GENERI X450DA2/d User manual

GENERI, s.r.o.
Uničovská 50
787 01 ŠUMPERK
USER'S MANUAL
Page: 1 of
EXPLOSION-PROOF SWITCHGEAR BOX
TYPE:
X450DA2/d
N740058
– 4rd edition
Valid from:
28.1.2020
Tel.:
+4220583221500, Fax: +420583214183
GENERAL
This User’s Manual has been drawn up in accordance with:

Technical requirements for equipment and protective systems
intended for use in potentially explosive atmospheres
(2014/34/EU).

Technical requirements for products from the point of their
electromagnetic compatibility (2014/30/EU).
SAFETY GUIDELINES AND IMPROPER USE
Do not leave this User’s Manual in the switchgear box during
operation!
• Do not operate X450DA2/d switchgears in SNM
mine areas ( NM3) according to ČB Decree No.
22/1989 Coll., or in explosive atmospheres
(hazardous conditions 1) according to ČSN EN 1127-2.
• Do not operate X450DA2/d switchgears in Zone 0
explosive gas atmospheres (ČSN EN 60079-10-1) and
Zone 20 and 21 explosive dust atmospheres (ČSN EN
60079-10-2)
• The cable glands must always be in the Ex “d” design
(flame-proof enclosure) according to ČSN EN 60079-1
• In the case of cable entry through cable glands with a
sealing ring, only use compact and round cables with
sheathing made of thermoplastic, thermoset or
elastomeric materials. The bedding and sheathing
must be extruded and the bedding material, if used,
non-absorbent. The cable must be at least m long!
• There may be parts with hot surfaces, i.e.
hazardous temperature inside the X450DA2/d
switchgear. Open the switchgear only in the
absence of explosive atmospheres and in a non-
voltage state after a sufficient time since its
deactivation to allow the hot parts to cool.
• X450DA2/d switchgears are not designed for non-
professional use. Installation, start up and any service
whatsoever must be performed by workers with
professional expertise and in conformance with safety
regulations.
• Operate X450DA2/d switchgears in accordance with
the following operating conditions, technical and label
data.
• Do not replace the existing internal equipment of
the switchgear with equipment inconsistent with
the documentation supplied with the product (e.g.
replacement of an existing 6A circuit breaker with a
10A circuit breaker).
• If the switchgear contains a current protector,
regularly verify their function at least every 6
months using the test button (while observing
applicable safety regulations).
• Some mining cables (e.g. type CBEH) have individual
wires provided with a semi-conductive removable layer.
Always remove this layer before connecting the
wires!
• Switching and protective devices inside switchgears
may produce short-term electromagnetic
interference and therefore have to be used in
industrial zones, where they do not have a negative
impact on other equipment.
• Carry out storage, transport, assembly, installation,
revision and preventive maintenance, repairs and
service in accordance with the instructions stated
hereunder.
1. USE
Switchgears X450DA2/d are designed primarily for installation in
mines containing methane, in areas with explosive gas atmospheres,
in areas with explosive atmospheres with flammable dust and areas
with a risk of fire or explosion of explosives.
2. OPERATING CONDITIONS
2.1. External influences in accordance with ČSN 33 2000-5-51 –
Category A: ENVIRONMENT
Code
Description of external influence Specification
AA Ambient temperature Ta -20 °C to +40°C
AB Atmospheric humidity
up to +30°C ..
100%
up to +40°C ...
70%
AD4 Presence of water spraying water
AE4 Presence of foreign solid particles light dustiness
AF4 Presence of corrosive substances or
contaminants permanent
AG Impact strong (20J)
AH Vibrations see Article 6 –
Revision
2.2. External influences in accordance with ČSN 33 2000-5-51 –
Category B: USE
Code Description of external influence Specification
BE N1 Risk of explosion of combustible dust see section
2.4
BE N2 Risk of explosion of flammable gases and
vapours
see section
2.4
BE N Risk of explosion of explosives see section
2.4
BA5 Skills of persons knowledgeabl
e persons
BC Contact of persons with earth potential frequent
2. . Unspecified external influences are normal in accordance
with ČSN 33 2000-5-51.
2.4. Use in areas and atmospheres in accordance to installation
regulations
Areas Standard name (version) Standard
SNM
( NM0, NM1,
NM2)
ČB Decree
(version I M2)
ČB No. 22/1989
Coll.,
s. 232, s. 233
ČB No. 75/2002
Coll.,
Explosive
atmospheres
(hazardous
conditions 2)
Explosive atmospheres –
Explosion prevention and
protection – Part 2: Basic
concepts and methodology
for mining.
(version I M2)
ČSN EN 1127-2
ZONE 1, 2 IIA,
IIB
Explosive atmospheres
– Part 10-1: Classification of
areas
– Explosive gas
atmospheres (version II
2G/ D)
ČSN EN 60079-10-1
ZONE 22 IIIA,
IIIB T>71°C
Explosive atmospheres
– Part 10-2: Classification of
areas
– Explosive dust
atmospheres
(version II 2G/ D )
1)
ČSN EN 60079-10-2
V1, V2
Regulations for electrical
equipment in areas with a
risk of fire or explosion of
explosives
ČSN 33 2340
1)
The device is designed for fixed installation, where the installation
is supposed to minimize the risk of electrostatic discharge – see
EN TR 50 404 a IEC/T 60 079-32.
GENERI, s.r.o.
Uničovská 50
787 01 ŠUMPERK
USER'S MANUAL
Page: 2 of
EXPLOSION-PROOF SWITCHGEAR BOX
TYPE:
X450DA2/d
N740058
– 4rd edition
Valid from:
28.1.2020
Tel.:
+4220583221500, Fax: +420583214183
2.5. Work position: Vertical
. TECHNICAL DATA
Name Specification Standard, note
Explosion-proof
design
Ex db I Mb
Ex db IIB T6 Gb
Ex tc IIIB T71°C Dc
ČSN EN 60079-0
ČSN EN 60079-1
ČSN EN 60079-31
Degree of
protection
IP 54 ČSN EN 60529
Group and
category
I M2 / II 2G / II D
2014/34/EU
Certification
FTZÚ 10 ATEX 01 9X FTZ NB 1026
Switchgear design
LV switchgear
LV power switchgear
ČSN EN 61439-1
ČSN EN 61439-2
Nominal voltage
and nominal
current
See company label
Nominal short-
time current Max. 10 kA ČSN EN 61439-1
Electromagnetic
compatibility
switchgear without built-in electronic equipment
resistant
to
interference
emitting short-term
interference
according to ČSN EN
61439-1
no further verification
required
switchgear with built-in electronic equipment
resistant
to
interference
not emitting
interference
according to
harmonized ČSN IEC
for EMC
Box material steel 11 373 pressure-welded
Outer terminal PE 16 mm
2
2 x M5 screw with
liner
Protection class
I
ČSN EN 61 140
4. INSTALLATION INSTRUCTIONS
4.1. Switchgear attachment – dimensions
4.2. Cable entries
For direct cable entry (in a flame-
proof enclosure), use only
appropriate explosion-proof
cable glands certified as Ex
equipment. You can use cable
glands sealed with a sealing
compound (barrier glands) or
cable glands with a sealing ring. In the case of entry through cable
glands with a sealing ring, carefully choose an appropriate cable –
see Safety guidelines and improper use. The cable used must be at
least m long.
Each cable gland seals only a certain range of cable diameters. In the
case of a larger number of cable glands on the box flange, always
insert and seal the cable in the cable gland gradually from one side
(e.g. from left to right) and always start with the cable glands on the
bottom row and then continue with the cable glands right above them.
For easier installation of cable glands, you can request special
tightening pliers – see fig. To attain reliable protection of cable glands,
tighten them properly with the specified torques.
Blank unused holes with certified plugs with the respective ingress
protection and explosion-proof design.
4. . Connecting wires to terminals
Wires can be connected using spring-cage terminal blocks or screw
terminal blocks.
4. .1 Spring-cage terminal blocks
By compressing the spring-cage (1) e.g.
with a suitable screwdriver (or special
WAGO screwdriver, which is supplied only
upon customer request), release the
window for attaching the wire. Insert the
wire (2) and release the spring cage (3),
which will lead to a perfect current-
carrying connection. Always equip
stranded wires with end ferrules.
Termination of stranded wires with soft
solder (Pb-Sn) is not allowed!
When interconnecting two
neighbouring terminal blocks with a
spring cage using special blade terminals, press this terminal with
force into both terminal blocks so that the terminal does not extend
beyond (see following fig.). In the case of some types of spring-cage
terminal blocks, connecting a wire with a ferrule requires the use of a
terminal block with a connection cross-section one grade higher than
the wire cross-section. E.g. a 2.5mm
2
wire with a ferrule requires the
use of a 4.0mm
2
terminal block.
4. .2 Screw terminal blocks
Connect the wires to the
side of the terminal block
and tighten the connection
properly. When
interconnecting screw
terminal blocks (see
following fig.), tighten the
screw terminals properly.
4. . General requirements
The following applies to both types of terminal blocks: only one wire
may be inserted into one outlet and its maximum cross-section must
not be larger than the nominal cross-section of the terminal block. The
wire insulation must reach as close as possible to the actual current-
carrying connection and the wire itself must not be damaged in any
way.
We recommend treating protective conductor connection points (or
other metal surfaces subject to corrosion) regularly with lubricating
grease at least once a year (according to the operating atmosphere).
Connect unused wires without voltage to empty terminals (including
protective ones) or terminate them in other ways according to
applicable regulations.
5. INSTALLATION ACCORDING TO APPLICABLE
REGULATIONS
The decision to use a given type of equipment in the areas
considered must be in accordance with the above operating
conditions (see section 2.), local operating regulations, ČB Decree
No. 75/2002 Coll. (for mining equipment with danger of presence of
methane), ČSN EN 60079-14 (for Group II equipment) and other
related regulations.
Apart from the above stated regulations, protection against injury
due to electric shock is also stipulated by ČSN 332000-4-41,
ČSN EN 61140 and other related regulations.
Safety regulations for operation and work on electrical equipment
are stipulated by ČSN EN 50110-1.
Professional competence of workers in electrical engineering is
stipulated by Decree No. 50/1978 Coll., as amended.
6. REVISION AND PREVENTIVE MAINTENANCE
Revision and preventive maintenance of explosion-proof electrical
equipment is stipulated by ČB Decree No. 75/2002 Coll. (for mining
equipment with danger of presence of methane) and ČSN EN 60079-
17 (for Group II equipment), unless specified otherwise e.g. by a
decree, local regulations.
Opening of the box lid – see Safety guidelines and improper use.
Before closing the flat enclosure surface of the steel box and lid,
GENERI, s.r.o.
Uničovská 50
787 01 ŠUMPERK
USER'S MANUAL
Page: of
EXPLOSION-PROOF SWITCHGEAR BOX
TYPE:
X450DA2/d
N740058
– 4rd edition
Valid from:
28.1.2020
Tel.:
+4220583221500, Fax: +420583214183
always clean it and coat it with a thin layer of K3 ČSN 65 6911
grease for corrosion protection.
Cleaning of enclosure surfaces can only be performed with non-
metal scrapers and corrosion-free liquid.
Re-lubrication of the enclosure surface must be performed at
least once a year. Switchgears must have all electrical and
mechanical connections secured against self-release. However,
vibration tests of equipment (external influences AH1, 2, 3 according
to ČSN 33 200-5-51) in relation to climatic condition classes
according to ČSN EN 60 721-3-3 and ČSN EN 60 721-3-4 are not
performed. For Group I mobile equipment, it is therefore
recommended to perform regular revisions according to Annex 2
to ČBÚ Decree No. 75/02 Coll., and for Group II equipment
according to ČSN EN 60079-17 at least twice a year at the level of
detailed inspection.
Cable glands and plugs may only be replaced with those with the
corresponding explosion-proof design (see Technical data) and
ingress protection and certified by the respective notified body.
Where it is not possible to secure fixed installation of cables,
cable glands must be also in the version secured against cable
tension (with a clamp) – this especially applies to mobile
equipment.
Other spare parts, see Article 10.
7. REPAIRS AND GENERAL INSPECTIONS, SERVICE
Repairs and general inspections of explosion-proof electrical
equipment are specified by ČB Decree No. 74/2002 Coll., (for Group
I mining equipment) and ČSN EN 60079-19 (for Group II equipment).
Repairs should preferably be entrusted to the manufacturer or its
authorized organization which, in the case of repairs of explosion-
proof mining equipment, must have valid authorization according to
the aforementioned ČB decree.
In case of damage to the flame-proof enclosure joint, contact the
manufacturer to receive information on joint dimensions.
The following parts are deemed irreparable:
•
tempered-glass window in the steel lid
•
Ex cable glands and plugs
•
non-losable stainless steel screws in the box lid
•
terminal blocks, circuit breakers, contactors and other electrical
components
These parts must be replaced when damaged.
During all repairs and renovations, maintain the original
explosion-proof design and ingress protection (see company
label).
In case of any problems related to GENERI, s.r.o. products (e.g.
loss of accompanying documentation, technical defect, etc.), all
you need to do is note down the following two pieces of
information on the company label:
1) EQUIPMENT TYPE DESIGNATION
2) SERIAL NUMBER (No.)
With the help of these two pieces of data, you can find all
accompanying and technical documentation for the specific product at
the manufacturer.
8. STORAGE, PACKAGING AND TRANSPORT
Switchgears are to be stored at ambient temperatures of +5 °C to
+40 °C, in non-aggressive indoor areas without exposure to UV
radiation and the weather, in which the quality will not worsen (climate
conditions 1K2, biological conditions 1B1, chemical active substances
1C2, mechanically active substances 1S1 and mechanical conditions
1M2 in accordance with ČSN EN 60 721-3-1).
Switchgears are packed in protective foil and shipped in cardboard
boxes (larger boxes may be fixed on pallets).
Transport is generally provided by an express service within 24
hours, or according to the demands of the customer. C.O.D. is also
possible.
Transport conditions are 2K2, 2B1, 2C2, 2S1, 2M2 in accordance
with ČSN EN 60 721-3-2.
9. DELIVERY TERMS AND CONDITIONS
The price of goods, delivery terms, payment method, and transport
mode are stated in the purchase agreement, which the Sales
Department sends out after obtaining an order form.
10. SPARE PARTS
Each switchgear contains a wiring diagram exactly specifying
individual electrical components.
11. DISPOSAL OF THE PRODUCT
Dispose of unnecessary product
s in accordance with
effective regulations.
!!! All components and parts may release harmful
vapours when burning!!!
12. DOCUMENTATION PROVIDED WITH THE PRODUCT

EC Declaration of Conformity

Wiring diagram inserted in the switchgear

This User’s Manual including the warranty

Delivery note
The certificate is available at www.generi.cz or on request.
WARRANTY
Product TYPE:
X450DA2/d
Serial No.: from: to:
This product is provided with a 12-month warranty
(unless stated otherwise in the purchase agreement),
commencing on the day it was accepted. We
guarantee the quality of work and materials.
Nevertheless, defects may arise as a result of storage,
transport or use, which are undetectable in the
production plant. If such defects have been incurred
by defective material or production, we shall render
the product into a perfect state at our own expense.
The warranty does not apply to defects incurred by
improper use, mechanical damages and by not
adhering to the instructions for assembly and
maintenance.
FINAL INSPECTION
Authorised
worker:
Result:
OK
Stamp and
signature:
WE WISH YOU MAXIMUM SATISFACTION WITH OUR
PRODUCTS AND SERVICES
ISO 9001

Popular Switch manuals by other brands

Zektor CVS4 user guide

Zektor

Zektor CVS4 user guide

StarTech.com ST4100USB Specifications

StarTech.com

StarTech.com ST4100USB Specifications

Crestron DM Lite HD(I)-MD Series Supplemental guide

Crestron

Crestron DM Lite HD(I)-MD Series Supplemental guide

IOGear GCS932UB installation guide

IOGear

IOGear GCS932UB installation guide

Axis T86 Series installation guide

Axis

Axis T86 Series installation guide

Fortinet FortiManager 1000D quick start guide

Fortinet

Fortinet FortiManager 1000D quick start guide

Kramer VIA CONNECT PRO user manual

Kramer

Kramer VIA CONNECT PRO user manual

fadini CORAL 1050 instruction manual

fadini

fadini CORAL 1050 instruction manual

HP AdvanceStack Remote 2C reference guide

HP

HP AdvanceStack Remote 2C reference guide

Castell KSUPS user manual

Castell

Castell KSUPS user manual

Redbird TD quick start

Redbird

Redbird TD quick start

Alcatel-Lucent OmniSwitch 6350 Hardware user's guide

Alcatel-Lucent

Alcatel-Lucent OmniSwitch 6350 Hardware user's guide

AirLive SNMP-GSH2416 user manual

AirLive

AirLive SNMP-GSH2416 user manual

Minicom 0SU52016 owner's manual

Minicom

Minicom 0SU52016 owner's manual

3Com Baseline 2824 user guide

3Com

3Com Baseline 2824 user guide

NETGEAR ProSafe GS108 installation guide

NETGEAR

NETGEAR ProSafe GS108 installation guide

Cross Technologies 1582-225L2 instruction manual

Cross Technologies

Cross Technologies 1582-225L2 instruction manual

Waters Network Systems ProSwitch-Quad Series Installation guide and operating manual

Waters Network Systems

Waters Network Systems ProSwitch-Quad Series Installation guide and operating manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.