
IO-231 6/03
4
The GMNTE series of furnaces meet the California NOx
emission standards and California seasonal efficiency stan-
dards. ANNUAL inspections of the furnace and its vent sys-
tem is strongly recommended. It is the installer’s responsi-
bility to inform the user of this importance. Any installation,
alteration or repair of this equipment must not be in viola-
tion of local code or the information contained in this manual.
This furnace shall be securely fastened in place when in-
stalled in the vertical position. This furnace must be in-
stalled in such a manner as to allow for service, inspection,
repair or replacement without removing permanent con-
struction. A platform is recommended to allow for service.
LOCATION
DO NOT install this furnace in a mobile home. This furnace
is designed only for installation in buildings constructed on
site and connected to ductwork. When installed in a utility
room or closet, the door should be wide enough to allow
the largest part of the furnace to enter, or to permit the
replacement of another appliance, such as a water heater.
This furnace is designed to be installed indoors only. DO
NOT install outdoors. This furnace should be installed in
such a manner so that it is protected from water. If any
components should become wetted or submerged under
water, replace those parts before returning the furnace to
operation. DO NOT use as a construction heater. DO
NOT use in an area where freezing may occur without
properly protecting the vent and drain system. The drain
may crack and leak if subjected to freezing temperatures.
DO NOT install in a room used or designed to be used as
a bedroom, bathroom or storage closet, or in any enclosed
space with access only through such a room or space.
A return air filter grille or means of inserting a filter into the
return air duct is recommended. The opening in the duct
used for filter access must be capable of being sealed air
tight if located in the same pressure zone as the furnace.
The furnace and it’s individual shut-off must be
disconnected from the gas supply piping system during
any pressure testing of that system at test pressures in
excess of 1/2 psig (3.5kPa)
The furnace must be isolated from the gas supply piping
system by closing it’s individual manual shut-off valve during
any pressure testing of the gas supply piping system at
pressures equal to or less than 1/2 psig (3.5 kPa).
MIN. CLEARANCES TO COMBUSTIBLE SURFACES
Unobstructed front clearance of 24" for servicing is
recommended.
RIGHT SIDE - 1" VENT - 0"
REAR - 0" LEFT SIDE - 1"
TOP OF PLENUM - 1" FRONT - 3"
Line contact is permitted in the horizontal position.
ACCESSIBILITY CLEARANCE, WHERE GREATER,
SHOULD TAKE PRECEDENCE OVER MINIMUM FIRE
PROTECTION CLEARANCE.
A gas-fired furnace for installation in a residential garage
must be installed so that the ignition source and burners
are located not less than eighteen inches (18") above the
floor and is protected or located to prevent physical damage
by vehicles.
A gas furnace must not be installed directly on carpeting,
tile, or other combustible materials other than wood
flooring.
Before proceeding with this installation check the following;
•Correct clearance from combustible materials
•Adequate accessibility for servicing
•Flooring is not carpet or any other combustible
material, except wood
•Adequate combustion / ventilation air is supplied
•Metal base plate is in place when using side(s) for
return air
•In a garage, the furnace has been adequately elevated
and protected from vehicle damage
•Furnace area is free of flammable materials and vapors
such as gasoline
COMBUSTION AIR
The GMNTE furnace can be installed either as a Direct
Vent (2 pipe) or a Non-Direct Vent (1 pipe) appliance. If
installed as direct vent appliance the combustion air is to
be taken from the outdoors via 3” schedule 40 PVC pipe
and terminate at the furnace cabinet. As a non-direct vent
furnace the combustion air is taken from the area which
the furnace is installed. Avoid combustion air sources
which contain flammable fumes and vapors, and gasses
such as carbon monoxide, hydrogen sulfide, ammonia,
chlorine, and halogenated hydrocarbons.
WARNING
A SOLID METAL BASEPLATE IS SUPPLIED WITH THIS
FURNACE. THIS BASEPLATE MUST BE IN PLACE AND
SEALED AIR TIGHT WHEN THE FURNACE IS INSTALLED
WITH SIDE RETURN AIR DUCTS. FAILURE TO DO SO MAY
PERMIT COMBUSTION PRODUCTS, INCLUDING CABON
MONOXIDE, TO ENTER THE LIVING SPACE AND CREATE
POTENTIALLY HAZARDOUS CONDITIONS SUCH ASCARBON
MONOXIDE POISONING OR DEATH. FULL SIZE RETURN AIR
DUCT OPENINGS MUST BE UTILIZED. EMBOSSES ARE
PROVIDED FOR THIS PURPOSE.
WARNING
COMBUSTIBLE MATERIAL MUST NOT BE PLACED ON OR
AGAINST THE FURNACE CABINET. THE AREA AROUND
THE FURNACE MUST BE KEPT CLEAR AND FREE OF ALL
COMBUSTIBLE MATERIAL INCLUDING GASOLINE AND
OTHER FLAMMABLE VAPORS AND LIQUIDS. THE USER
MUST BE CAUTIONED THAT THE FURNACE AREA MUST NOT
BE USED AS A BROOM CLOSET OR FOR ANY OTHER STOR-
AGE PURPOSE.