities are shown in alarm.
Fig. 4 SCE-SS: Typical fault-tolerant wiring for speaker supervision and switching, NFPA Style Z.
• Connect modules to Listed compatible Gamewell control panels only.
• All wiring shown is supervised.
• Wires must be supervised per NFPA.
• Module polarities are shown in alarm.
6724wir3.wmf
6724wir4.wmf
NOTE regarding
AUDIO AMPLIFIER in
Figures 3 & 4:
1) Audio circuit wiring
must be twisted-pair as a
minimum. See Gamewell
installation manual for
detailed information.
Fig. 5 RCE-SS:
Relay module wiring
diagram.
• Connect modules to Listed
compatible Gamewell
control panels only.
• Module does NOT supervise
controlled circuits.
6724wir5.wmf

This manual suits for next models

1

Popular Relay manuals by other brands

Immergas 3.031943 quick start guide

Immergas

Immergas 3.031943 quick start guide

Basler BE1-50/51B-232 instruction manual

Basler

Basler BE1-50/51B-232 instruction manual

Crydom DC60 Series Installation sheet

Crydom

Crydom DC60 Series Installation sheet

ABB SPAJ 111 C user manual

ABB

ABB SPAJ 111 C user manual

ABB SPAU 140 C User manual and technical description

ABB

ABB SPAU 140 C User manual and technical description

ABB RELION REF615R Engineering manual

ABB

ABB RELION REF615R Engineering manual

Pilz PNOZ mmc7p CC operating manual

Pilz

Pilz PNOZ mmc7p CC operating manual

Pilz PST 4 operating manual

Pilz

Pilz PST 4 operating manual

Pilz PNOZ 2VQ operating instructions

Pilz

Pilz PNOZ 2VQ operating instructions

Pilz PNOZ Ex operating instructions

Pilz

Pilz PNOZ Ex operating instructions

Siemens SIRIUS 3RF23 0 Series Original operating instructions

Siemens

Siemens SIRIUS 3RF23 0 Series Original operating instructions

New Elec KB LV manual

New Elec

New Elec KB LV manual

CD Automation Revo Sx user manual

CD Automation

CD Automation Revo Sx user manual

Thytronic DTB 49-50 instruction manual

Thytronic

Thytronic DTB 49-50 instruction manual

Westinghouse SBF-1 Installation, operation & maintenance instructions

Westinghouse

Westinghouse SBF-1 Installation, operation & maintenance instructions

Omron K8AB-PM Series manual

Omron

Omron K8AB-PM Series manual

Busch-Jaeger 6711 UBT product manual

Busch-Jaeger

Busch-Jaeger 6711 UBT product manual

Rockwell Automation Allen-Bradley Guardmaster Minotaur MSR117T installation instructions

Rockwell Automation

Rockwell Automation Allen-Bradley Guardmaster Minotaur MSR117T installation instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.