Great Lakes WMCM Series User manual

WMCM, WDX, WM, WD,15WM, WE
& NEMA 12K Series Wall Mounts
Installation Instructions
GreatCabinets.com - 1-866-879-4522
WMCM
WDX

PREFACE
This manual is provided to prevent service personnel from committing
an act that results in the risk of re, electric shock, or injury to persons.
Only trained service personnel should receive, unpack, and assemble
the Great Lakes Wall Mount. In addition, only trained service personnel
should install equipment in enclosures.
SAFETY SYMBOLS USED IN THIS MANUAL
This manual provides general safety guidelines to be observed during
installation, operation, and maintenance of the Great Lakes Wall Mount.
WARNING: Failure to follow directions in the warning could result in
injury to persons or loss of life.
CAU T I ON : Failure to follow directions in the caution could result in
damage to equipment or storage data.
SAFETY CONSIDERATIONS
WARNING: Improper handling and use of the Great Lakes Wall Mount
could result in equipment damage, serious injury, or possible death.
Only trained service personnel should be used to remove the enclosure
from the pallet. Also, be sure you have a sucient number of service
personnel. Do not attempt to move enclosures by yourself.
Only UL® Listed ITE (Information Technology Equipment) units should
be installed inside the Great Lakes Wall Mount.
Be sure to read and follow all individual manufacturer equipment
manuals for safety and installation instructions.
Proper spacing is required when installing electrical equipment to avoid
electrical shock. Maintain minimum spacing between the accessories
and components and the computer enclosure assembly for safe
operation of the equipment when installed in accordance with the
National Electrical Code ANSI/NFPA 70-1999.
The ambient temperature operating range for the Great Lakes Wall
Mount and accessories is +50 to +95° F (+10 to +35° C).
The non-operating temperature is -4 to +140° F (-20 to +60° C).
2

INSTALLATION
Receiving and Unpacking
Inspect and report any damage before receiving. Unpack the wall
mount by carefully removing the corrugated carton and corners. Avoid
damaging the wall mount when removing packaging.
WARNING: Only trained service personnel should be used to unpack
and move the enclosure. Also, be sure you have a sucient number of
service personnel. Do not attempt to move enclosures by yourself.
WARNING: Be careful when moving enclosures before installation.
Sudden stops and starts, excessive force, obstructed routes, and
uneven oor surfaces may cause the enclosure to topple over.
MOUNTING INSTRUCTIONS
Wood Studded Wall
Once the location on the wall has been determined, inspect the wall
surface. The wall must be at and square in the horizontal and vertical
plane to ensure the Great Lakes Wall Mount closes correctly. If the wall
is not at and square, the use of shims may be required.
Wood studded wall mounting instructions apply to a 2" x 4" wood stud
wall with 3/4" plywood.
Recommended Mounting Hardware for Wood Studded Wall
For WM, WE, and 15WM Series:
Qty (4) 3/8 x 2" long Lag Bolts and 1" O.D. Flat Washer
For WMCM, WDX and NEMA 12K Series:
Qty (4) 3/8 x 2 1/2" long Lag Bolts and 1" O.D. Flat Washer
Masonry Wall Surface- For masonry wall surface, the installer must
provide all the appropriate hardware.
PROTECTIVE GROUNDING
Protective grounding studs are provided along with grounding jumper
wires that electrically bond the enclosure doors to the enclosure frame.
3

4
Part No. Height (in.) Width (in.) Depth (in.) RMU Wt. Cap. (lbs.)
GL24WMCM 24.00 24.00 30.54 12 150
GL36WMCM 36.00 24.00 30.54 19 250
GL48WMCM 48.00 24.00 30.54 25 350
GL24WDX 24.00 24.00 32.07 12 250
GL36WDX 36.00 24.00 32.07 19 300
GL48WDX 48.00 24.00 32.07 25 350
GL2418WM 24.00 21.25 18.00 12 100
GL24WM 24.00 21.25 24.54 12 150
GL36WM 36.00 21.25 24.54 19 250
GL48WM 48.00 21.25 24.54 25 350
GL24WD 24.00 24.00 32.13 11 250
GL36WD 36.00 24.00 32.13 18 300
GL48WD 48.00 24.00 32.13 25 350
GL15WM 15.38 22.25 17.66 7 100
GL24WE 24.00 36.10 20.5 10 350
GL240N12 24.00 24.00 24.00 12 150
GL360N12 36.00 24.00 24.00 19 250
GL480N12 48.00 24.00 24.00 26 300
WARNING: Only install equipment after the Wall Mount has been
properly secured. Do not move the Wall Mount assembly while loaded.
To maintain a uniform distribution of the mechanical load in the Wall
Mount, load the heaviest equipment rst, at the bottom of the Wall
Mount and load the lighter units at the top. Rated or maximum load
capacities for the Wall Mounts are as follows:
Loading Equipment

5
WARNING: To avoid injury to persons or loss of life, ground each
enclosure individually to the dedicated branch circuit ground.
Connecting Main Protective Grounding Stud to the Dedicated
Branch Circuit Ground- Connect the dedicated branch circuit ground
connector to the main protective grounding stud located inside on the
back of the rear section on the WMCM, WM, WDX, WE and inside on
the side of the 15WM Series using a listed ring or closed-loop terminal.
Connecting Main Protective Grounding Stud to the Protective
Bonding Conductors- Connect the middle wall mount frame on the
WS, WM and WD Series to the main protective grounding stud located
inside on the back of the rear section using a listed ring or closed-loop
terminal. Connect the wall mount frame on the WE and 15WM Series
to the main protective grounding stud located inside on the back of
the rear section on the WE Series and inside on the side of the 15WM
Series using a listed ring or closed-loop terminal. Connect the front
door to the grounding stud located inside at the side of the wall mount
frame using a listed ring or closed-loop terminal.
Parts Not Bonded to Protective Earthing Terminal- The following
parts are not eectively bonded to the protective earthing terminal: rails.
If these parts need to be bonded to the protective earthing terminal, do
so in accordance with Article 250 of the National Electrical Code.
POWER AND GROUNDI N G

24.00
HEIGHT
1. Mounting holes are designed for 3/8"hardware, 16" on center.
2. Use the template on the shipping box to locate your mounting holes.
3. Wall mount comes hinged right from the manufacturer. For mounting hinged left,
rotate wall mount 180o and follow additional steps on page 8.
WMCM SERIES WALL MOUN T
1", 2" and 3" nominal
concentric conduit
knockouts on top,
bottom and non-
hindged side of
rear section
Heavy duty
hinges
Front door
Center swing section
Offset 19" EIA
mounting rails;
2 pairs,
tapped #12-24
Independent
locking front
door & rear
section
Rear section
mounts to wall
Part No. Height RMU Mounting Holes
GL24WMCM 24.00" 12 19.00"
GL36WMCM 36.00" 19 24.00"
GL48WMCM 48.00" 25 36.00"
Provision for optional fan
assembly (7217WS)
FRONT VIEW WITHOUT DOOR
18.31
TO
17.75 INSIDE
RMU
19.23 OPENING
17.76 Inside
18.31 C-to-C
21.84 Open Access
FRONT VIEW WITH DOOR
24.00
HEIGHT
Swing handle
locking, keyed
1333 (optional
handles
available)
6
RMU
Cable tie
points on top,
bottom and
non-hinged
side

7
1.25 16.00
TO
6.75
1.4
0
KEYHOLEMOUNTING
CENTERED
3.758.2512.00
TOP/BOTTOM VIEW REAR VIEW
1", 2" and 3" rear section with
nominal concentric conduit
knockout
5.00
30.54
30.54
5.00
Usable depth = 28.00
Cable
management
area outside
of EIA on
hinge side
INTERNAL TOP VIEW
Front
door
29.00 USEABLE DEPTH
23.38 MAX RAIL SPACING
Usable depth = 28.00
23.38 Max rail spacing
3.41 Max cable
area width
Optional 1/4
turn “D” ring
Square
holes for
CM-25
1/4 turn
“D” rings
Cable management tie points
on rails; outside of EIA
SIDE VIEW
WMCM SERIES WALL MOUN T
1.25
Mounting Holes
Mounting
holes for
3/8"hardware
1.50
16.00 C-TO-C 6.75
12-24
U
#
.63
.63
.50
1.75
PATTERN
REPEATS
1.75
(1 RMU)
repeating
#12-24
Tapped
holes
EQUIPMENT
MOUNTING
RAIL DETAIL
1", 2" and 3" rear section with
nominal concentric conduit knockout
Provision for optional fan
assembly (7217WS)
12.00 8.25 3.75
Centered
.63
.63
.50
Side ventilation
Additional
tie points

Standard
at cam
supplied
Swing-latch handle;
pull out and rotate
to open and close
Move draw latch
to now top of
center section
Flip rear guide bracket and install
on now bottom of center section;
guide bracket should be oriented
with handle and pointing up
Remove center section
of gasket on now
bottom of rear section
Move receiving bracket to
now top of rear section
Add additional strip of
gasket (included) to
now top of rear section
REVERSING THE WALL MOUNT - LEFT HAND HINGE
Flip handle on
door 180o; flip
cam on inside of
handle 180o
8
WMCM SERIES WALL MOUN T
1", 2" and 3"
nominal concentric
conduit knockouts
on non-hinged side;
quantity of knockout
sets vary with wall
mount height
GL24WMCM -2 sets
GL36WMCM -3 sets
GL48WMCM -4 sets

9
1. Mounting holes are designed for 3/8" hardware, 16.00" on center.
2. Use the template on the shipping box to locate your mounting holes.
3. Wall mount comes hinged right from the manufacturer.
WDX SERIES WALL MOUN T
Removable gland plate exposes provision
for optional 2 fan assembly (7217WS)
Cover plate with 1", 2",
and 3" nominal concentric
conduit knockouts
Front door frame
with optional
inserts: solid steel,
mesh or plexi
Center swing section
Rear section
mounts to
wall
Independent
locking front
door & rear
section
21.26 OPEN ACCESS
18.31
TO
17.76 INSIDE
RMU
21.26 Open Access
FRONT VIEW WITHOUT DOOR
17.76 Inside
18.31 C-to-C
23.81
23.43
Swing
handle
locking,
keyed
1333
(optional
handles
available)
Part No. Height RMU Mounting Holes
GL24WDX 24.00" 12 18.82"
GL36WDX 36.00" 19 31.46"
GL48WDX 48.00" 25 34.76"
FRONT VIEW WITH DOOR
23.81
HEIGHT
Vent pattern

A A
3
USEABLE DEPTH = 28.00
32.07
5.2824.29
20.93 MAX
3.94
2.56
1
32.07
24.29 5.28
Usable depth = 28.00
1", 2", and 3" nominal concentric conduit
knockouts (knockouts on right side only)
3.94
2.56
RIGHT SIDE VIEW
29.00 USEABLE DEPTH
20.93 MAX
RAIL SPACING
Usable depth = 28.00
20.93 max
rail spacing
INTERNAL TOP VIEW
15.984
TO
3.89
18.82TO
3.94
19.921
TO
1.92
Open
area in
rear
19.921 C-to-C
15.984 C-to-C
1.92
3.89
Mounting Holes
REAR VIEW
.50
.63
.63
1
R
.50
.63
.63
1.75
(1 RMU)
repeating
3/8" square EIA mounting
holes with cage nuts (M6)
17.70
OPENING
Cover plate with 1", 2", and
3" nominal concentric conduit knockouts
17.70" opening
Provision for optional 2
fan assembly (7217WS)
TOP VIEW
WDX SERIES WALL MOUN T
10
EQUIPMENT MOUNTING
RAIL DETAIL

11
WDX SERIES WALL MOUN T
Remove bolt in
center section
alignment pin and
move to opposite
side
Notch gasket
for new
alignment
pin and cam
latch location
Move bottom
hinge collar pin
to opposite side
of rear section
(see step 3)
Remove collar
bolt on stop
bracket and
move, with
bushing, to
opposite side
weld nut in rear
section
Move
bumpers
to opposite
side of rear
section
Move quarter
turn latch to
opposite side of
rear section
Move hole
plugs in top of
rear section to
opposite side
1. Remove flat head bolt on top hinge mechanism
2. Lift center section off bottom hinge collar pin
3. After bottom hinge collar pin is moved, align with new hinge location on
center section
4. Move bushing in center section to opposite side and install top hinge mechanism
on opposite side
REVERSING THE CENTER SECTION
Move bushing in center section to
opposite side and install top hinge
mechanism on opposite side

WM SERI ES WALL MOUN T
1. Mounting holes are designed for 3/8" hardware, 16.00" on center.
2. Use the template on the shipping box to locate your mounting holes.
A
FRONT VIEW
(without Door)
19.17
21.25
18.31 TO
HEIGHT
10.63
12.00
RMU
E
18.31 C-to-C
FRONT VIEW WITHOUT DOOR
FRONT VIEW WITH DOOR
#12-24 UNC - 2B
Tapped Mounting Holes
(screws provided)
Part No. Height RMU Mounting Holes
GL2418WM 24.00" 12 19.00"
GL24WM 24.00" 12 19.00"
GL36WM 36.00" 19 31.00"
GL48WM 48.00" 25 21.50" (3)
21.25
19.17
RMU
HEIGHT
12.00
10.63
DETAIL A
DETAIL B
1
1
2
2
3
3
4
4
6
6
A A
C C
D D
DWG NO: REV
SHEET:
DRAWN
CHECKED & APP.
TITLE
DRAWING NOT TO SCALE
PART NUMBER:
QTY PER UNIT: 1
MATERIAL TYPE:
MATERIAL GAUGE:
FINISH:
GREAT LAKES CASE & CABINET CO., INC.
P.O. BOX 551 EDINBORO, PA 16412
PHONE (814) 734-7303 FAX (814) 734-3907
E-MAIL glcc@greatcabinets.com
Use of this document is subje ct to
a confidentiality and nondisclosure
agreement with Great Lakes Case
& Cabinet Co., Inc. (GLCC) and may
not be reproduced, disclosed or
utilized in whole or in part without
prior written authorization from GLCC.
NOTICE:
TOLERANCE UNLESS OTHERWISE NOTED:
ANGULAR +/- 1~
.XXXX +/- .010
.XXX +/- .015
.XX +/- .030
.X FOR REF. ONLY
UNLESS OTHERWISE SPECIFIED
ALL DIMENSIONS ARE IN INCHES
DIMENSIONAL LIMITS APPLY
AFTER APPLICATION OF FINISH
INTERPRET DRAWING PER ASME Y14.5M-1994
THIRD ANGLE
PROJECTION
DATE
DATE 11
ANDY 10/5/2007
Use latch supplied in hardware bag,
when horseshoe knockout is used
Rear section
1", 2" and 3" nominal
concentric conduit
knockouts and
horseshoe knockouts;
top & bottom rear
section
Continuous Hinges
on front door & rear
section
Front door
Option: 2, Fan unit ventilation
top or bottom mounting
Center swing section
19" EIA mounting rails;
2 pairs, tapped #12-24
Independent locking front
door & rear section
UL60950-1
UL2416
12

7.386.50
SECTION E-E
DEPTH
MAX RAIL SPACING
USABLE DEPTH
TOP/BOTTOM VIEW
INTERNAL SIDE VIEW
2 fan unit mounting
shown for GL24WM,
GL36WM and
GL48WM. 2 fan unit
is rotated 90oon
GL2418WM
1", 2", and 3" rear
section nominal
concentric conduit
knockouts
WM SERI ES WALL MOUN T
6.50
7.38
16.00 TO
2.55
1.50
MTGHOLES
3.50
REAR VIEW
Mounting holes for
3/8" hardware
1", 2", and 3" rear
section nominal
concentric conduit
knockouts
3.50
Mounting Holes
2.55
1.50
16.00 C to C
.63
.63
.50
1.75
(1 RMU)
repeating
#12-24 Tapped EIA mounting holes
Usable depth 22.00
Max. rail spacing
EQUIPMENT MOUNTING
RAIL DETAIL
GL2418WM usable
depth -16.00 "
13

WD SERIES WALL MOUN T
1. Mounting holes are designed for 3/8" hardware, 16.00" on center.
2. (Optional) For the ease of installation, mount only rear section to the wall rst.
Remove the hinge pins to detach the center swing section (see Detail A ). After
mounting rear section to the wall, reassemble center swing section and secure
it with hinge pins.
3. WS and WD handles can be found in the hardware bag.
Part No. Height RMU Mounting Holes
GL24WD 24.00" 11 14.00"
GL36WD 36.00" 18 26.00"
GL48WD 48.00" 25 19.00"
Rear section
Side ventilation
Front door with
keyed lock
Center swing section
19" EIA mounting rails;
2 pairs, tapped #12-24
24.00
RMU
HEIGHT
18.31 C-to-C
1", 2",3" and 4"
nominal
concentric
conduit
knockouts
1/2 -13 threaded holes
TYP (5) places
5.0
6.0
6.0
TOP/BOTTOM VIEW
14
FRONT VIEW WITHOUT DOOR
1", 2",3" and 4"
nominal
concentric
conduit
knockouts
Provision
for optional
2 fan
assembly
Provision for optional
2 fan assembly
Draw Latch
Draw Latch

WD SERIES WALL MOUN T
Mounting holes for
1/4" hardware
A
2.50 16.00
Mounting
holes
1", 2",3" and 4" nominal
concentric conduit knockouts
12.00
32.13
25.90 6.0
28.00 usable depth
1.75 (1 RMU)
repeating
.50
.63
.63
DETAIL A
Rear section
Rear section
support plate
Hinge pin
Nylon shoulder
washer
Lock pin
bracket
Lock pin
screw
Center swing section
15
REAR VIEW #12-24 Tapped EIA
mounting holes
INTERNAL SIDE VIEW
EQUIPMENT MOUNTING
RAIL DEATAIL

15WM SERIES WALL MOUN T
1. Unscrew specialty torx screw using the supplied torx screw bit. Fig 1 (A)
2. Remove back panel from wall mount. Fig 1
3. Mount back panel to wall using 3/8" hardware, 16" on center.
4. Once back panel is mounted, hang main body on mounted back panel. Fig 1 (B)
5. Secure main body using torx screw (keep bit in safe place for future use).
Note: Push down tabs (Detail A ) to get one RMU mounting on the back panel.
A
A
15.38
22.25
B
18.31 TO
16.00 TO
12.25
7RMU
12.00
TO
FRONT VIEW WITHOUT DOOR
FRONT VIEW WITH DOOR
18.31 C-to-C
16.00 C-to-C
12.00 C-to-C
“Spare” 1 RMU Mounting tabs
(shown extended)
Torx drive
security screws
Keyed lock
for front door
Door shown with
optional plexiglas
12.25
7 RMU
15.38
22.25
16

15WM SERIES WALL MOUN T
17.66
TOP/BOTTOM VIEW
SIDE VIEW
5/8" Knockout
1" and 1 1/2" Conduit knockouts
1/2" and 3/4" Conduit knockouts
INTERNAL SIDE VIEW
16.93
Usable depth from plexiglas to
back plate
Adjustable
equipment rails
.625
.500
.625
1.750
PATTERN
REPEATS
#10-32 Tapped EIA
mounting holes
1.750
Pattern
repeats
16.93
17.66
.500
.625
.625
EQUIPMENT MOUNTING
RAIL DETAIL
Provision for optional 1 fan
assembly (7217-04)
17

ISO VIEW COLLAPSED
C
24.00
17.50 (10 RMU)
20.51
18.31
TO
WE SERIES WALL MOU NT
1. Mounting holes are designed for 3/8" hardware, 16.00" on center.
2. Wall Mount must be mounted to three wall studs to achieve maximum
weight capacity.
SIDE VIEW WITHOUT DOORFRONT VIEW
ISO VIEW OPENED
1", 2" and 3" nominal
concentric conduit
knockouts,
20.51
17.50 (10 RMU)
24.00
18.31 C-to-C
Provision for optional 2 fan
assembly (7217WS)
Removable front panel
with key lock
18

19
A
19.45
3.00
6.05
12.0012.00
TOP/BOTTOM VIEW
REAR VIEW
6.05
5.75
12.0012.00
2.05
8.00
8.00
8.00
8.00
14.00
12.00
4.25
.
.
B
29.00 MAX RAIL SPACING
34.00 USABLE DEPTH
INTERNAL VIEW FRONT PANEL REMOVED
WE SERIES WALL MOU NT
Mounting
holes for
3/8" hardware
1.75
Pattern
repeats
3/8" Square holes
mounting with
cage nut (M6)
12.00 12.00 6.05 3.00
19.45
4.25 12.00 12.00 6.05
12.00
14.00
5.75
8.00 8.00 8.00 8.00 2.05
34.00 Usable depth
29.00 Max. rail spacing
.50 .63 .63
EQUIPMENT
MOUNTING
RAIL DETAIL

Center section
secured by
over-center
latches and
a key-locking
latch w/ dust
cover
NEM A 12K WALL MOUN T
1. Mounting holes are designed for 3/8" hardware, 16.00" on center.
2. Use the template on the shipping box to locate your mounting holes.
Hinged
center
section
Gland plates can be removed to
add optional fans or lters
3/8" lag screws recommended
for mounting into wall studs
Rear
section
Rear cable access for
2" nominal conduit; on
top and bottom
Part No. Height RMU
GL240N12 24.00" 12
GL360N12 36.00" 19
GL480N12 48.00" 26
FRONT VIEW WITHOUT DOOR
FRONT VIEW WITH DOOR
20
A
A
16.00
TO
(HEIGHT+2.50)
TO
24.00
(Height +2.50)
24.00
16.00
C-to-C
B
18.31
TO
17.86 INSIDE
(RMU)
22.12
OPEN ACCESS
HEIGHT-1.88"
OPENACCESS
Height - 1.88"
Open Access
18.31
C to C
17.86
Inside
(RMU)
Other manuals for WMCM Series
1
This manual suits for next models
23
Table of contents
Other Great Lakes Rack & Stand manuals

Great Lakes
Great Lakes SR Series User manual

Great Lakes
Great Lakes GL24SRD User manual

Great Lakes
Great Lakes GL840EZ-3042 User manual

Great Lakes
Great Lakes VRX Highlander User manual

Great Lakes
Great Lakes VRX User manual

Great Lakes
Great Lakes WR Series User manual

Great Lakes
Great Lakes SR Series User manual

Great Lakes
Great Lakes CMR-45U16 User manual

Great Lakes
Great Lakes UL60950-1 User manual

Great Lakes
Great Lakes VCMX Series User manual