GAYLORD ELX SERIES User manual

i
10900 S.W. AVERY STREET - TUALATIN, OREGON 97062 U.S.A.
www.gaylordvenlaon.com
Rev 05
OPERATION, MAINTENANCE
& INSTALLATION MANUAL
For
“ELX” And “ELX-UVi” SERIES
VENTILATORS
GAYLORD INDUSTRIES

ii
All rights reserved. No part of this book may be reproduced, stored in a retriev-
al system, or transmied in any form by an electronic, mechanical, photocopy-
ing, recording means or otherwise without prior wrien permission of Gaylord
Industries.
©Copyright 2012, Gaylord Industries
The manufacturer reserves the right to modify the materials and
specicaons resulng from a connuing program of product
improvement or the availability of new materials
Addional Copies $25.00 Each

iii
Gaylord Industries
10900 SW Avery St.
Tualatin, OR 97062
Office: 503.691.2010
Toll Free: 800.547.9696
www.gaylordventilation.com
Gaylord Industries 10900 SW Avery Street Tualatin, OR 97062 www.gaylordventilation.com
To Our Customers:
Congratulations on your recent purchase of a Gaylord Model ELX Series Ventilator. We are
proud to be able to provide you with a quality product that exemplifies our long standing
dedication to quality engineering and manufacturing.
Your Gaylord Ventilator is assembled from some to the very finest components available and
is designed for years of efficient, effective, and trouble-free operation. In addition, the product
has undergone rigorous quality control inspections and testing prior to shipment.
If you have any questions, please contact us at info@gaylordventilation.com or by calling us
toll free 800-547-9696. We are more than happy to help.
Sincerely,
Gaylord Industries

iv
Page iv
This Page Intenonally Le Blank

v
Page v
Table of Contents
Chapter 1 – Introducon
Introducon ..……………………………………………………………………………………………………………………. 1-1
Model Descripon …………………………………………………………………………………………………………….. 1-2
Model Number Explanaon ………………………………………………………………………………………………. 1-3
Chapter 2 – Principles of Operaon
EL and ELX Series
Turning on the Exhaust Fan ………....................................................................................... 2-1
Turning o the Exhaust Fan ………………….…….…………………………………………………………………… 2-2
Cleaning the Venlator ……………………………………………………………………………………………………… 2-3
Fire Protecon …………………………………………………………………………………………………………………… 2-3
ELX-UVi Series
Turning on the Exhaust Fan and UV System ……...................................................................... 2-5
Turning o the Exhaust Fan and UV System ..…………………………………………………………………….. 2-9
Cleaning the Venlator ……………………………………………………………………………………………………… 2-9
Fire Protecon …………………………………………………………………………………………………………………… 2-10
Oponal Balancer Dampers ………………………………………………………………………………………………. 2-12
Chapter 3 - Maintenance
Operator Cleaning and Maintenance Instrucons ……………................................................... 3-1
UV System - Scheduled Prevenve Maintenance ……………………………………………………………… 3-4
Recommended Detergent for Cleaning ................................................................................. 3-7
Chapter 4 - Troubleshoong
Trouble Shoong ……………………………………………………………………………………………………………… 4-1
Chapter 5 – Tesng and Repair
Measuring Airow .................................................................................................................. 5-1
Make-Up Air Guidelines ……………………………………………………………………………………………………. 5-11
Replacing UV Lamps ............................................................................................................... 5-13
Replacing UV Lamp Sockets .................................................................................................. 5-16
UV Ballast Box – Replacing Ballast ........................................................................................ 5-20
UV Ballast Box – Replacing Ballast Boards .............................................................................. 5-21
UV Ballast Box – Replacing UV Venlaon Control Board ...................................................... 5-21
UV Ballast Box – Replacing Venlaon Fan ............................................................................ 5-22
UV Ballast Box – Pressure Switches - Overview e.................................................................... 5-22
UV Ballast Box – Seng Pressure Switches ............................................................................ 5-23
UV Ballast Box – High Temperature Shutdown Controller ..................................................... 5-26

vi
Page vi
Table of Contents – Cont.
Chapter 6 - Parts
Parts - Venlator ..................................................................................................................... 6-1
Parts – UV Venlator …………………………………………………………………………………………………………. 6-4
Parts – UV Lamp Module …………………………………………………………………………………………………… 6-5
Parts – UV Ballast Box ……………………………………………………………………………………………………….. 6-7
Chapter 7 – Wiring Diagrams
Wiring Diagrams ……………………………………………………………………………………………………………….. 7-1
Appendices
Installaon Requirements …………………………………………………………………………………………………. A-1
Venlator Start-Up Inspecon and Tests ………………………………………………………………………...... B-1

1-1
Chapter 1 - Introducon, Page 1-1
Introducon
About this Technical Manual
The purpose of this manual is to provide the Operator, Maintenance and Service personnel instrucons for
operang, maintaining and troubleshoong the Gaylord Venlator. Venlators incorporang UV Systems,
maintenance and repair must be performed by a trained and cered service company. This manual also
includes informaon and guidance to contractors for the inial installaon of the Venlator.
The manual is divided into chapters for easy reference to a parcular subject. The pages in the chapters
are numbered with the chapter number then a dash and then the page number. So for example pages
in Chapter 2 are numbered 2-1, 2-2, 2-3 etc. Figures and Tables are numbered in a similar manor. For
example Figure 5-3-2 is on page 5-3 and is the second gure. Please keep your manual in a convenient
locaon for so it can be accessed easily.
If you have any quesons or concerns with the installaon, operaon, maintenance or service of your
Gaylord Venlator, please contact Gaylord Industries;
Web: www.gaylordvenlaon.com
E-mail: info@gaylordvenlaon.com
Main Phone: 503-691-2010 Toll Free: 800-547-9696
Safety
It is important that the operator read Chapter 2, Principle of Operaon, and Chapter 3, Maintenance,
before operang the Venlator for the rst me. Parcular aenon should be given to all the Cauon
and Warning statements.
Related Technical Manuals
1. ELX-UVi Series Venlators are controlled by a Gaylord Command Center. The specic manual for
this control is tled Operaon, Maintenance and Installaon Manual for the Gaylord Command
Center and Wash Control Cabinet.
2. ELX and ELX-UVi Series Venlators installed in the United States all include a Gaylord Autostart
Control. In some instances Venlators installed outside the United States will include an Autostart
Control. To determine if the Venlator includes an Autostart Control refer to page 1-3 and the
Nameplate mounted on the Venlator. The specic manual for this control is tled Operaon and
Maintenance Manual for the Gaylord Autostart Control.
3. ELX and ELX-UVi Venlators may include a Gaylord “Capture Wall” opon. The specic manual for
installaon of this is tled Installaon Manual – ELX Venlators with Capture Wall.
Operaon and Maintenance Manuals may be downloaded from the Gaylord website at
www.gaylordvenlaon.com or may be obtained by calling Gaylord Industries.

1-2
Figure 1-2-2
Model ELX-AB Series
Wall Mounted
Backshelf Style
Figure 1-2-4
Model ELX-CL Series
Single Extractor Design
for Single Island Arrangement
Chapter 1 – Introducon, Page 1-2
Model Descripon
OVERVIEW
The Gaylord Model EL Series Venlator uses a Listed bae lter and the ELX uses a Gaylord Model XGS high
grease Extractor. The Model ELX-UVi Series includes the addional feature of an Ultraviolet Light System
that removes up to 99% of the grease parculate.
The EL, ELX and ELX-UVi Venlators come in many dierent models, some of which are illustrated below.
Your Venlator may appear slightly dierent as they may have been custom designed to t the space and
applicaon.
Figure 1-2-1
Model ELX-BDL Series
Wall Mounted Canopy Shown With
Oponal Capture Wall
Figure 1-2-3
Model ELX-BB Series
Island Style for all
Double Island Arrangements

1-3
Chapter 1 – Introducon, Page 1-3
Model Number Explanaon
Model Number Sequence
Gaylord Venlator model numbers are made up of an alphabec prex followed by a series of alphabec
and/or numeric suxes to designate the style of venlator and various opons. Sequence of model
numbers is as follows.
1._______ 2._______ 3._______ 4._______ 5._______ 6._______ 7._______ 8.________ 9.________
Series Damper
Type
Style Front Lip
Design
(Opon)
Apron
Design (If
Applicable)
Canopy
Front Height
(Opon)
Solid fuel AutoStart Hood Depth
Denion of Prexes and Suxes
1. Series
EL ....................... Non water-wash venlator with UL 1046 lters.
ELX …………………. Non water wash ventilator incorporating XGS Extractors.
ELX-UVi ............. Non water wash ventilator incorporating XGS Extractors and UV filtration.
ELX-ENL …………. Non water wash ventilator incorporating XGS Extractors and UV filtration.
2. Damper Type
GBD ………………… Gaylord Balancing Damper. Has a mechanical balancing damper located at the duct
collar. (Standard)
GFBD.................. Gaylord Fire Balancing Damper. Has an electric, thermostatically activated Fire/
Balancing damper located at the duct collar with back draft feature. 325°F
thermostat standard.
GEBD ………………. Gaylord Electric Balancing Damper. Has an electric balancing damper located at the
duct collar with back draft feature.
FDD .................... Weighted fuse link acvated damper located at the duct collar. 280°F fuse link
standard.
ND …………………… No Damper.
3. Style
Blank ……………… Wall mounted canopy style.
CL …………………… Island style for single line of cooking equipment using one extraction chamber
(Light to Medium Duty only).
BBC-CL …………… Island style for single line of equipment using one extraction chamber with one
common exhaust duct.
BBC ………………… Island style for double line of cooking equipment using on one extracon chamber
and one common exhaust duct.
BB …………………… Island style for double line of equipment using two extraction chambers and two
separate exhaust ducts

1-4
Chapter 1 – Introducon, Page 1-4
Model Number Explanaon – Cont.
Denion of Prexes and Suxes – Cont.
4. Front Lip Design (Front lower edge of the hood)
Blank ……………… Facetted front design with 6 inch return flange. (3 Break or greater at front lip)
(CL models to have a maximum of 9”)
S ......................... Square front with 6 inch “Super Capture” lip
5. Apron Design Designation
Blank ………………. Capture wall to be added below hood.
A …………………….. Hood to have an apron, which will terminate at the bottom lower edge of the
canopy. (No interconnecting drains).
UW …………………. Gaylord UDS to be incorporated into capture wall. (Mixed Intertek and UL listing
required).
6. Front Canopy Profile Option
Blank ……………… Standard Profile - 30”or greater canopy height.
MP …………………. Medium Prole - 24” to 30” front height.
LP …………………… Low Profile - 12” to 23”front height. (Considerations for proper capture and contain need
to be considered with this opon).
7. Solid Fuel Equipment (If Applicable – 700°F Applications only)
Blank………………. Cooking equipment powered by sources other than the burning of wood.
SPA………………… Hood use “XGS-SPA” Spark Arrestor Extractors – Intended applications that utilize
the burning of wood as a heat source.
8. AutoStart Opon
Blank ................. Indicates the hood section does not have Autostart system as required by IMC.
AS .................... Indicates the hood section has Autostart conforming with the IMC requirement.
ASM ……………….. Indicates the hood is equipped with the second generation AutoStart system
conforming with the IMC requirement or the Demand Control Ventilation System
complying with IMC IECC, Calif. Title 24, IGCC, and ASHRAE Std. 90.1 / 189.
ASM1………………. Indicates the hood is equipped with a DCV system for a single fan mul-hood
applicaon.
9. Hood Depth (Outside of Structural wall to front of hood canopy)
(##) …………………. Value in inches to indicate the hood depth.

2-1
Chapter 2 – Principles of Operaon, Page 2-1
EL and ELX Series
Turning on the Exhaust Fan
Cauon: Always turn on the exhaust fan before turning on the cooking equipment.
Cauon: The chemical re exnguishing system may discharge if the exhaust fan is not on while the
cooking equipment is on or sll hot.
Cauon: Never operate your Venlator without the XGS Extractors or Grease Filters in place. Refer to
Figure 2-1-1.
To operate the exhaust fan ip the fan switch to the ON posion. The switch is typically mounted on a wall
near the Venlator or it may be mounted on the face of the Venlator.
Note 1: The EL and ELX Series Venlator may be equipped with a Gaylord Electric Balancing Damper,
designated “GEBD” in the Venlator model number, or a Gaylord combinaon Fire Damper/Balancing
Damper, designated “GFBD” in the model number. The Venlator model number can be found on the
Venlator Nameplate (Refer to Figure 5-5-2 for a sample of the nameplate and to Page 2-12 for informaon
on Balancing Dampers). If the Venlator includes one of these dampers when the fan is started the damper
moves from the closed to open posion and it will take approximately 45 seconds for the exhaust to come
up to 100%.
Note 2: Typically EL, ELX and ELX-UVi Series Venlators installed in the United States are equipped with a
Gaylord Autostart Controller that automacally turns on the exhaust fan if the temperature at the sensors
mounted in the canopy exceeds 90°F. (Refer to Figure 2-8-1). In some instances Venlators installed
outside the United States will include an Autostart Control. Inclusion of an Autostart Control is designated
by the sux “AS” in the model number. The Venlator model number can be found on the Venlator
Nameplate (Refer page 5-5-2 for a sample of the Nameplate). Refer to the Operaon, Maintenance and
Installaon Manual for the Gaylord Command Center for complete informaon on the Autostart Control.
Grease Extracon
Grease is extracted by either Listed Grease Filters or by the use of Gaylord Model XGS Extractors. Venlators
with Listed Grease Filters are designated EL Series and with Gaylord XGS Extractors they are designated
ELX Series. The Gaylord Industries Patent Pending Model XGS Extractor is designed to deliver the absolute
opmum in collecon eciency at the lowest possible pressure drop. The Extractors are ETL Recognized
as part of the ELX Venlator. They are constructed of corrosion resistant stainless steel.

2-2
Chapter 2 – Principles of Operaon, Page 2-2
EL and ELX Series – Cont.
Turning on the Exhaust Fan – Cont.
Figure 2-2-1
Grease Extracon
Turning O the Exhaust Fan
Cauon: Always turn o the cooking equipment and allow to cool before turning o the exhaust fan.
The chemical re exnguishing system may discharge if the cooking equipment is on or hot when the
exhaust fan is o.
At the end of the cooking day, turn o the cooking equipment and allow to cool before turning o the
exhaust fan. To turn o the exhaust fan ip the fan switch to the o posion
Note 1: If the Venlator includes a Gaylord Autostart Controller the exhaust fan will stay on if the temperature
at the duct collar is above 90°F. Once the temperature drops below 90°F., the fan will connue to run for
60 minutes and then shut o.
Note 2: If the Venlator is equipped with a Gaylord Electric Balancing Damper, designated “GEBD” or a
combinaon Gaylord Fire/Balancing Damper, designated “GFBD”, when the fan is turned o the damper
will move from the open to the closed posion, and remain closed unl the exhaust fan is re-started.
Closing the damper saves building energy by not allowing condioned air from draing up the exhaust
duct, or in cold climates prevents cold air from coming down the duct and into the kitchen.
Autostart Sensor
Grease Laden Air
Balancing Damper
Gaylord Model
XGS Extractor
Grease Gutter
Grease Drawer
Light Fixture

2-3
Chapter 2 – Principles of Operaon Page 2-3
EL and ELX Series – Cont.
Cleaning the Venlator
At the end of the cooking day, or at periodic intervals, depending upon the type of cooking, the XGS
Extractors must be removed and cleaned. They may be removed by hand or by use of an Extractor Removal
Tool (refer to Figure 2-3-1). In addion the Grease Drawer must be removed and cleaned and the Grease
Guer wiped out. Refer to page 3-1 for detailed instrucons on cleaning.
Figure 2-3-1
Cleaning
Fire Protecon
Fire Damper
The EL and ELX Series Venlator may be equipped with a combinaon Gaylord Fire Damper/Balancing
Damper, designated “GFBD” in the Venlator model number. If equipped, a 250°F. thermostat will be
mounted at the entrance of the exhaust duct collar (refer to Figure 2-3-1). In the event or a re and the
thermostat reaches 250°F., the following will occur:
1. The re damper will close prevenng re from extending into the exhaust duct and fan.
2. The exhaust and supply fans will also shut o.
3. If the Venlator is wired to the building re alarm system the alarm will acvate.
4. Once the thermostat cools below 250°F., the re damper will open, and the exhaust and supply
fans re-start.
Plenum Area
Grease Drawer
Gaylord Model XGS
Extractor

2-4
Chapter 2 – Principles of Operaon Page 2-4
EL and ELX Series – Cont.
Fire Protecon – Cont.
Fire Exnguishing Systems
The Naonal Fire Protecon Associaon Standard 96 (NFPA-96) and the Internaonal Fire Code (IFC)
requires the use of a Fire Exnguishing System to cover the cooking surfaces, Venlator exhaust plenums
(the area behind the grease extractors), and the exhaust duct (Refer to Figure 2-4-1). Upon acvaon of
the Fire Exnguishing System the follow will occur:
1. Fire exnguishing agent will discharge through the cooking equipment nozzles, the plenum nozzles
and the duct nozzle(s).
2. The protected cooking equipment and possibly other cooking equipment will shut o. Refer to the
above referenced codes for specic equipment that must shut o.
3. If the Fire Exnguishing System is wired to a building re alarm system the alarm will acvate.
4. If the Fire Exnguishing System is wired to a building management system it will nofy of a re
condion.
5. The Fire Exnguishing System should be wired to the Gaylord fan control. If is the following will
occur:
a) If the exhaust and supply fan were on the exhaust fan would stay on and the supply fan would
shut o. It the exhaust and supply fans were o, the exhaust fan would come on and the
supply fan would stay o.
b) If the Venlator is equipped with a Gaylord Electric Balancing Damper (model GEBD) or a
Gaylord Fire/Balancing Damper (model GFBD) the damper will open.
6. Aer discharge, the Fire Exnguishing System must be recharged and cered by a re system
contractor before the cooking equipment can be turned back on.
For Operaon and Maintenance of the Fire Exnguishing System, refer to the system manufacture’s
Owner’s Manual.
Important: NFPA-96 requires inspecon and cercaon of re systems every 6 months.
Figure 2-4-1
Fire Exnguishing System Discharge
When a Fire Exnguishing System
Discharges, the Balancing Damper
remains open. If equipped with an
Electric Balancing Damper, Model
GED, the damper remains open or
opens if it was closed. If equipped
with a Model GFBD Fire Damper,
and the thermostat acvates, the
damper closes.
Fire Extinguishing System
Detector
Fire Extinguishing System
Plenum Nozzle
Fire Extinguishing System
Cooking Equipment Nozzles
Balancing Damper
Fire Extinguishing System
Duct Nozzle

2-5
Chapter 2 – Principles of Operaon Page 2-5
ELX-UVi Series
Ultraviolet Systems (UV)
Overview
Venlators incorporang UV Lamps are designated Model ELX-UVi Series Venlators. UV Systems are used
to remove a high percentage of grease that the Extractors cannot remove, oering many benets to the
owner/operator. The UV Lamps are mounted in a UV Module which slide into a track downstream (aer)
the XGS Extractors (refer to Figure 2-8-1). The electronics and ballasts for UV System are mounted in a UV
Ballast Box which is located on the top of the Venlator (refer to Figure 2-8-1). The ELX-UVi Venlator is
equipped with UV Status Lights to monitor the status of the UV System, and Safety Interlocks to protect
operators from exposure to UV light (refer to Figure 2-7-1).
For proper UV operaon, the Venlators must be maintained in good working order. The UV system must
be inspected periodically and the lamps replaced as necessary. The Venlator, ductwork and exhaust fan
must be inspected in accordance with NFPA-96 or local guidelines, though frequency of duct cleanings
should be signicantly reduced.
UV Safety
Cauon: Exposure to UV light is harmful to skin and eyes.
The ELX-UVi Venlator is equipped with panels and Safety Interlocks to protect operators from direct
exposure to UV light. All safety precauons called for is this manual must be followed to avoid the potenal
for harm to service personnel or operators. Refer to Page 3-3 for complete descripon of safety precauons.
Turning On the Exhaust Fan and UV System
Cauon: Always turn on the exhaust fan before turning on the cooking equipment
Cauon: The chemical re exnguishing system may discharge if the exhaust fan is not on while the
cooking equipment is on or sll hot.
Cauon: Never operate the Venlator without the XGS extractors in place. Refer to Figure 2-5-2.
Operaon of the exhaust fan and UV Lamps is controlled by the Gaylord Command Center (refer to Figure
2-6-1). To start the exhaust fan and turn on the UV Lamps push START FAN on the Command Center. The
Command Center may be programmed to automacally start the exhaust fan at a specic me. Refer
to the Operaon, Maintenance and Installaon Manual for the Gaylord Command Center for complete
operang instrucons.
Note 1: The UV Lamps will not come on unless all the XGS Extractors are in place as shown in Figure 2-5-2.
Note 2: The UV Lamps will not come on unless all the UV Module Access Panels are closed and latched as
shown in Figure 2-5-2.

2-6
Chapter 2 – Principles of Operaon Page 2-6
ELX-UVi Series – Cont.
Turning On the Exhaust Fan and UV System – cont.
Note 3: ELX-UVi Series Venlator may be equipped with a Gaylord Electric Balancing Damper, designated
“GEBD” in the Venlator model number, or a Gaylord combinaon Fire/Balancing Damper, designated
“GFBD” in the model number. The Venlator Model number can be found on the Venlator Nameplate
(Refer to page 2-12 informaon on Balancing Dampers and page 5-5-2 for a sample of the nameplate). If
the Venlator includes one of these dampers, when the fan is started the damper moves from the closed
to the open posion and it will take approximately 45 seconds for the exhaust air to come up to 100%.
Note 4: The ELX-UVi Series Venlator may be equipped with a Gaylord Autostart Controller that automacally
turns on the exhaust fan if the temperature at the exhaust duct collar exceeds 90° F. If the Venlator does
include Autostart, the Venlator will include one or more sensors mounted in the canopy (Refer to Figure
2-5-2). Refer to the Gaylord AutoStart Technical Manual for Operaon and Maintenance.
Figure 2-6-1
Gaylord Command Center

2-7
Chapter 2 – Principles of Operaon Page 2-7
ELX-UVi Series – Cont.
Turning On the Exhaust Fan and UV System – cont.
UV Status Lights
Each Venlator secon contains a bank of UV Status Lights to monitor the UV System (refer to Figure
2-7-1). There are three colored lights, Green, Yellow and Blue. They indicate the system status as follows:
1. Green On: The UV system is operang properly.
2. Yellow On: One or more UV Lamps are not operang.
3. Blue On: One or more XGS Extractors are not in place and/or one or more UV Module Access Panels
are not latched properly, or the internal temperature of the Ballast Box has exceeded 118° F. and the
High Temperature Shutdown Controller acvated. During this mode the UV System is not operang,
and is in a Uvi System Standby mode unl the cause has been corrected.
Note: If either the Yellow or Blue light are on refer the Troubleshoong secon of this manual beginning
on page 4-1 for correcve acon.
Figure 2-7-1
UV Status Lights
Grease Extracon
Grease is removed from the exhaust air by combinaon of the Gaylord Model XGS Extractors and the UV
Lamps (Refer to Figure 2-8-1). The hot contaminate-laden air rising from the cooking surface is drawn
through the Extractors where a high percentage of the grease and other parculate are extracted from
the airstream. As the air enters the Plenum chamber, the grease parcles are exposed to the ultraviolet
light which oxidizes the parcles into a light gray powder which are deposited on the Lamps, the Plenum
chamber and in the exhaust duct. Some powder may exhaust out the exhaust fan. The extracted liquid
grease will drain down the Extractors and into the Grease Guer which then drains to the Grease Collecon
Drawer. The scky grease will remain in the Extractors unl cleaned.
The Gaylord Industries Model XGS Extractor is designed to deliver the absolute opmum in collecon
eciency at the lowest possible pressure drop. The Extractors are ETL Recognized as part of the ELXC-UVi
Venlator. They are constructed of corrosion resistant stainless steel.
UVi
SYSTEM
ON
UVi
LAMP
FAILURE
UVi
SYSTEM
STANDBY
20385
SYSTEM STATUS
UVi Ventilator
Integrated DCV

2-8
Chapter 2 – Principles of Operaon Page 2-8
ELX-UVi Series – Cont.
Turning On the Exhaust Fan and UV System – cont.
Figure 2-8-1
Grease Extracon
Figure 2-8-2
Model ELX-UVi Series Cutaway
Grease Drawer
Optional
Rear Capture Wall
UV Lamp Module
Static Tap Cover
UV Module Access Doors
Access to Ballast Box
UV Status Lights
Autostart Sensor
Grease Laden Air
Balancing Damper
Gaylord Model
XGS Extractor
Grease Gutter
Grease Drawer
Ballast Box Accessible
from Underside UV Lamps
UV Lamp Module

2-9
Chapter 2 – Principles of Operaon Page 2-9
ELX-UVi Series – Cont.
Turning O the Exhaust Fan and UV System
Cauon: Always turn o the cooking equipment and allow to cool before turning o the exhaust fan.
The chemical re exnguishing system may discharge if the cooking equipment is on or hot when the
exhaust fan is o.
At the end of the cooking day, turn o the cooking equipment and allow to cool before turning o the
exhaust fan. To stop the exhaust fan and turn o the UV Lamps push STOP FAN on the Gaylord Command
Center. The Command Center may be programmed to automacally turn o the exhaust fan at a specic
me. Refer to the Operaon, Maintenance and Installaon Manual for the Gaylord Command Center for
complete operang instrucons.
Note 1: If the Venlator includes a Gaylord Autostart Controller the exhaust fan will stay on if the
temperature at the duct collar is above 90° F. Once the temperature drops below 90° F., the fan will
connue to run for 60 minutes and then shut o.
Note 2: If the Venlator is equipped with a Gaylord Electric Balancing Damper, designated “GEBD” or a
Gaylord combinaon Gaylord Fire/Balancing Damper, designated “GFBD”, when the fan is turned o the
damper will move from the open to closed posion and remain closed unl the exhaust fan is re-started.
Closing the damper saves building energy by not allowing condioned air from draing up the exhaust
duct, or in cold climates prevenng cold air from coming down the duct and into the kitchen.
Cleaning the Venlator
At the end of the cooking day, or at periodic intervals, depending upon the type of cooking, the XGS
Extractors must be removed and cleaned. They may be removed by hand or by use of an Extractor Removal
Tool (Refer to Figure 2-9-1). In addion the Grease Drawer must be removed and cleaned and the Grease
Guer wiped out. The UV Lamps should be inspected weekly and cleaned if necessary. Refer to Page 3-1
for detailed instrucons.
Figure 2-9-1
Cleaning
Plenum Area
Grease Drawer
Gaylord Model XGS
Extractor
Grease Gutter
UV Lamps
UV Lamp Module

2-10
Chapter 2 – Principles of Operaon Page 2-10
ELX-UVi Series – Cont.
Fire Protecon
Fire Damper
The ELX-UVi Series Venlator may be equipped with a combinaon Gaylord Fire/Balancing Damper,
designated “GFBD” in the Venlator model number. If equipped, a 250°F. thermostat will be mounted at
the entrance of the exhaust duct collar (Refer to Figure 2-11-1). In the event of a re and if the thermostat
reaches 250°F., the following will occur:
1. The re damper will close prevenng re from extending into the exhaust duct and fan.
2. The exhaust and supply fans will shut o.
3. The UV Lamps will shut o.
4. If the Command Center is wired to a building re alarm system the alarm will acvate.
5. If the Command Center is wired to a building management system it will nofy of a re condion.
6. Once the thermostat cools below 250°F., plus a 5 minute cool down, the exhaust and supply fans
can be re-started by pushing the START FAN on the Command Center.
Fire Exnguishing Systems
The Naonal Fire Protecon Associaon Standard 96 (NFPA-96) and the Internaonal Fire Code (IFC)
requires the use of a Fire Exnguishing System to cover the cooking surfaces, Venlator exhaust plenums
(the area behind the grease extractors), and the exhaust duct (Refer to Figure 2-11-1). Upon acvaon of
the Fire Exnguishing System the follow will occur:
1. Fire exnguishing agent will discharge through the cooking equipment nozzles, the plenum nozzle(s)
and the duct nozzle(s).
2. The protected cooking equipment and possibly other cooking equipment will shut o. Refer to the
above referenced codes for specic equipment that must shut o.
3. If the Fire Exnguishing System is wired to a building re alarm system the alarm will acvate.
4. If the Fire Exnguishing System is wired to a building management system it will nofy of a re
condion.
5. The Fire Exnguishing System should be wired to the Gaylord Command Center. If it is the following
will occur:
a) If the exhaust and supply fan were on the exhaust fan would stay on and the supply fan
would shut o. If the exhaust and supply fans were o, the exhaust fan would come on and
the supply fan would stay o.
b) If the Venlator is equipped with a Gaylord Electric Balancing Damper (model GEBD) or a
Gaylord Fire/Balancing Damper (model GFBD) the damper will open.
6. Aer discharge, the Fire Exnguishing System must be recharged and cered by a re system
contractor before the cooking equipment can be turned back on.
Other manuals for ELX SERIES
1
This manual suits for next models
1
Table of contents
Other GAYLORD Ventilation Hood manuals