Installation Method 2 14
•Strip cable to correct lengths as shown in diagram 14a.
•Break open cable entry ➄point then insert cable.
•Push the wires into the terminal block ➅until cable comes to a
dead stop.
•Peel open the terminal cover, so that terminal screws are visible, then
tighten screws and replace terminal cover, making sure that cover is fully
replaced.
Wiring Diagrams
The electrical connections must
be carried out by a qualified
electrician in accordance with
IEE or local regulations.
Warning: Isolate electricity
supply before starting work.
The fans are double insulated
and do not require an earth
connection.
The fans must be connected
to a double pole isolating switch
having contact separation of at
least 3mm.
When supplied from a 5 amp
lighting circuit no local fuse is required.
Fan Specification
220V/240V~50Hz. Power Consumption: 10.5W IP24
Cable sizes: Fixed flat wiring 2 core 1mm2
3 core 1/1.5mm2
Air flow rate: 17 L/S
Sound Pressure @ 3 m: 27.1 dB(A)
Timer Adjustment
Warning: Isolate electricity supply before starting work.
15 Remove anti-backdraught shutter spider ➆then PCB cover ➇at rear
end of fan by unscrewing the two PCB cover screws.
•The timer ➈is preset (approximately 20 minutes) but may be adjusted
by using a screwdriver and rotating clockwise to reduce time and
anticlockwise to increase time overrun.
Cleaning and Servicing the Fan
Warning: Always isolate fan from mains supply before cleaning. Do not use
solvents to clean this fan.
•Loosen the two retaining screws under grille (Do not remove screws),
then pull bottom of grille while lifting.
•The fan may now be cleaned using a brush or damp cloth.
Do not immerse in water.
•After cleaning replace internal grille.
Fuse
Double pole
isolating switch
Fanterminal
Light switch
Light
N
L
N
L
L1
Fuse
Double pole
isolating switch
N
L
Fanterminal
Light switch
Light N
L
L1
Timer
Basic
8652 Affresco Silent instr v5 28/7/06 10:32 Page 25
26.7
Installation Method 2 14
•Strip cable to correct lengths as shown in diagram 14a.
•Break open cable entry ➄point then insert cable.
•Push the wires into the terminal block ➅until cable comes to a
dead stop.
•Peel open the terminal cover, so that terminal screws are visible, then
tighten screws and replace terminal cover, making sure that cover is fully
replaced.
Wiring Diagrams
The electrical connections must
be carried out by a qualified
electrician in accordance with
IEE or local regulations.
Warning: Isolate electricity
supply before starting work.
The fans are double insulated
and do not require an earth
connection.
The fans must be connected
to a double pole isolating switch
having contact separation of at
least 3mm.
When supplied from a 5 amp
lighting circuit no local fuse is required.
Fan Specification
220V/240V~50Hz. Power Consumption: 10.5W IP24
Cable sizes: Fixed flat wiring 2 core 1mm2
3 core 1/1.5mm2
Air flow rate: 17 L/S
Sound Pressure @ 3 m: 27.1 dB(A)
Timer Adjustment
Warning: Isolate electricity supply before starting work.
15 Remove anti-backdraught shutter spider ➆then PCB cover ➇at rear
end of fan by unscrewing the two PCB cover screws.
•The timer ➈is preset (approximately 20 minutes) but may be adjusted
by using a screwdriver and rotating clockwise to reduce time and
anticlockwise to increase time overrun.
Cleaning and Servicing the Fan
Warning: Always isolate fan from mains supply before cleaning. Do not use
solvents to clean this fan.
•Loosen the two retaining screws under grille (Do not remove screws),
then pull bottom of grille while lifting.
•The fan may now be cleaned using a brush or damp cloth.
Do not immerse in water.
•After cleaning replace internal grille.
Fuse
Double pole
isolating switch
Fanterminal
Light switch
Light
N
L
N
L
L1
Fuse
Double pole
isolating switch
N
L
Fanterminal
Light switch
Light N
L
L1
Basic
8652 Affresco Silent instr v5 28/7/06 10:32 Page 25
Installation Method 2 14
•Strip cable to correct lengths as shown in diagram 14a.
•Break open cable entry ➄point then insert cable.
•Push the wires into the terminal block ➅until cable comes to a
dead stop.
•Peel open the terminal cover, so that terminal screws are visible, then
tighten screws and replace terminal cover, making sure that cover is fully
replaced.
Wiring Diagrams
The electrical connections must
be carried out by a qualified
electrician in accordance with
IEE or local regulations.
Warning: Isolate electricity
supply before starting work.
The fans are double insulated
and do not require an earth
connection.
The fans must be connected
to a double pole isolating switch
having contact separation of at
least 3mm.
When supplied from a 5 amp
lighting circuit no local fuse is required.
Fan Specification
220V/240V~50Hz. Power Consumption: 10.5W IP24
Cable sizes: Fixed flat wiring 2 core 1mm2
3 core 1/1.5mm2
Air flow rate: 17 L/S
Sound Pressure @ 3 m: 27.1 dB(A)
Timer Adjustment
Warning: Isolate electricity supply before starting work.
15 Remove anti-backdraught shutter spider ➆then PCB cover ➇at rear
end of fan by unscrewing the two PCB cover screws.
•The timer ➈is preset (approximately 20 minutes) but may be adjusted
by using a screwdriver and rotating clockwise to reduce time and
anticlockwise to increase time overrun.
Cleaning and Servicing the Fan
Warning: Always isolate fan from mains supply before cleaning. Do not use
solvents to clean this fan.
•Loosen the two retaining screws under grille (Do not remove screws),
then pull bottom of grille while lifting.
•The fan may now be cleaned using a brush or damp cloth.
Do not immerse in water.
•After cleaning replace internal grille.
Fuse
Double pole
isolating switch
Fanterminal
Light switch
Light
N
L
N
L
L1
Fuse
Double pole
isolating switch
N
L
Fanterminal
Light switch
Light N
L
L1
Timer
Basic
8652 Affresco Silent instr v5 28/7/06 10:32 Page 25
Installation Method 2 14
•Strip cable to correct lengths as shown in diagram 14a.
•Break open cable entry ➄point then insert cable.
•Push the wires into the terminal block ➅until cable comes to a
dead stop.
•Peel open the terminal cover, so that terminal screws are visible, then
tighten screws and replace terminal cover, making sure that cover is fully
replaced.
Wiring Diagrams
The electrical connections must
be carried out by a qualified
electrician in accordance with
IEE or local regulations.
Warning: Isolate electricity
supply before starting work.
The fans are double insulated
and do not require an earth
connection.
The fans must be connected
to a double pole isolating switch
having contact separation of at
least 3mm.
When supplied from a 5 amp
lighting circuit no local fuse is required.
Fan Specification
220V/240V~50Hz. Power Consumption: 10.5W IP24
Cable sizes: Fixed flat wiring 2 core 1mm2
3 core 1/1.5mm2
Air flow rate: 17 L/S
Sound Pressure @ 3 m: 27.1 dB(A)
Timer Adjustment
Warning: Isolate electricity supply before starting work.
15 Remove anti-backdraught shutter spider ➆then PCB cover ➇at rear
end of fan by unscrewing the two PCB cover screws.
•The timer ➈is preset (approximately 20 minutes) but may be adjusted
by using a screwdriver and rotating clockwise to reduce time and
anticlockwise to increase time overrun.
Cleaning and Servicing the Fan
Warning: Always isolate fan from mains supply before cleaning. Do not use
solvents to clean this fan.
•Loosen the two retaining screws under grille (Do not remove screws),
then pull bottom of grille while lifting.
•The fan may now be cleaned using a brush or damp cloth.
Do not immerse in water.
•After cleaning replace internal grille.
Fuse
Double pole
isolating switch
Fanterminal
Light switch
Light
N
L
N
L
L1
Fuse
Double pole
isolating switch
N
L
Fanterminal
Light switch
Light N
L
L1
Timer
Basic
8652 Affresco Silent instr v5 28/7/06 10:32 Page 25
Installation Method 2 14
•Strip cable to correct lengths as shown in diagram 14a.
•Break open cable entry ➄point then insert cable.
•Push the wires into the terminal block ➅until cable comes to a
dead stop.
•Peel open the terminal cover, so that terminal screws are visible, then
tighten screws and replace terminal cover, making sure that cover is fully
replaced.
Wiring Diagrams
The electrical connections must
be carried out by a qualified
electrician in accordance with
IEE or local regulations.
Warning: Isolate electricity
supply before starting work.
The fans are double insulated
and do not require an earth
connection.
The fans must be connected
to a double pole isolating switch
having contact separation of at
least 3mm.
When supplied from a 5 amp
lighting circuit no local fuse is required.
Fan Specification
220V/240V~50Hz. Power Consumption: 10.5W IP24
Cable sizes: Fixed flat wiring 2 core 1mm2
3 core 1/1.5mm2
Air flow rate: 17 L/S
Sound Pressure @ 3 m: 27.1 dB(A)
Timer Adjustment
Warning: Isolate electricity supply before starting work.
15 Remove anti-backdraught shutter spider ➆then PCB cover ➇at rear
end of fan by unscrewing the two PCB cover screws.
•The timer ➈is preset (approximately 20 minutes) but may be adjusted
by using a screwdriver and rotating clockwise to reduce time and
anticlockwise to increase time overrun.
Cleaning and Servicing the Fan
Warning: Always isolate fan from mains supply before cleaning. Do not use
solvents to clean this fan.
•Loosen the two retaining screws under grille (Do not remove screws),
then pull bottom of grille while lifting.
•The fan may now be cleaned using a brush or damp cloth.
Do not immerse in water.
•After cleaning replace internal grille.
Fuse
Double pole
isolating switch
Fanterminal
Light switch
Light
N
L
N
L
L1
Fuse
Double pole
isolating switch
N
L
Fanterminal
Light switch
Light N
L
L1
Timer
Basic
8652 Affresco Silent instr v5 28/7/06 10:32 Page 25
Installation Method 2 14
•Strip cable to correct lengths as shown in diagram 14a.
•Break open cable entry ➄point then insert cable.
•Push the wires into the terminal block ➅until cable comes to a
dead stop.
•Peel open the terminal cover, so that terminal screws are visible, then
tighten screws and replace terminal cover, making sure that cover is fully
replaced.
Wiring Diagrams
The electrical connections must
be carried out by a qualified
electrician in accordance with
IEE or local regulations.
Warning: Isolate electricity
supply before starting work.
The fans are double insulated
and do not require an earth
connection.
The fans must be connected
to a double pole isolating switch
having contact separation of at
least 3mm.
When supplied from a 5 amp
lighting circuit no local fuse is required.
Fan Specification
220V/240V~50Hz. Power Consumption: 10.5W IP24
Cable sizes: Fixed flat wiring 2 core 1mm2
3 core 1/1.5mm2
Air flow rate: 17 L/S
Sound Pressure @ 3 m: 27.1 dB(A)
Timer Adjustment
Warning: Isolate electricity supply before starting work.
15 Remove anti-backdraught shutter spider ➆then PCB cover ➇at rear
end of fan by unscrewing the two PCB cover screws.
•The timer ➈is preset (approximately 20 minutes) but may be adjusted
by using a screwdriver and rotating clockwise to reduce time and
anticlockwise to increase time overrun.
Cleaning and Servicing the Fan
Warning: Always isolate fan from mains supply before cleaning. Do not use
solvents to clean this fan.
•Loosen the two retaining screws under grille (Do not remove screws),
then pull bottom of grille while lifting.
•The fan may now be cleaned using a brush or damp cloth.
Do not immerse in water.
•After cleaning replace internal grille.
Fuse
Double pole
isolating switch
Fanterminal
Light switch
Light
N
L
N
L
L1
Fuse
Double pole
isolating switch
N
L
Fanterminal
Light switch
Light N
L
L1
Timer
Basic
8652 Affresco Silent instr v5 28/7/06 10:32 Page 25
Silent Fan Instructions.indd 25 02/02/2012 18:20